Wis. Admin. Code Department of Safety and Professional Services SPS 322.45 - Air conditioner and heat pump efficiencies
|
Equipment Type |
Minimum Efficiency |
Minimum Efficiency |
Test Procedure |
|
Split system and single package air conditioner, air cooled |
13.0 SEER |
ARI 210/240 |
|
|
Space constrained product-air conditioner |
12 SEER |
ARI 210/240 |
|
|
Through-the-wall air conditioner, air cooled, split system |
10.9 SEER (before Jan. 23, 2010) 12.0 SEER (as of Jan. 23, 2010) |
ARI 210/240 |
|
|
Through-the-wall air conditioner, air cooled, single package |
10.6 SEER (before Jan. 23, 2010) 12.0 SEER (as of Jan. 23, 2010) |
ARI 210/240 |
|
|
Split system and single package air conditioner, water and evaporatively cooled |
12.1 SEER |
ARI 210/240 |
|
|
Split system and single package heat pump, air cooled |
13.0 SEER |
7.7 HSPF |
ARI 210/240 |
|
Through-the-wall air conditioner and heat pump-split system |
10.9 SEER (before Jan. 23, 2010) 12.0 SEER (as of Jan. 23, 2010) |
7.1 HSPF (before Jan. 23, 2010) 7.4 HSPF (as of Jan. 23, 2010) |
ARI 210/240 |
|
Through-the-wall air conditioners and heat pumps-single package |
10.6 SEER (before Jan. 23, 2010) 12.0 SEER (as of Jan. 23, 2010) |
7.0 HSPF (before Jan. 23, 2010) 7.4 HSPF (as of Jan. 23, 2010) |
ARI 210/240 |
|
Space constrained products-heat pumps |
12 SEER |
7.4 HSPF |
ARI 210/240 |
|
Water source, heating mode, 68°F entering water |
4.2 COP |
ARI/ASHRAE 13256-1 |
|
|
Groundwater source, heating mode, 50°F entering water |
3.6 COP |
ARI/ASHRAE 13256-1 |
|
|
Ground source, heating mode, 32°F entering water |
3.1 COP |
ARI/ASHRAE 13256-1 |