Wis. Admin. Code Department of Safety and Professional Services SPS 327.50 - Electrical standards
(1) All electrical wiring, installations, equipment and materials used in the construction of camping units shall comply with the requirements of the Wisconsin Administrative Electrical Code, Vol. 2., ch. SPS 316, except as provided in this section.
(2) The requirements in NEC section 210.70(A) (2) (b) do not apply to a stairway for a deck. A light over the stairs of the deck is not required, but a light outside the door exiting to the deck is required.
(3) Except as provided in s. SPS 327.11, the inspection of the electrical construction of a camping unit is not required.
(4) No more than one receptacle outlet is required to be installed for the entire countertop space of a kitchen in a camping unit.
(5) The requirements for installation of fire alarms and smoke detectors in a camping unit are as provided in s. SPS 327.26.
(6) The rating of the disconnecting means and the ampacity of a conductor providing supply to a camping unit consisting of a framed structure may not be less than 50 amperes.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.