Wis. Admin. Code Department of Safety and Professional Services SPS 362.0705 - Exterior Walls
(1) CONNECTIONS BETWEEN BUILDINGS. This is a department exception to the requirements in IBC section 705.1: This section does not apply to connections between buildings that are in compliance with IBC section 3104.
(2) PROJECTIONS. Substitute Table 362.0705-2 for IBC Table 705.2.
Table 362.0705-2
Minimum Distance of Projection
|
Fire Separation Distance (FSD) |
Minimum Distance From Line Used to Determine FSD |
|
0 feet to 2 feet |
Projections not permitted |
|
Greater than 2 feet to 3 feet |
24 inches |
|
Greater than 3 feet to less than 30 feet |
24 inches plus 8 inches for every foot of FSD beyond 3 feet or fraction thereof |
|
30 feet or greater |
40 inches |