010-4 Wyo. Code R. §§ 4-30 - Gas Chlorinators, Booster Pump

(a) A booster pump water supply for the gas chlorinator injector shall:
(i) Be capable of producing the flow rate and pressure required by the manufacturer's specifications for proper operation of the equipment;
(ii) Be activated by a booster pump using re-circulated water supplied via the re-circulation system; and
(iii) Be interlocked to the filter pump to prevent feeding of chlorine when the re-circulation pump is not running.