010-4 Wyo. Code R. §§ 4-5 - Sanitizing Equipment, Practices
(a) Sanitizing
equipment and practices shall comply with the following:
(i) A chlorine or bromine residual or
residual of other sanitizers, approved by the regulatory authority shall be
maintained in the pool, spa or similar installation to meet the water quality
parameters outlined in chapter 5, section 1(a); and
(ii) Sanitizing equipment shall be selected
and installed so that continuous and effective sanitizing can be maintained
under all conditions.
(A) The use of
elemental gas chlorine shall be in accordance with sections 26 through 33 of
this chapter.
(b) Water shall be continuously sanitized by
a sanitizing agent.
(i) The residual must be
easily measured by simple and accurate field tests.
(c) If needed in order to maintain proper
chemical levels, chlorine, pH or other chemical control equipment which adjusts
chemical feed based on demand, shall be provided.
(d) If ancillary non-chlorine or non-bromine
sanitizer is used, it shall be used in addition to chlorine or bromine or other
approved equivalent unless the sanitizing method used is capable of producing a
measurable residual when tested with an accurate field test kit.
(e) Sanitizing agents shall be:
(i) Capable of being tested by a field test
kit; and
(ii) Registered for use by
the United States Environmental Protection Agency (EPA).