053-11 Wyo. Code R. §§ 11-2 - Use of Hydrogen
(a) Hydrogen
cylinders in use or in storage shall be secured to a fixed or stable
object.
(b) A regulator shall be
attached to the hydrogen cylinder before the cylinder valve is
opened.
(c) Flow of hydrogen from
the cylinder shall be in either permanently plumbed metal tubing or in single
wire braid flexible tubing.
(d)
Pressure from a hydrogen cylinder shall be controlled to a maximum of 40 pounds
per square inch.
(e) An excess flow
valve shall be attached to the low pressure outlet of the regulator which is
attached to the hydrogen cylinder.
(f) Hydrogen cylinder valves and lines shall
be tested under pressure before each initial use on site to detect any leaks.
Any leaks detected shall be repaired prior to actual use of the
hydrogen.