053-2 Wyo. Code R. § 56.4430 - Storage facilities
(a) Storage tanks
for flammable or combustible liquids shall be-
(1) Capable of withstanding working pressures
and stresses and compatible with the type of liquid stored;
(2) Maintained in a manner that prevents
leakage;
(3) Isolated or separated
from ignition sources to prevent fire or explosion; and
(4) Vented or otherwise constructed to
prevent development of pressure or vacuum as a result of filling, emptying, or
atmospheric temperature changes. Vents for storage of Class I, II, or IIIA
liquids shall be isolated or separated from ignition sources. These pressure
relief requirements do not apply to tanks used for storage of Class IIIB
liquids that are larger than 12,000 gallons in capacity.
(b) All piping, valves, and fittings shall
be-
(1) Capable of withstanding working
pressures and stresses;
(2)
Compatible with the type of liquid stored; and
(3) Maintained in a manner that prevents
leakage.
(c) Fixed,
unburied tanks located where escaping liquid could present a hazard to persons
shall be provided with-
(1) Containment for
the entire capacity of the largest tank; or
(2) Drainage of a remote impoundment area
that does not endanger persons. However, storage of only Class IIIB liquids
does not require containment or drainage to remote impoundment.