053-4 Wyo. Code R. § 75.1902 - Underground diesel fuel storage-general requirements
(a) All diesel fuel must be stored in:
(1) Diesel fuel tanks in permanent
underground diesel fuel storage facilities;
(2) Diesel fuel tanks on diesel fuel
transportation units in permanent underground diesel fuel storage facilities or
in temporary underground fuel storage areas; or
(3) Safety cans.
(b) The total capacity of stationary diesel
fuel tanks in permanent underground diesel fuel storage facilities must not
exceed 1000 gallons.
(c)
(1) Only one temporary underground diesel
fuel storage area is permitted for each working section or in each area of the
mine where equipment is being installed or removed.
(2) The temporary underground diesel fuel
storage area must be located-
(i) Within 500
feet of the loading point;
(ii)
Within 500 feet of the projected loading point where equipment is being
installed; or
(iii) Within 500
feet of the last loading point where equipment is being
removed.
(3) No more than
one diesel fuel transportation unit at a time shall be parked in the temporary
underground diesel fuel storage area.
(d) Permanent underground diesel fuel storage
facilities and temporary underground diesel fuel storage areas must be-
(1) At least 100 feet from shafts, slopes,
shops, or explosives magazines;
(2) At least 25 feet from trolley wires or
power cables, or electric equipment not necessary for the operation of the
storage facilities or areas; and
(3) In a location that is protected from
damage by other mobile equipment.
(e) Permanent underground diesel fuel storage
facilities must not be located within the primary escapeway.