(a) The owner or
operator of an oil terminal, crude oil transmission pipeline, exploration
facility, or production facility shall ensure that all facility oil piping
associated with that facility meets the requirements of this section.
(b) The owner or operator shall maintain
metallic facility oil piping containing oil in accordance with a written
corrosion control program.
(c)
Unless the owner or operator must comply with a more stringent requirement set
out in this section, the owner or operator shall ensure that facility oil
piping placed in service after December 30, 2008 is designed and constructed in
accordance with one of the following standards, as appropriate:
(1) American Society of Mechanical Engineers,
Process Piping,2004 Edition (ASME B31.3-2004), adopted by
reference;
(2) American Society of
Mechanical Engineers, Pipeline Transportation Systems for Liquid
Hydrocarbons and Other Liquids, 2002 Edition (ASME B31.4-2002),
adopted by reference;
(3) American
Society of Mechanical Engineers, Gas Transmission and Distribution
Piping Systems,2003 Edition (ASME B31.8-2003), adopted by
reference;
(4) another equivalent
standard approved by the department.
(d) The owner or operator shall ensure that
buried metallic facility oil piping placed in service between May 14, 1992 and
December 30, 2008 is protected from corrosion by installing protective coating
and cathodic protection appropriate for local soil conditions, and is of all
welded construction with no clamped, threaded, or similar connections for lines
larger than a one inch nominal pipe size.
(e) The owner or operator shall ensure that
buried facility oil piping placed in service after December 30, 2008
(1) is of all welded construction with no
clamped, threaded, or similar connections for lines larger than a one inch
nominal pipe size; and
(2) unless
constructed of a corrosion-resistant material approved by the department, is
(A) protected from corrosion by installing
protective coating; and
(B)
cathodically protected in accordance with (f) of this section.
(f) The owner or
operator shall ensure that, after December 30, 2008, cathodic protection
systems installed on facility oil piping are
(1) consistent with NACE International's
Standard Recommended Practice: Control of External Corrosion on
Underground or Submerged Metallic Piping Systems, 2002 edition (NACE
RP0169-2002), adopted by reference;
(2) designed by a corrosion expert;
and
(3) installed under the
supervision of a corrosion expert.
(g) The owner or operator shall ensure that,
if a piping segment of a buried facility oil piping installation is exposed for
any reason, the segment is carefully examined for damaged coating or corroded
piping in accordance with Section 9.2.6 of
Piping Inspection Code:
Inspection, Repair, Alteration, and Rerating of In-service Piping
Systems(API 570), adopted by reference in (j) of this section. If
active corrosion is found during that examination,
(1) the owner or operator shall implement
actions for control of future corrosion; and
(2) significant repairs or replacements must
meet the requirements of (c) and (e) of this section.
(h) An owner or operator of a buried facility
oil piping installation of metallic construction without cathodic protection
shall ensure that the piping
(1) is
electrically inspected by a corrosion expert for active corrosion at least once
every three years, but with intervals between inspection not exceeding 39
months; and
(2) in areas in which
active corrosion is found, is cathodicaily protected in accordance with (d) or
(f) of this section, as appropriate.
(i) The owner or operator shall ensure that
aboveground facility oil piping is supported consistent with the requirements
of Paragraph 321 of Process Piping(ASME B31.3-2004), adopted
by reference in (c) of this section.
(j) After December 30, 2007, unless the owner
or operator must comply with a more stringent requirement set out in this
section, the owner or operator shall ensure that all facility oil piping is
maintained and inspected under
(1) a program
developed in accordance with the requirements of the American Petroleum
Institute's (API) Piping Inspection Code: Inspection, Repair,
Alteration, and Rerating of In-service Piping Systems,Second Edition,
October 1998, Addendum 1, February 2000, Addendum 2, December 2001, and
Addendum 3, August 2003 (API 570), adopted by reference; or
(2) another equivalent program approved by
the department.
(k)
Unless the owner or operator must comply with a more stringent requirement set
out in this section, the operation and maintenance of a cathodic protection
system on facility oil piping must
(1) be
consistent with Section 10 of Standard Recommended Practice: Control of
External Corrosion on Underground or Submerged Metallic Piping
Systems(NACE RP0169-2002), adopted by reference in (f) of this
section;
(2) include a cathodic
protection survey by a corrosion expert or qualified cathodic protection
tester; and
(3) include maintenance
of test lead wires, in a condition that enables electrical measurements to be
taken to determine the effectiveness of a cathodic protection system.
(l) The owner or operator of above
ground facility oil piping, other than piping specified in (m) of this section,
shall ensure that the piping is protected from atmospheric corrosion by the
application of a protective coating or by the use of corrosion-resistant
material unless the owner or operator demonstrates by test, investigation, or
experience appropriate to the environment of the piping segment that the
anticipated extent of corrosion will
(1) only
be a light surface oxide; or
(2)
not affect the safe operation of the piping before the next scheduled
inspection under a program developed under (j) of this section.
(m) The owner or operator of
aboveground facility oil piping located outside a sufficiently impermeable deck
on board a marine structure or at a soil-to-air interface shall ensure that the
piping is protected against external corrosion through the application of a
protective coating or by the use of corrosion-resistant materials.
(n) The owner or operator of aboveground
facility oil piping and valves shall ensure that the piping and valves are
(1) visually checked for leaks or damage
during routine operations or at least monthly; and
(2) appropriately protected from damage by
vehicles.
(o) The owner
or operator of facility oil piping that is removed from service for more than
one year shall ensure that the facility oil piping is free of accumulated oil,
identified as to origin, marked on the exterior with the words "Out of Service"
and the date taken out of service, secured in a manner to prevent unauthorized
use, and either blank flanged or otherwise isolated from the system. For piping
removed from service after December 30, 2006, the owner or operator shall
notify the department when facility oil piping is removed from service and when
the actions required by this subsection are completed.
(p) In this section,
(1) "active corrosion" means continuing
corrosion that, unless controlled, could result in a spill;
(2) "buried" means covered or in contact with
soil;
(3) "protective coating"
means a durable external coating that is applied to piping and that
(A) isolates the external surface of the
piping from the environment;
(B)
has sufficient adhesion to effectively resist underfilm migration of
moisture;
(C) is sufficiently
ductile to resist cracking in the range of temperatures encountered during
bending, handling, installation, and operation;
(D) has sufficient strength and adhesion, or
is otherwise protected, to resist mechanical damage;
(E) resists degradation throughout the range
of temperatures encountered during storage, shipping, construction, and
operation; and
(F) is compatible
with the cathodic protection system in use on the piping;
(4) "removed from service" means not in
regular use for the service intended and not included in a regular maintenance
and inspection program in accordance with (j) of this section;
(5) "submerged" means located below the
surface of waters of the state.