18 AAC 78.045 - Operation and maintenance of corrosion protection
(a) The owner or
operator of a steel UST with corrosion protection shall comply with the
requirements of this section to ensure that a release caused by corrosion is
prevented until the UST is permanently closed or undergoes a change-in-service
under 18 AAC 78.085.
(b) A corrosion protection system must be
operated and maintained to continuously provide corrosion protection to the
metal components of that portion of the tank and piping that routinely contains
petroleum and th at is in contact with the ground. This requirement applies to
single and double wall steel tanks and piping. For purposes of this subsection,
piping that routinely contains petroleum includes all product piping, except
for vent lines and except for most tank fill pipe configurations.
(c) A UST equipped with a cathodic protection
system must be inspected for proper operation by a cathodic protection tester
who is certified under 18 AAC 78.4 10 in accordance with the following
requirements:
(1) a cathodic protection
system must be tested not later than six months after installation and at least
every three years after that, or according to another reasonable testing
schedule approved by the department; and
(2) the criteria used to determine if
cathodic protection is adequate as required under this section must be in
accordance with one of the following requirements:
(A) NACE International Standard RP0285-2002,
Standard Recommended Practice Corrosion Control of Under ground Storage Tank
Systems by Cathodic Protection, 2002, adopted by reference.
(B) NACE International Test Method
TM0101-2012, Measurement Techniques Related to Criteria (or Cathodic Protection
on underground Storage Tank Systems, March 2012, adopted by
reference;
(C) NACE International
Test Method TM0497-2012, Measurement Techniques Related to Criteria (or
Cathodic Protection on underground or Submerged Metallic Piping Systems, June
2012, adopted by reference;
(D)
Steel Tank Institute Recommended Practice R051, Cathodic Protection Testing
Procedures for STl-P3® USE, January 2006, adopted by reference;
(E) NACE International Standard Practice
SP0169-2007, Control of' External Corrosion 011 Underground or Submerged
Metallic Piping Systems, reaffirmed March 15, 2007, adopted by reference;
or
(F) another standard that is no
less protective of human health and safety and the environment and approved by
the department.
(d) Repealed 9/27/2018.
(e) A UST with an impressed current cathodic
protection system must be inspected every 60 days to ensure that the equipment
is running properly. The owner or operator shall document the findings of each
inspection. The owner or operator may use a form provided by the department or
an equivalent form to document those findings. If the inspection of the
impressed current cathodic protection system indicates a redline of zero, the
owner or operator shall notify the department and take corrective action to
investigate and, if necessary, to correct the problem.
(f) For a UST with cathodic protection,
records of the operation of the cathodic protection system must be maintained
in accordance with
18 AAC 78.056 to demonstrate
compliance with the performance standards in this section. These records must
provide the following:
(1) the results of the
last three inspections required in (e) of th is section; and
(2) the results of testing from the last two
in spections required in (c) of this section.