Ariz. Admin. Code § R20-5-407 - Inspection of Boilers, Lined Hot Water Storage Heaters, Direct Fired Jacketed Steam Kettles and Issuance of Inspection Certificates
A. An Authorized
Inspector shall comply with the guidelines set forth in The National Board
Inspection Code, ANSI/NB-23- 2019 Edition, incorporated by reference. This
incorporation does not include any later amendments or editions of the
incorporated material. A copy of this referenced material is available for
review at the Industrial Commission of Arizona, 800 W. Washington Street,
Phoenix, AZ 85007 and may be obtained from the National Board of Boiler and
Pressure Vessel Inspectors, 1055 Crupper Avenue, Columbus, OH 43229-1183 or at
http://www.nationalboard.org/.
B. If an Owner, Operator, or User fails to
comply with the requirements for an inspection or pressure test under this
Article, the Division shall withhold the Inspection Certificate until the
Owner, Operator, or User complies with the requirements.
C. An Authorized Inspector shall not engage
in the sale of any object or device relating to, or equipment associated with,
Boilers, Lined Hot Water Heaters, or Direct Fired Jacketed Steam
Kettles.
D. Under A.R.S. §
23-485(D), the
Special Inspector shall file an inspection report within 30 days of an
inspection by entering data into the Division's Web-based inspection entry
form, by submitting a paper inspection report issued by the Division, or by
electronic transfer of data. Whatever form of data transfer a Special Inspector
chooses, there shall be no cost to the Division. The inspection report shall
contain the following:9.
10. Whether the object is active, inactive,
Out-of-Service, standby, or scrapped;
10.
11. MAWP permitted or
allowed;
11.
12. National Board registration number;
12.
13.
Name of the manufacturer and the year the object was built;
13.
14.
Special location in plant, if applicable;
14.
15. Boiler
type;
15.
16. Purpose of the Boiler;
16.
17. Specify type of
fuel used;
17.
18. Whether the firing method is automatic, manual, or unknown;
18.
19. Whether the fuel train is in compliance with
CSD-1, NFPA 85, Z21.10.3 or other;
20.
21.
Size/ input rate, as applicable;
21.
23. Whether the heating surface type is stamped,
computed, or unknown;
22.
24. Minimum Safety
Valve relief capacity required;
23.
25. Whether the
minimum Safety Valve relief capacity type is BTU/Hr, lbs/Hr or
unknown;
24.
26. Number of temperature/pressure controls, as
applicable;
25.
27. Owner number assigned by the Owner to specifically
identify object's location;
26.
28. Inspection
date;
27.
29. Whether the Inspection Certificate is
posted;
28.
30. Safety Valve total capacity;
29.
32. Safety Valve #1 set pressure;
30.
33.
Safety Valve #2 set pressure;
31.
34. Safety Valve #3
set pressure;
32.
36. Whether the object
has been hydro tested;
33.
37. Hydro Test (psi),
if applicable;
34.
38. Whether Pressure/Altitude Gage was
tested;
35.
39. Whether the condition of the object is okay to
issue an Inspection Certificate;
36.
40. Inspection
comments, condition of Boiler;
37.
41. Violations
noted;
38.
42. Inspector name and Special Inspector number;
and
39.
43. National Board Commission number
.
1. Whether it is a
Certificate or non-Certificate Inspection;
2. Whether it is an Internal Inspection,
External Inspection, or both;
3.
Name of location, address and phone number of the object;
4. Name, address and phone number of owner or
responsible party;
5. Contact
person's name and phone number at the inspection location;
6. State Identification Number;
7. Inspection Certificate due date;
8. Inspection Certificate duration;
9. Install/reinstall date, if
known;
22. Size classification
(HS/BTU/Kw);
31. Safety Valve total capacity type (PPH/Hr
or BTU/Hr);
35. Safety Valve code
stamping (Example: V,HV,UV,UV3.TV,TD, OR NV);
E. The Division shall
issue to an Owner, Operator, or User an Inspection Certificate within 30
calendar days of receipt of an inspection report that documents a Boiler, Lined
Hot Water Heater, or Direct Fired Jacketed Steam Kettle that complies with the
Act and this Article. An Owner, Operator, or User of a Boiler, Lined Hot Water
Heater, or Direct Fired Jacketed Steam Kettle shall post the Inspection
Certificate in the establishment where the Boiler, Lined Hot Water Heater, or
Direct Fired Jacketed Steam Kettle is located.
F. An Owner, Operator, or User shall ensure
that an Authorized Inspector tags or stamps a steam Boiler with an
identification number immediately after installing, but before operating, a new
steam Boiler, or when an Authorized Inspector performs an initial Certificate
Inspection of an existing steam Boiler. The identification number shall be at
least 5/16" in height and in the following format: AZ-# # # #.
G. The Division shall mark with a metal dye
stamp a Boiler or Lined Hot Water Heater identified by the Division as not safe
for further service, with the code "XXX AZ8 XXX" which shall designate that the
Boiler or Lined Hot Water Heater is Condemned.
H. For any conditions not covered by this
Article, the applicable provisions of the ASME Code that was in effect in
Arizona at the time of the installation of the Boiler or Lined Hot Water Heater
shall apply.