Fla. Admin. Code Ann. R. 62-252.300 - Gasoline Dispensing Facilities - Stage I Vapor Recovery
(1) Applicability. The requirements of this
rule section shall apply to:
(a) All gasoline
dispensing facilities with a monthly gasoline throughput of 20, 000 gallons
(75, 700 liters) or more located in any area designated as a nonattainment area
or air quality maintenance area for ozone under Rule
62-204.340, F.A.C.;
(b) All gasoline dispensing facilities in the
state with a monthly throughput of 10, 000 gallons (37, 850 liters) or more
that begin operation on or after August 1, 2007;
(c) All gasoline dispensing facilities in the
state with a monthly throughput of 10, 000 gallons (37, 850 liters) or more
that are not otherwise subject to this rule pursuant to paragraph
62-252.300(1)(a) or
(b), F.A.C., and whose storage tanks are
upgraded or replaced to meet the secondary containment requirements for
integral piping in Rule
62-761.510, F.A.C., and are
returned to operation on or after August 1, 2007; and,
(d) All gasoline dispensing facilities in the
state with a monthly throughput of 10, 000 gallons (37, 850 liters) or more
that are not otherwise subject to this rule pursuant to paragraph
62-252.300(1)(a), (b) or
(c), F.A.C.
(2) Prohibition. No owner or operator of a
gasoline dispensing facility subject to the provisions of this section shall
transfer or cause or allow the transfer of gasoline from any gasoline cargo
tank into any stationary storage tank located at any such gasoline dispensing
facility unless the stationary storage tank is equipped for submerged filling
and the vapors displaced from the storage tank during filling are processed by
a Stage I vapor recovery system in accordance with subsection
62-252.300(3),
F.A.C.
(3) Control Technology
Requirements.
(a) The Stage I vapor recovery
system required by this rule section shall conform with the equipment
specifications of the U.S. Environmental Protection Agency document, "Design
Criteria for Stage I Vapor Control Systems - Gasoline Service Stations, " dated
November 1975, with the exception of Attachment A, hereby adopted and
incorporated by reference.
(b) The
Stage I vapor recovery system piping shall include pressure-vacuum vents and be
leak-tight.
Notes
Rulemaking Authority 403.061 FS. Law Implemented 403.031, 403.061, 403.087 FS.
Formerly 17-2.650(1)(f)11., Amended 2-2-93, Formerly 17-252.300, Amended 5-9-07, 9-24-13.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.