Fla. Admin. Code Ann. R. 62-296.508 - Petroleum Liquid Storage
(1)
Applicability.
(a) The control technology set
forth in Rule 62-296.508, F.A.C., shall apply
to all fixed roof storage vessels with capacities equal to or greater than 42,
000 gallons (159, 000 liters; nominal design 1, 000 barrels (bbls.)) containing
petroleum liquids whose true vapor pressure is greater than 1.50 psia (10.3
kilopascals) but shall not be used if the petroleum liquid has a true vapor
pressure of 11.0 psia (76 kilopascals) or greater under actual storage
conditions.
(b) Rule
62-296.508, F.A.C., shall not
apply to volatile petroleum liquid storage vessels:
1. Equipped with external floating roofs
before the effective date of this rule, or
2. Having capacities equal to or less than
420, 000 gallons (1, 590, 000 liters; nominal design 10, 000 bbls.) located at
oil field production sites and used to store produced oil and condensate prior
to lease custody transfer.
(2) Control Technology. Except as provided
under paragraph 62-296.508(1)(b),
F.A.C., no owner or operator of an affected emissions unit under paragraph
62-296.508(1)(a),
F.A.C., shall permit the use of such emissions unit unless:
(a) The emissions unit has been retrofitted
with an internal floating roof equipped with a closure seal, or seals, to close
the space between the roof edge and tank wall, or the emissions unit has been
retrofitted with an equally effective alternative control; and,
(b) The emissions unit is maintained such
that there are no visible holes, tears, or other openings in the seal or any
seal fabric or materials; and,
(c)
All openings, except stub drains are equipped with covers, lids, or seals such
that:
1. The cover, lid, or seal is in the
closed position at all times except on demand for sampling, maintenance,
repair, or necessary operational practices; and,
2. Automatic bleeder vents are closed at all
times except when the roof is floated off or landed on the roof leg supports;
and,
3. Rim vents, if provided, are
set to open when the roof is being floated off the roof leg supports or at the
manufacturer's recommended setting.
(3) Test Methods and Procedures. All
emissions tests performed pursuant to the requirements of this rule shall
comply with the following requirements.
(a)
Internal Floating Roof and Roof Seals. The test method for volatile organic
compounds shall be p. 6-2 of EPA 450/2-77-036, incorporated and adopted by
reference in Chapter 62-297, F.A.C.
(b) Add-on Control Device.
1. Destructive. The test method for volatile
organic compounds shall be EPA Method 25, as described at 40 C.F.R. Part 60,
Appendix A-7, adopted and incorporated by reference at Rule
62-204.800, F.A.C., or
Attachment 3 of EPA 450/2-78-041, Alternate Test Method for Direct Measurement
of Total Gaseous Organic Compounds Using a Flame Ionization Analyzer, adopted
and incorporated by reference in Chapter 62-297, F.A.C.
2. Non-destructive. The test method for
volatile organic compounds shall be VOC Capture Efficiency Test Procedures as
described at Rule 62-297.450, F.A.C. The sampling
time for each capture efficiency test run shall be at least 8 hours, unless
otherwise approved by the Department pursuant to Rule
62-297.620,
F.A.C.
(c) Test
procedures shall meet all applicable requirements of Chapter 62-297,
F.A.C.
Notes
Rulemaking Authority 403.061 FS. Law Implemented 403.031, 403.061, 403.087 FS.
Formerly 17-2.650(1)(f)8., 17-296.508, Amended 11-23-94, 1-1-96, 10-6-08, 7-10-14.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.