Fla. Admin. Code Ann. R. 62-524.550 - Well Construction Requirements for New Potable Water Well Permitting in Delineated Areas
(1) New potable
water wells shall comply with the minimum construction standards contained in
Rule 62-532.500, F.A.C. Additional
requirements may be assigned by the permitting authority relative to depth
restrictions, location of screened or open hole interval, and length of casing
where warranted by local specific information.
(2) Methods for constructing new potable
water wells shall be limited to rotary drilling, boring, or other method
specifically approved by the permitting authority pursuant to subsection
62-524.700(1),
F.A.C., which meets the water well construction criteria in Rule
62-532.500, F.A.C., except as
required below.
(a) Well casing and liner
pipe shall be new, free of breaks, corrosion and dents, straight and true, and
not out of round. Welded or seamless black or galvanized steel pipe or casing,
or stainless steel pipe or casing, or approved types of nonmetallic pipe shall
be used for well casing or liner pipe.
(b) Solvent-bonded couplings shall be
prohibited in areas with known ground water contamination which includes
solvent components.
(c) To prevent
the interchange of water and loss of artesian pressure, contaminated,
unconfined ground water intervals shall be sealed off prior to drilling through
the underlying confining interval. Uncontaminated, unconfined ground water
intervals shall be sealed off or otherwise protected prior to drilling into
deeper, contaminated ground waters.
(d) For any well casing installed in a bore
hole, the annular space shall be filled from bottom to top with not less than a
nominal two inch thickness of neat cement grout.
(e) A concrete pad measuring three feet by
three feet by four inches shall be constructed around the elevated portion of
the casing so that the casing is centered in the pad to prevent soil erosion
and seepage of surface contamination into the annular space.
(f) A minimum elevation of one foot of casing
above land surface shall be required.
(g) A raw water tap shall be provided to
allow sampling of the well before exposure to storage or treatment.
(h) The well casing shall be visibly and
permanently marked above the land surface with the latitude and longitude and
the permit number issued by the permitting authority for that well.
(i) To the extent practical, potable water
wells shall be located outside an area delineated under Rule
62-524.420, F.A.C.
(j) Where the source of contamination and the
direction of ground water flow are known, in an area delineated under Rule
62-524.420, F.A.C., to the
extent practical, potable water wells shall be located upgradient of the
source.
(k) New potable water wells
shall be located on ground least subject to inundation.
(l) Any new potable water well constructed
within a delineated area that does not meet the construction standards of this
section shall be abandoned and plugged in accordance with Rule
62-532.500, F.A.C., and
applicable water management district rules.
Notes
Rulemaking Authority 373.309, 403.061, 403.062 FS. Law Implemented 373.309 FS.
New 5-16-89, Amended 3-25-90, 3-3-92, Formerly 17-524.550, Amended 12-9-96.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.