The following minimum standards shall apply to the
construction, repair, and abandonment of water wells in the State unless
exempted by a water management district rule with the concurrence of the
Department. Operation requirements for public water systems are included in
Chapter 62-555, F.A.C., and operation requirements for limited use public water
systems, multifamily water systems, and private water systems are included in
Chapter 64E-8, F.A.C.
(1) Well Casing,
Liner Pipe, Coupling, and Well Screen Requirements.
(a) Well casing, liner pipe, coupling, and
well screen shall be new or in like new condition. Such well casing, liner
pipe, coupling, or well screen shall not be used unless free of breaks,
corrosion and dents, is straight and true, and not out of round. Welded or
seamless black or galvanized steel pipe or casing, or stainless steel pipe or
casing, or approved types of nonmetallic pipe shall be used for well casing or
liner pipe. All well casing shall conform to one of the following standards:
American Society for Testing and Materials (ASTM) A53/A53M-99b (1999), A135-01
(2001), A252-98 (1998), A589-96 (1996), or American Petroleum Institute (API)
5L-2000 (2000). Well casing that conforms to any of the aforementioned ASTM or
API standards shall also conform to the 2000 American National Standard
Institute for Welded and Seamless Wrought Steel Pipe (ANSI/ASME B36.10M-2000).
All well casing shall be stenciled with the applicable standard, or proper
documentation of manufacturer specifications must be supplied to the permitting
authority upon request. Copies of these standards may be obtained from the
American Society for Testing and Materials, 100 Barr Harbor Drive, P. O. Box
C700, West Conshohocken, PA 19428-2959; the American Petroleum Institute, 1220
L Street NW, Washington, DC 20005-4070; and the American National Standards
Institute, 1819 L Street NW, Washington, DC 20036, respectively.
(b) Black or galvanized steel casing
installed by driving shall not have less than the dimensions and weights
specified below.
|
Nominal
|
Outside
|
Wall
|
Plain End
|
|
Size
|
Diameter
|
Thickness
|
Weight
|
|
(in.)
|
(in.)
|
(in.)
|
(lbs./ft.)
|
|
1.25
|
1.660
|
.140
|
2.27
|
|
1.5
|
1.900
|
.145
|
2.72
|
|
2
|
2.375
|
.154
|
3.65
|
|
3
|
3.5
|
.216
|
7.58
|
|
3.5
|
4.000
|
.226
|
9.11
|
|
4
|
4.5
|
.237
|
10.79
|
|
5
|
5.563
|
.258
|
14.62
|
|
6
|
6.625
|
.280
|
18.97
|
|
8
|
8.625
|
.277
|
24.70
|
|
10
|
10.750
|
.307
|
34.24
|
|
12
|
12.750
|
.330
|
43.77
|
|
14-30
|
|
.375
|
|
|
more than 30
|
|
.500
|
|
Note: A 4 inch nominal size casing with a wall thickness of
.188 inches and a plain end weight of 8.66 pounds/foot may be used if it
conforms to standard API 5L-2000, Grade B, 60 KSI tensile strength. Other
casing that meets these minimum tensile strength standards shall be acceptable.
For example, A53/A53M-99b, Grade B, may also be substituted.
(c) Black or galvanized steel casing or liner
pipe set into place without driving shall not have less than the dimensions and
weights specified below.
|
Nominal
|
Outside
|
Wall
|
Plain End
|
|
Size
|
Diameter
|
Thickness
|
Weight
|
|
(in.)
|
(in.)
|
(in.)
|
(lbs./ft.)
|
|
1.25
|
1.660
|
.140
|
2.27
|
|
1.5
|
1.900
|
.145
|
2.72
|
|
2
|
2.375
|
.154
|
3.65
|
|
2.5
|
2.875
|
.203
|
5.79
|
|
3
|
3.500
|
.188
|
6.65
|
|
3.5
|
4.000
|
.188
|
7.65
|
|
4
|
4.500
|
.188
|
8.66
|
|
5
|
5.500
|
.188
|
10.79
|
|
6
|
6.625
|
.188
|
12.92
|
|
8
|
8.625
|
.188
|
16.94
|
|
10-16
|
|
.250
|
|
|
>16
|
|
.375
|
|
(d)
Stainless steel pipe used for casing or liner pipe shall be Schedule 10S of the
American National Standards Institute (ANSI/ ASME B36.19M-1985), or stronger
classification.
(e) Polyvinyl
Chloride (PVC) pipe may be used for well casing, liner pipe, and well screens.
Any PVC pipe used for well construction or repair shall at a minimum meet the
specifications for Schedule 40 or Standard Dimension Ratio (SDR) 21. The
appropriate water management district shall require the use of stronger PVC
casing if necessary to protect the integrity of the well.
(f) The Department shall approve a well
casing or liner pipe not otherwise specified in paragraphs
62-532.500(1)(a) through
(e), F.A.C., if the applicant makes a
showing, certified by a professional engineer, to justify that such use would
provide an equivalent material strength and durability. The following material
has been approved pursuant to this procedure: DNS Well-Cor, Allied Tube and
Conduit, A Division of Grinnel Corporation, 1440 Massaro Boulevard, Tampa,
Florida, 33619.
|
Nominal
|
Outside
|
Wall
|
|
Size
|
Diameter
|
Thickness
|
|
(in.)
|
(in.)
|
(in.)
|
|
1.25
|
1.638
|
.085
|
|
2
|
2.360
|
.095
|
|
4
|
4.466
|
.150
|
(g)
Well casing, liner pipe, coupling, and well screens used for potable water well
construction or repair shall conform to 2008 NSF International
Standard/American National Standard NSF/ANSI 14-2008e, Plastics Piping System
Components and Related Materials, or NSF International Standard/American
National Standard NSF/ANSI 61-2008, Drinking Water System Components - Health
Effects, both of which are adopted and incorporated by reference herein. Copies
of these copyrighted standards may be obtained from NSF International, P. O.
Box 130140, Ann Arbor, MI 48113-0140.
(h) Steel well casing and liner pipe shall be
joined in a watertight manner by threaded couplings, electrical welding
methods, or other methods approved by the appropriate water management district
which provide equivalent protection. PVC pipe shall be joined by solvent bonded
couplings, threaded couplings, heat welding, or other methods approved by the
appropriate water management district which provide equivalent
protection.
(i) Nonmetallic and
stainless steel well casing or liner pipe shall not be installed by driving
unless prior approval is obtained from the appropriate water management
district based on a demonstration that the integrity of the well casing or
liner pipe will be maintained. For well casing or liner pipe installed by
driving, the casing or pipe shall not butt together inside threaded couplings
unless the joint is electrically welded so as to be completely watertight. A
drive shoe is required for use on casing or pipe installed by driving unless
prior approval is obtained from the appropriate water management district based
on a demonstration that a drive shoe is not necessary to maintain the integrity
of the casing or pipe.
(2) Geothermal well heat exchanger pipe and
fitting materials shall meet the standards and specifications in the document
Closed-Loop/Geothermal Heat Pump Systems Design and Installation Standards,
Revised Edition 2008, published by the International Ground Source Heat Pump
Association, Oklahoma State University, which is adopted and incorporated by
reference herein. In addition, the reference Closed-Loop/Ground-Source Heat
Pump Systems Installation Guide, 1988, Oklahoma State University, is excellent
and is included here as a guidance document. Copies of all of these references
may be obtained from the International Ground Source Heat Pump Association,
Oklahoma State University, 374 Cordell South, Stillwater, OK 74078-8018.
(a) All geothermal well heat exchanger pipe
and fitting materials shall be stenciled with the applicable standard, or
proper documentation of manufacturer specifications must be supplied to the
permitting authority upon request.
(b) The Department or the permitting
authority shall approve geothermal well heat exchanger pipe and fitting
materials not meeting the standards and specifications in the document adopted
in subsection
62-532.500(2),
F.A.C., if the applicant makes a showing, certified by a professional engineer,
to justify that such use would provide an equivalent material strength and
durability.
(3) Well
Construction Criteria.
(a) Well casings,
which are seated into unconsolidated earth material, shall extend from the
upper terminus of the well to the well screen. The well screen shall be
attached to the casing with a watertight seal.
(b) Well casings that are seated into a rock
layer or other consolidated earth material, shall be continuous and shall
extend from the upper terminus of the well to no less than the top of the
uppermost consolidated unit. Wells constructed of telescoping casings shall be
considered as a continuous casing provided the grout requirements are met. The
lower terminus of the well casing shall extend to or below the water level of
the aquifer intended to supply water to the well or receive fluids from the
well. In addition, all caving zones below the uppermost consolidated unit shall
be cased.
(c) Geothermal wells
shall be grouted in accordance with subparagraph
62-532.500(3)(i)
6., F.A.C.
(d) For public water
system wells using telescoped casing, the casing shall be overlapped by not
less than 20 feet when increases or reductions occur in casing size, unless
another footage is approved by the appropriate water management district or
permitting authority. Not less than two centralizing spacers shall be used in
the overlapped sections, and the annular space in the overlapped sections shall
be completely sealed with cement grout.
(e) Prevention of Interchange of Water and
Loss of Artesian Pressure. All water wells shall be properly designed and
constructed to prevent an interchange of water between water bearing zones that
may result in deterioration of the quality of water in one or more water
bearing zones, or will result in a loss of artesian pressure. If a well cannot
be properly completed to prevent such an unauthorized interchange of water
between water bearing zones or to prevent a loss of artesian pressure, the well
shall be abandoned and plugged in accordance with this chapter or other
directions from the permitting authority, which are appropriate for the
hydrogeologic conditions encountered.
(f) In the construction, repair, or
abandonment of a water well, caution shall be taken to maintain the work site
so as to minimize the potential entrance of contaminants into the bore hole and
the ground water resource.
(g) Only
water from a potable water source shall be used in the construction, repair or
abandonment of a water well, including water for cleaning of well materials,
drilling equipment, and water used to mix drilling fluids.
(h) Use of Explosives. The use of dynamite or
other high-grade explosives in the construction or repair of water wells is
prohibited.
(i) Grouting and
Sealing.
1. All well casings seated into a
consolidated formation shall be seated or sealed with neat cement
grout.
2. Except as provided in 3.
below, wells with driven casing into natural earth or a bore hole equal to or
smaller in diameter than the outside diameter of the casing shall be sealed by
adding dry bentonite to the casing string at land surface and allowing that
material to be carried down the outside of the casing as the casing is driven
to completion. Dry bentonite shall be applied to maintain a grout seal around
the casing.
3. In the construction
of water wells with driven casing, for limited use commercial public water
systems, limited use community public water systems, public water systems,
potable water wells permitted pursuant to Chapter 62-524, F.A.C., and water
wells serving bottled water plants, the minimum acceptable seal shall be
accomplished by undercutting or under-reaming the last five feet of the hole
before seating the casing. A minimum of one foot of such enlarged hole must be
into the consolidated formation in which the casing will be seated. The entire
enlarged portion of the hole shall be filled with cement grout, and then the
casing shall be driven through the cement grout and seated into the enlarged
one-foot portion of the consolidated formation. The uppermost 20 feet of casing
shall be sealed with no less than a two-inch nominal thickness of cement grout.
No other minimum seal shall be acceptable unless approved by the appropriate
water management district or delegated permitting authority as providing
equivalent protection to the resource.
4. For any part of a well casing with an
outside diameter of four inches or larger intended to be installed in a bore
hole which is larger in diameter than the inside diameter of the casing, the
annular space shall be filled from bottom to top with not less than a nominal
two-inch thickness of neat cement grout. For well casings with an outside
diameter of less than four inches, intended to be installed in a bore hole
which is larger in diameter than the inside diameter of the casing, the minimum
grout thickness shall be a nominal one inch thickness of neat cement grout. The
casing shall be centered in the bore hole prior to grouting. In those cases
where, during grouting operations, circulation of the grout is lost so that the
annular space being grouted cannot be filled in one continuous operation, a
tremie pipe shall be installed in the annular space to a point immediately
above the zone of lost circulation and the annulus shall be bridged at that
point by sand or other approved material introduced through the pipe. Grouting
of the annular space shall be completed using the tremie pipe or other
equivalent method approved by the permitting authority.
5. Any district may grant individual
exceptions or, with the concurrence of the Department, may exempt any areas of
that district from the requirements of cement grouting the annular space
between the well casing and bore hole wall of that part of a well which
penetrates an unconsolidated formation upon demonstration that:
a. The unconsolidated formation material is
of such a caving nature that upon stopping the circulation of drilling fluid
through the well the aquifer material will immediately cave into and fill up
the annular space between the well casing and bore hole wall.
b. A flow space is not created by such
construction that will allow any movement of waters along the outside of the
well casing which did not naturally occur prior to construction of the
well.
6. Except as
provided in subparagraph 5. above, grouting and sealing of water wells shall be
accomplished by the practices and methods recommended by Appendix C of American
Water Works Association (AWWA) Standard A100-97 (1997), AWWA Standard for Water
Wells, and grouting and sealing of geothermal wells shall be accomplished by
the practices and methods recommended by the Vertical Geothermal Heat Pump
Systems Engineering Design and Field Procedures Manual, published by the
International Ground Source Heat Pump Association, First Edition 2000, Oklahoma
State University, which are adopted and incorporated by reference herein.
Copies of these recommended practices and methods may be obtained from the
American Water Works Association, 6666 West Quincy Avenue, Denver, CO 80235;
and the International Ground Source Heat Pump Association, Oklahoma State
University, 374 Cordell South, Stillwater, OK 74078-8018,
respectively.
7. Alternate grouting
methods and materials providing equivalent protection shall be approved in
writing by the permitting authority. Alternatives to the grouting methods
described in subparagraphs 1.-6. above, must be requested for use from the
permitting authority as part of the construction permit application, or once
construction begins only in situations where the methods in the rules are not
working. In either situation, a detailed explanation of what and why alternate
methods are requested must be provided. Alternate grout materials (other than
neat cement grout) must be requested in the construction permit application, or
once construction begins only when neat cement grout is not providing or will
not provide as good a seal as the alternate
materials.
(4)
Top of the Well.
(a) Well Covers.
1. Whenever there is an interruption in work
on the well, such as overnight shutdown, the well opening shall be sealed with
a tamper resistant cover.
2. Except
for those areas of a district designated by the Department with the concurrence
of the permitting authority, any well in which pumping equipment is installed
seasonally or periodically shall, whenever pumping equipment is not installed,
be capped with steel or reinforced concrete cover, or valve.
3. Any cased well equipped with permanently
installed pumping equipment shall have that pumping equipment and any necessary
piping installed through a well seal.
4. Any unused well shall be capped in a
watertight manner with a threaded, welded, or bolted cover or
valve.
(b) Upper
Terminus.
1. At the time of well
construction, all wells shall be accessible at the upper terminus of the well
casing for inspection, servicing, and testing.
2. For private and multi-family water system
wells and irrigation wells, the upper terminus of the well casing shall project
at least 12 inches above finished grade. Where a potential physical structure
or traffic hazard may be present or where a potential public health threat
exists, the upper well casing terminus may be placed in an appropriate
enclosure terminating at finished grade. The enclosure shall be designed to
allow vertical access to the upper well casing terminus for maintenance and
inspection and provide for gravity drainage of the enclosure. The upper well
casing terminus shall be constructed to a point 18 inches or less below
finished grade. The upper well casing terminus shall be sealed with a water
tight seal to prevent the entrance of surface water and contaminants into the
well.
3. For limited use commercial
public water system wells and limited use community public water system wells
constructed on or after April 1, 2002, the upper terminus of the well casing
shall project at least 12 inches above the concrete apron around the
well.
4. For public water system
wells constructed on or after April 1, 2002, the upper terminus of the well
casing shall project at least 12 inches above the pump house floor, pump pit
floor, or concrete apron around the well.
5. For public water system wells, limited use
commercial public water system wells, and limited use community public water
system wells constructed on or after April 1, 2002, located at sites subject to
flooding, the upper terminus of the well casing shall project at least 12
inches above the 100-year flood elevation and 100-year wave-action elevation.
Where it is not practicable to comply with this requirement, the water
management district or delegated permitting authority shall allow exceptions on
a case-by-case basis provided the upper terminus of the well casing is fitted
with a watertight seal.
6. Public
water system wells, limited use commercial public water system wells, and
limited use community public water system wells, shall be equipped with a
sealable opening that will allow introduction of disinfectants and measurement
of static water level and drawdown or artesian pressure.
(c) Well Aprons. For public water system
wells, limited use commercial public water system wells, and limited use
community public water system wells constructed on or after April 1, 2002, not
located within a pump house or pump pit, a concrete apron at least six feet by
six feet and at least four inches thick shall be centered around the well. The
bottom surface of the concrete apron shall be constructed on top of the
finished grade, and the top surface of the concrete apron shall be sloped to
drain away from the well casing.
(d) Flowing Wells. If the well flows at land
surface, control shall be provided by valved pipe connections, watertight pump
connections, or receiving reservoirs set at an altitude corresponding to the
artesian head.
(5)
Plugging. All abandoned wells shall be plugged by filling them from bottom to
top with neat cement grout or bentonite and capped with a minimum of one foot
of neat cement grout. An alternate method providing equivalent protection shall
be approved in writing by the Department or the permitting
authority.