(1) Onsite sewage tank design. The following
requirements must apply to all onsite sewage tanks manufactured for use in
Florida unless specifically exempted by other provisions of these rules:
(a) Onsite sewage tanks include: septic
tanks, graywater tanks, laundry tanks, grease interceptors, pump tanks, aerobic
treatment unit tanks, tanks containing treatment media and stationary holding
tanks not described in paragraph
62-6.0101(7)(p),
F.A.C. Tanks must be constructed of concrete, fiberglass or
polyethylene.
(b) Design and
testing of concrete treatment tanks:
1.
Structural design of tanks must be by calculation or by performance.
2. Structural design must be verified by
actual vacuum load or hydrostatic test in accordance with the Department's
policy for Test Requirements for Structural Proofing, February 28, 2022, herein
adopted and incorporated by reference at
http://www.flrules.org/Gateway/reference.asp?No=Ref-14367.
Copies of this policy are available as provided in subsection (12) below. The
vacuum test must be followed by a flow and water tightness test.
3. Tanks must be watertight as defined in
ASTM C1227-20, Standard Specification for Precast Concrete Septic Tanks,
paragraph 9.2., (2020) herein adopted and incorporated by reference. This
standard has been deemed copyright protected and is available from the
publisher at ASTM International, P.O. Box C700 West Conshohocken, Pennsylvania
19428-2959, or at publisher's website at
www.astm.org/, and is available for
inspection as provided in subsection (12) below. ASTM C1227-20, paragraph
9.2.2, must be modified to read as follows: Water tightness testing - Fill the
tank with water to the invert of the outlet and let stand for 24 hours. Refill
the tank. The tank is approved as water tight if the water level is held for
one hour.
4. Manufacturers may use
calculations provided by the design engineer in lieu of proof testing for tanks
using reinforcement bars for structural strength and having a wall thickness of
5 inches or greater. Design by calculation must be completed using the Strength
Design Method outlined in Chapters 4, 5 and 6 of the American Concrete
Institute (ACI) publication ACI 318-19, Building Code Requirements for
Structural Concrete and Commentary (2019), herein adopted and incorporated by
reference. This document has been deemed copyright protected and is available
from the publisher at American Concrete Institute, 38800 Country Club Drive,
Farmington Hills, MI 48331-3439, or at publisher's website at
www.concrete.org/, and is available for
inspection as provided in subsection (12) below. For the design strength a
strength reduction factor will be applied per ACI 318-19 Chapter
21.
(c) Design and
testing of fiberglass and polyethylene tanks:
1. Vacuum testing must be conducted in
accordance with the Department's policy for Test Requirements for Structural
Proofing, February 28, 2022, adopted and incorporated by reference in
subparagraph
62-6.013(1)(b)
2., F.A.C. Copies of this policy are available as provided in subsection (12),
below and at
http://www.flrules.org/Gateway/reference.asp?No=Ref-14367.
The vacuum test will be followed by a water-tightness test.
2. Vacuum testing must demonstrate a
distortion of volume of no more than 1% at a safety factor of 1.0 and 2% at a
safety value of 1.4 followed by passing a water-tightness test to be considered
satisfactory. To determine the vacuum at a 1.0 safety factor, divide the
required total vacuum values by 1.4. There must be no distortion of the access
hatch perimeters at the full vacuum load and the access hatch must be able to
be removed and reinstalled at the conclusion of the test.
3. Flow and water-tightness testing must be
performed as follows: Fill the tank with water to the invert of the outlet. The
tank is approved as water tight if the water level is held for one
hour.
(d) Testing must be
performed by or witnessed by an engineer licensed in the state of Florida, or
by an employee of the Department that has been authorized to perform or witness
tank testing. Test results must be certified by the witnessing engineer or
Department employee.
(e) Tank lids
for non-traffic residential installations must be designed for a dead load of
12'' inch earth cover with a dry soil density of 100 pounds per cubic foot or a
live load of two concentrated loads of 1, 750 pounds at a 60'' inch spacing or
a concentrated load of 1, 750 pounds located at the center of the lid,
whichever provides the greater shear and moment stresses to the lid. The
required strength must be per ACI 318-19, Chapter 5, incorporated by reference
in subparagraph
62-6.013(1)(b)
4., F.A.C., effective 06-21-2022. Structural integrity proof test or
calculations for the 12 inch overburden earth load and the 1750 pound
concentrated loading must be provided. Designs sealed by an engineer licensed
in the state of Florida will be acceptable for design proof of tank lid
designs.
(f) Tanks and tank lids
for traffic installations must be designed, signed and sealed by an engineer
licensed in the state of Florida. Whenever vehicular traffic is anticipated to
cross over the tank, traffic lids must be installed with manhole covers to
finished grade. Traffic tanks and lids must be designed in accordance with ASTM
C 890-21, Standard Practice for Minimum Structural Design Loading for
Monolithic or Sectional Precast Concrete Water and Wastewater Structures
(2021), herein adopted and incorporated by reference, for the appropriate
loading. This standard has been deemed copyright protected and is available
from the publisher at ASTM International, P.O. Box C700 West Conshohocken,
Pennsylvania 19428-2959, or at publisher's website at
www.astm.org, and is available for inspection as
provided in subsection (12) below. Application of paragraph 5.2.4 of ASTM C
890-21, will be at the discretion of the design engineer.
(2) Onsite sewage tank design requirements.
The following details must be incorporated into the design:
(a) Septic tanks and graywater tanks must
have multiple compartments, or single compartment tanks must be placed in
series to achieve the required effective capacity. Grease interceptors, laundry
tanks, pump tanks and aerobic treatment unit tanks must be either
multi-compartment or single compartment tanks. All tank stiffening members such
as ribs must be a homogeneous integral part of the structure. When slide-in
type compartment walls are proposed, the structural testing for such tanks must
be conducted without the slide-in wall in place. There must be a maximum of two
horizontal seams between the topside of the bottom of the tank and the
underside of the lid. There must be no vertical seams. Except as noted in this
paragraph, the first chamber of a dual compartment septic or graywater tank or
the first tank of single compartment tanks in series must have a minimum
effective capacity of at least 2/3 of the total required effective capacity.
The second single compartment tank or chamber of a multi-compartment tank must
have a minimum effective capacity of at least 1/5 of the total required
effective capacity. The combined effective capacities of the first and second
chambers or the first and second single-compartment tanks must equal or exceed
the total required effective capacity. Systems with daily flows in excess of 3,
500 gallons per day may utilize two tanks to achieve the total required
effective capacity, provided that the first tank provides no less than 1/2 of
the total required effective capacity. The second tank must provide no less
than 1/5 of the total required effective capacity and the total effective
capacities of the two tanks combined must be no less than the total required
effective capacity.
(b) The liquid
depth of compartments for septic tanks and grease interceptors must be at least
40 inches. The liquid depth of compartments for graywater tanks, laundry tanks
and pump tanks must be at least 30 inches. Liquid depths greater than 84 inches
must not be considered in determining the effective capacity.
(c) A minimum free board or airspace of 15
percent by volume of the effective capacity of all blackwater, graywater and
laundry tanks must be provided. The volume of risers above the liquid level
line cast as an integral part of the tank may be included as free board or
airspace.
(d) The inlet invert of
septic tanks, graywater tanks and laundry tanks must enter the tank 1 to 3
inches above the liquid level of the tank. A vented inlet tee, vented sweep or
a baffle may be provided at the discretion of the manufacturer to divert the
incoming sewage. The inlet device, if utilized, must have a minimum diameter of
4 inches and must not extend below the liquid surface more than 33 percent of
the liquid depth.
(e) In septic
tanks, graywater tanks and laundry tanks, a minimum 4 inch diameter vented
outlet tee, sweep or baffle must extend below the liquid level of the tank so
that the invert level of the outlet device is a distance not less than 30
percent nor greater than 40 percent of the liquid depth. The outlet device must
extend at least 4 inches above the liquid level. The submerged intake orifice
of any outlet fixture not incorporating an approved outlet filter device must
be provided with an approved solids deflection device to reduce, by a minimum
of 90 percent, the intake area of the outlet fixture exposed to the vertical
rise and fall of solid particles within the tank. Turning the intake orifice of
an outlet tee or sweep 90 degrees from the vertical will satisfy the solids
deflection device requirement.
(f)
The inlet and outlet devices must be located at opposite ends of the tank so as
to be separated by the maximum distance practical and must be in accordance
with ASTM C-923/C-923M-20, Standard Specification for Resilient Connectors
Between Reinforced Concrete Manhole Structures, Pipes, and Laterals (2020),
herein adopted and incorporated by reference. This standard has been deemed
copyright protected and is available from the publisher at ASTM International,
P.O. Box C700 West Conshohocken, Pennsylvania 19428-2959, or at publisher's
website at
www.astm.org/, and is available
for inspection as provided in subsection (12) below. Inlets and outlets on the
sides of any tank must be located no more than 12 inches from the end of the
tank.
(g) Compartment walls must be
designed to withstand the stresses induced by pumping out either of the
compartments. There must be no relief holes. However, the compartment walls may
be inserted in grooves without grouting, fiberglassing or otherwise permanently
attaching in place, unless such attachment is required for proving structural
integrity of either the tank or compartment wall.
(h) Sewage flow between the first and second
chamber of a multi-chamber tank must interconnect utilizing either a minimum 4
inch diameter hole or equivalent size slot in the wall or with a minimum 4 inch
diameter vented and inverted U-fitting or a tee. Receptacles in series must
interconnect utilizing a minimum 4 inch diameter vented, inverted U-fitting or
a tee. For septic, graywater and laundry tanks, the outlet device or slot must
extend below the liquid level of the tank so that the invert level is located
not less than 30 percent nor greater than 40 percent of the liquid
depth.
(i) Joints of tanks,
including mid-seams, risers, and lids must be sealed using a bonding compound
that meets ASTM C-990-09R19, Standard Specification for Joints for Concrete
Pipe, Manholes, and Precast Box Sections using Preformed Flexible Joint
Sealants (2019), herein adopted and incorporated by reference. This standard
has been deemed copyright protected and is available from the publisher at ASTM
International, P.O. Box C700 West Conshohocken, Pennsylvania 19428-2959, or at
publisher's website at
www.astm.org/, and is
available for inspection as provided in subsection (12) below.
(j) The Department's designated approval
number for the tank, and the effective capacity of the tank in gallons must be
cast or stamped into the wall or permanently stenciled or decaled onto the wall
at the inlet end, to begin within 6 inches of the top of the wall. All
identifying marks must be inscribed or affixed at the point of manufacture
only. All information supplied in the legend must be provided with a minimum of
two inch high lettering.
(k) Each
compartment must have access using manholes, with each manhole having a minimum
area of 225'' square inches. Manholes must be located so as to allow access to
the inlet and outlet devices. A minimum 6''-inch diameter opening must be
placed at the inlet and outlet ends of the lid if a minimum 225'' square inch
access port is placed in the middle of the lid. The access manhole over the
inlet and outlet must extend to within 8'' inches of finished grade. If a riser
is used, and if the riser access lid opens directly to the receptacle interior,
joints around the riser and receptacle must be sealed and made watertight as
specified in paragraph
62-6.013(2)(i),
F.A.C., to prohibit intrusion of ground water into the tank. For
multi-compartment tanks or tanks in series, manholes must extend to within 8
inches of finished grade over the first compartment inlet and the last
compartment outlet. An appropriate mechanism must be provided to make access
manholes vandal, tamper, and child resistant. Acceptable protection of openings
must consist of one or more of the following methods as specified by the
manufacturer:
1. A padlock.
2. A twist lock cover requiring special tools
for removal.
3. Covers weighing 58
pounds or more, net weight.
4. A
hinge and hasp mechanism which uses stainless steel or other corrosion
resistant fasteners to fasten the hinge and hasp to the lid and tank for
fiberglass, metal or plastic lids.
(l) Tank designs that specify a monolithic
compartment wall from the bottom of the tank up to the invert of the
pass-through orifice and a drop-in section for the upper portion of the wall
must be approved for both single and multi-compartment use.
(m) Tanks must have a one-piece lid or a lid
with a maximum of three sections. All lids must be designed by Licensed
Engineers in accordance with paragraphs
62-6.013(1)(e) and
(f), F.A.C., and approved by the
Department.
(3) Onsite
sewage tank design approval. All onsite sewage tanks distributed in the state
must be approved for use by the Department prior to being offered for sale or
installed. Such approval must not be obtained until the manufacturer of a
specific tank model has submitted the following:
(a) Detailed design drawings of the tank and
lid showing:
1. Design calculations or proof
testing results in accordance with subsection
62-6.013(1),
F.A.C.
2. Dimensions, including
location and size of all inlets, outlets, access hatches, manholes and pass
through orifices.
3. Effective
capacity in gallons.
4. Freeboard
or air space in gallons.
5.
Production materials. For concrete tanks include 28 day compressive strength,
in pounds per square inch (psi).
6.
Reinforcing materials. For concrete tanks, include size and location of all
rebar, if any; and fiber reinforcing material size and quantity (in pounds) per
cubic yard, if any.
(b)
For concrete tanks - see subsection
62-6.013(5),
F.A.C.
(c) For fiberglass and
polyethylene tanks - see subsection
62-6.013(6),
F.A.C.
(d) Certification that the
tank has undergone flow testing to confirm the effective capacity, airspace,
and water tightness. Flow testing must be conducted by an engineer licensed in
the state of Florida or a Department employee. Test results must be certified
by the engineer or Department employee.
(e) Designs must be submitted to the
Department, Onsite Sewage Program.
(f) There must be two tank design
classifications. The following criteria must be used for each category:
1. Category 3 tanks must be designed for
saturated soil with the saturation at finished grade. The design must provide
for a maximum of 18 inches of saturated soil cover over the top of the tank.
Soil density must be 100 pounds per cubic foot. The lateral earth pressure
coefficient (K) must be no less than 0.33.
2. Category 4 tanks must be designed for
saturated soil with the saturation at finished grade. The design must provide
for a maximum of 48'' inches of saturated soil cover over the top of the tank.
Soil density must be 100 pounds per cubic foot. The lateral earth pressure
coefficient (K) must be no less than 0.33. Where a tank will be placed with
greater than 48'' inches of soil over the top of the tank, an engineer licensed
in the state of Florida must design the tank for the specific conditions
anticipated at the site.
(g) A series of tanks may be approved by
successful demonstration of the largest in a series of tanks. Approval for
inclusion of the tanks to be considered in a series must be obtained from the
Department prior to testing the tanks. A series is either where only one
dimension, this being height, length, or width, is changed or where two
dimensions change in the same proportion to offer a different capacity of
tank.
(h) The manufacturer must
notify the Department in writing, stipulating the date, time and location of
the test, no less than ten working days prior to the tank proof testing. The
notice must include the tanks to be tested. Approval must not be granted until
after successfully passing the required tests, and submitting the testing
results.
(i) The Department will
issue an approval number to the manufacturer. Form DEP 4012, "Application for
Septage Disposal Service Permit, Temporary System Service Permit, Septic Tank
Manufacturing Approval, " adopted and incorporated by reference in subsection
62-6.010(2),
F.A.C., and available as provided in subsection (12) below, must be used to
apply for manufacturing approval. The form can be obtained from the
Department.
(4) Onsite
sewage tank manufacturer's yearly inspection - Yearly inspection of the
manufacturer's facility must consist of the following:
(a) Verify that the manufacturer has the
design mix recorded and in a readily accessible location for the plant
operators.
(b) Verify that the
production process is recorded and that the operators are following the
process.
(c) Verify that the
necessary tests are being conducted by a certified testing lab or by a
technician certified by the ACI. The preparation of the test specimens must be
performed by certified third party testing laboratory personnel; or
manufacturers, or their employees, that have successfully passed the ACI
certification program. Each manufacturer must submit a minimum of three
cylinders per year. The specimens must be taken from a production
mix.
(d) Verify that the
manufacturer has the proper number of tests for the year and that the results
are recorded. Review the results for compliance with the design.
(e) Examine the material stockpiles to ensure
that the materials are free from deleterious materials.
(f) Examine the measuring equipment to ensure
that the equipment has been calibrated within the last year.
(g) Examine conveyors to insure that material
is transported as measured.
(h)
Inspect a minimum of five tanks in the manufacturers' inventory. For different
series, a minimum of one tank must be inspected from each series. Report the
following unacceptable defects:
1. Cracks in
all interior and exterior surfaces of the tanks.
2. Cold joint lines. This is an indication of
non-monolithic pours. Examine both the interior and exterior of the tank for
confirmation of a cold joint that extends across the thickness of the
wall.
3. Evidence of improper steel
cover. Rebar and wire mesh must not be exposed.
4. Watertight inlets and outlets must be
provided per rule.
(i)
Where cold-joint lines that appear to extend through the wall, or cracks in any
surface of the tank exist, conduct a watertightness test on a maximum of two
tanks as follows: Fill the tank with water to the invert of the outlet. The
tank is approved as watertight if the water level is held for one hour. For
concrete tanks, if the test fails within the first 24 hours after filling, it
may be repeated after 24 hours. The tanks must not be tested until they have
cured for 28 days. If there are no indications of cold-joint lines that appear
to extend through the wall, or cracking of tank surfaces, two tanks must be
tested at random. Record all data and submit results to the
Department.
(j) Verify that the
manufacturer is not relocating the tanks prior to the tank achieving 75% of the
design compressive strength. Record how this is accomplished.
(k) Conduct impact hammer tests-record
data.
(l) Examination of the
manufacturer's receipts for material used during the previous year. Tank
manufacturers must retain all receipts from the previous year for material used
in the manufacture of tanks and make them available for
inspection.
(5) Concrete
tanks must be built of precast or poured in place concrete in accordance with
ACI 318-19, Building Code Requirements for Structural Concrete and Commentary
incorporated by reference in subparagraph
62-6.013(1)(b)
4., F.A.C., effective 06-21-2022, or ASTM C-1227-20, Standard Specification for
Precast Concrete Septic Tanks, incorporated by reference in subparagraph
62-6.013(1)(b)
3., F.A.C., effective 06-21-2022, except as revised herein.
(a) For design and analysis of concrete
septic tanks, the publication "Rectangular Concrete Tanks" revised 5th edition
(1998), as published by the Portland Cement Association may be used at the
designer's discretion, herein incorporated by reference. When computing length
to height and width to height ratios the designer may interpolate between
tables for intermediate ratios and values or may use the table and values for
the higher ratios.
(b) Temperature
and shrinkage crack control in concrete tanks must be accomplished by use of
steel reinforcing in accordance with ACI 318-19 Chapter 11, incorporated by
reference in subparagraph
62-6.013(1)(b)
4., F.A.C., effective 06-21-2022 or by use of fiber reinforcement. Minimum
ratio of vertical and horizontal reinforcement area to gross concrete area must
be 0.0010 for deformed bars or welded wire fabric. Fiber reinforcing materials
may be used by the manufacturer to achieve crack control equivalent to the use
of deformed bars or welded wire fabric. To be considered equivalent, acceptable
fibers must at least meet or exceed ACI recommendations regarding materials,
fiber sizing, and required fiber quantities. Any current or future revisions to
the ACI recommendations may be used by the manufacturer, at their option.
Materials other than materials recognized by ACI for crack control use will not
be acceptable. Minimum reinforcement must be as outlined in the document
entitled Reinforcement Required to Meet paragraph
62-6.013(5)(b),
F.A.C., dated February 28, 2022, herein adopted and incorporated by reference.
Copies of this document are available as provided in subsection (12), below and
at
http://www.flrules.org/Gateway/reference.asp?No=Ref-14805.
(c) Concrete mixes must be in accordance with
the Portland Cement Association (PCA) publication entitled PCA Design and
Control of Concrete Mixtures, Seventeenth Edition (2021), herein adopted and
incorporated by reference. This standard has been deemed copyright protected
and is available from the publisher at the Portland Concrete Association, 5420
Old Orchard Road, Skokie Illinois 60077-1083 or at the publisher's website at
www.concrete.org/, and is available for
inspection as provided in subsection (12) below.
(d) Terminology relating to concrete and
concrete aggregates must be in accordance with ASTM C-125-21a, Standard
Terminology Relating to Concrete and Concrete Aggregates (2021), herein adopted
and incorporated by reference. This standard has been deemed copyright
protected and is available from the publisher at ASTM International, P.O. Box
C700, West Conshohocken, Pennsylvania 19428-2959, or at publisher's website at
www.astm.org/, and is available for
inspection as provided in subsection (12) below.
(e) Concrete aggregates used in the
manufacturing of all precast or poured-in-place concrete tanks for use in
onsite sewage treatment and disposal systems must conform to ASTM C 33-/33M-18,
Standard Specification for Concrete Aggregates (2018), herein adopted and
incorporated by reference. This standard has been deemed copyright protected
and is available from the publisher at ASTM International, P.O. Box C700, West
Conshohocken, Pennsylvania 19428-2959, or at publisher's website at
www.astm.org/, and is available for
inspection as provided in subsection (12) below.
(f) Minimum concrete cover over structural
steel reinforcing must be 3/4'' inches. The minimum bend radius for structural
reinforcing must be three times the reinforcing bar diameter.
(g) Temperature and shrinkage crack control
steel must not be exposed. Exposure of fiber reinforcing is
acceptable.
(h) Minimum 28-day
compressive strength must be 4000 psi.
(i) Three compressive test cylinders must be
prepared, cured, and tested in accordance with ASTM C 31/C31M-21a, Standard
Practice for Making and Curing Concrete Test Specimens in the Field (2021),
herein adopted and incorporated by reference, and ASTM C-39/C-39M-21, Standard
Test Method for Compressive Strength of Cylindrical Concrete Specimens (2021),
herein adopted and incorporated by reference, at least one time every year, or
whenever the manufacturer changes the design mix or the manufacturing process.
These standards have been deemed copyright protected and are available from the
publisher at ASTM International, P.O. Box C700, West Conshohocken, Pennsylvania
19428-2959, or at publisher's website at
www.astm.org/, and are available for inspection as
provided in subsection (12) below.
(j) The bottoms of concrete tanks must be
monolithic and must either be an integral part of the walls or must be sealed
to the walls using water-stops cast into the wall and bottom. Receptacle
bottoms must not contain openings for any purpose, for example, to facilitate
the removal of rainwater.
(k)
Approval of new designs must not be granted until the following has been
completed and submitted as part of the application:
1. Establish a design mix and production
process. Record the aggregate material, size and gradation; type and strength
of cement; cement to aggregate ratios; water to cement ratio; and any other
pertinent design data. Record the production process, for example; measuring
equipment, batch sizes, mixing sequence, transportation techniques from mixer
to mold, pouring techniques with consolidation of concrete methods
detailed.
2. Construct three tanks
using the design mix.
3. Test two
sets of cylinders from the design mix at 7 days and 28 days.
4. Structural proof test three tanks to the
design strength in accordance with paragraph
62-6.013(1)(b),
F.A.C., for tanks having an effective capacity of 1, 350 gallons or
less.
5. Structural proof test one
tank to the design strength in accordance with paragraph
62-6.013(1)(b),
F.A.C., for tanks having an effective capacity greater than 1, 350 gallons but
not more than 1, 500 gallons.
6.
Structural proof test one tank or provide tank strength calculations in
accordance with paragraph
62-6.013(1)(b),
F.A.C., for tanks having an effective capacity exceeding 1, 500
gallons.
7. Verify that the
manufacturer is not removing tanks from the producer's facility prior to the
tank achieving 75% of the design compressive strength. Record how this is
accomplished.
(6) The following structural requirements are
applicable to fiberglass and polyethylene tanks:
(a) Materials and sealants used in the tank
manufacturing process must be capable of effectively resisting the corrosive
influences of the liquid components of sewage, sewage gases and soil burial.
Materials used must be formulated to withstand shock, vibration, normal
household chemicals, deterioration from sunlight and other environmental
factors.
(b) Fiberglass tanks must
be constructed so that all parts of the tank meet the following mechanical
requirements. A test report from an independent testing laboratory is required
to substantiate that individual tank designs and material formulations meet
these requirements.
1. Ultimate tensile
strength - minimum 12, 000 psi when tested in accordance with ASTM D-638-14,
Standard Test Method for Tensile Properties of Plastics (2014), herein adopted
and incorporated by reference. This standard has been deemed copyright
protected and is available from the publisher at ASTM International, P.O. Box
C700, West Conshohocken, Pennsylvania 19428-2959, or at publisher's website at
www.astm.org/, and is available for
inspection as provided in subsection (12) below.
2. Flexural strength - minimum 19, 000 psi
when tested in accordance with ASTM D-790-17, Standard Test Methods for
Flexural Properties of Unreinforced and Reinforced Plastics and Electrical
Insulating Materials (2017), herein adopted and incorporated by reference. This
standard has been deemed copyright protected and is available from the
publisher at ASTM International, P.O. Box C700, West Conshohocken, Pennsylvania
19428-2959, or at publisher's website at
www.astm.org/, and is available for inspection as
provided in subsection (12) below.
3. Flexural modulus of elasticity - minimum
800, 000 psi when tested in accordance with ASTM D-790-17 Standard Test Methods
for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical
Insulating Materials, incorporated by reference in subparagraph
62-6.013(6)(b)
2., F.A.C., effective 06-21-2022.
4. Not less than 30 percent of the total
weight of the fiberglass tank must be fiberglass reinforcement.
5. Internal surfaces must be coated with an
appropriate gel coating or resin to provide a smooth, pore-free, watertight
surface.
(c) Polyethylene
tanks must meet the requirements of International Association of Plumbing and
Mechanical Officials (IAPMO)/American National Standards Institute (ANSI)
Z1000-2019 Paragraph 7.1 "Blow Molded and Single-Layer Rotationally-Molded
Polyethylene Septic Tanks" and 7.2 "Multi-Layer Rotationally-Molded
Polyethylene Septic Tanks" (2019) herein adopted and incorporated by reference.
This standard has been deemed copyright protected and is available from the
publisher at IAPMO, 4755 East Philadelphia Street, Ontario, California 91761,
or at publisher's website at
www.iapmo.org/, and is available for inspection as
provided in subsection (12) below. Where the requirements of IAPMO/American
National Standards Institute (ANSI) Z1000-2019, Paragraphs 7.1 and 7.2 conflict
with the standards in this section, the standards in this section must apply. A
test report from an independent testing laboratory is required to substantiate
that individual tank designs and material formulations meet these
requirements.
(d) Approval of new
designs must not be granted until the following has been completed and
submitted as part of the application:
1.
Establish a design mix and production process. Record the material
specifications and other pertinent design data. Record the production process,
for example; measuring equipment, batch sizes, mixing sequence, transportation
techniques from mixer to mold, and spraying techniques.
2. Construct three receptacles using the
design mix.
3. Test two sets of
test strips from the design mix.
4.
Structural proof test three receptacles to the design strength per paragraph
62-6.013(1)(c),
F.A.C., for receptacles having an effective capacity of 1, 350 gallons or
less.
5. Structural proof test one
receptacle to the design strength in accordance with paragraph
62-6.013(1)(c),
F.A.C., for receptacles having an effective capacity greater than 1, 350
gallons.
6. Verify that the
manufacturer is not planning to relocate the receptacles prior to the
receptacle achieving 75% of the design compressive strength. Record how this is
accomplished.
(7) Grease interceptors are not required for
a residence. However, one or more grease interceptors are required where grease
waste is produced in quantities that could otherwise cause line stoppage or
hinder sewage disposal. The design of grease interceptors must be based on
standards found in paragraph (a) below. In addition, the following general
requirements found in paragraphs (b), (c), and (d), apply when determining the
proper use and installation of a grease interceptor used as a component of an
onsite sewage treatment and disposal system.
(a) The inlet invert must discharge a minimum
2 1/2'' inches above the liquid level line and the outlet pipe must have a tee
with a minimum diameter of 4 inches that extends to within 8'' inches of the
bottom of the tank.
(b)
Interceptors must be located so as to provide easy access for routine
inspection, cleaning and maintenance. Manholes must be provided over the inlet
and outlet of each interceptor and be brought to finished grade.
(c) Where a grease interceptor is required or
used, only kitchen wastewater must first pass through the interceptor and then
be discharged into the first compartment of a septic tank or other approved
system.
(d) Sizing of grease
interceptors must be based on the equations below. The minimum volume of any
grease interceptor must be 750 gallons and the maximum volume of an individual
single grease interceptor chamber must be 1, 250 gallons. When the required
effective capacity of the grease interceptor is greater than 1, 250 gallons,
installation of multi-chambered grease interceptors or grease interceptors in
series is required.
1. Restaurants: (S) X (GS)
X (HR/12) X (LF) = effective capacity of grease interceptor in gallons.
S = number of seats in the dining area.
GS = gallons of wastewater per seat; use 25 gallons for
ordinary restaurant, use 10 gallons for single service article
restaurants.
HR = number of hours establishment is open.
LF = loading factor: use 2.0 interstate highways, 1.5 other
freeways, 1.25 recreational areas,
1. 0 main highways, and 0.75 other roads.
2. Other type establishments with commercial
kitchens: (M) X (GM) X (LF) = effective capacity of grease interceptor in
gallons.
M = meals prepared per day.
GM = gallons of wastewater per meal: use 5 gallons.
LF = loading factor: use 1.00 with dishwashing and 0.75
without dishwashing.
(8) Laundry tank or laundry waste interceptor
- when a separate system is installed to accept effluent from a single home
washing machine only, the laundry tank or laundry waste interceptor for such
system must meet the following minimum standards:
(a) The minimum effective capacity must be
225 gallons for establishments with an estimated sewage flow of up to 300
gallons per day and must be increased by 50 gallons for every 100 gallons of
additional daily sewage flow.
(b)
The laundry waste interceptor must be provided with a vented inlet tee, vented
sweep, or a baffle.
(c) The laundry
waste interceptor must not receive waste flow from kitchen fixtures or be used
as a grease trap.
(9)
Pump tanks and pumps - when used as part of an onsite sewage treatment and
disposal system, the following requirements must apply to all pump tanks
manufactured for use in Florida unless specifically exempted by other
provisions of these rules:
(a) Pump tanks must
have a minimum total capacity measured from the bottom of the tank to the top
of the tank in accordance with Table II. At least 80% of the required total
capacity must be contained below the invert of the inlet. Pump levels must be
set as low as practical to preserve as much reserve capacity as possible in the
event of pump failure.
(b) The
electrical conduit and effluent dosing pipe must exit the dosing chamber:
1. Through the tank outlet using plumbing
fittings and reducers to produce a watertight seal,
2. When risers are used, the electrical line
and the effluent dosing pipe may penetrate the riser wall provided the
penetration is above the wet season high water table elevation and there is a
soil-tight seal around the penetrations. When the top of the dosing tank is
placed more than 8'' inches below the finished grade, risers must be used to
provide access within 8'' inches of the finished grade. Where risers are used,
risers must be attached to the tank in accordance with paragraph
62-6.013(2)(i),
F.A.C. Any unused tank outlet must be sealed with a length of capped PVC pipe
installed in accordance with paragraph
62-6.013(2)(f),
F.A.C., or
3. Through a 2 to 4''
inch access port installed in the tank lid by the manufacturer as approved by
the Department. After installation the port must be sealed with a bonding
compound per paragraph
62-6.013(2)(i),
F.A.C. Unused ports must be sealed watertight with cement or bonding compound
or with a length of capped PVC pipe.
(c) When a pump is used as part of a system,
the following conditions must apply.
1. Pumps
used to distribute sewage effluent must be certified by the manufacturer to be
suitable for such purpose or pumps must be designed in accordance with the Sump
and Sewage Pump Manufacturers Association's Recommended Standards for Sump,
Effluent and Sewage Pumps (2019 Revision) for the purpose intended, herein
adopted and incorporated by reference. This standard has been deemed copyright
protected and is available from the publisher at the Sump and Sewage Pump
Manufacturers Association, P.O. Box 44071, Indianapolis, Indiana, 46244, or at
publisher's website at
www.sspma.org/, and
is available for inspection as provided in subsection (12) below. The use of a
timer as part of any pump system is not allowed unless it is part of a design
submitted by an engineer, or master septic tank contractor, and is approved by
the Department.
2. An audio and
visual high water alarm must be provided in a conspicuous location visible by
system users to warn of pump failures. If the alarm is located outdoors, the
alarm must be waterproof and specified by the manufacturer for outdoor
use.
3. A pump must be placed in a
separate compartment or tank, except when using a pump chamber insert. Except
as noted below, any compartment or tank in which a pump is located must not be
considered when determining total effective capacity of a septic
tank.
4. A pump chamber insert may,
at the applicant's discretion, be used to house a pump inside a septic tank. If
a pump chamber insert is used, it must be approved for use by the Department.
Approval must be based on the ability of the pump chamber insert to effectively
filter solids from the effluent prior to intake by the pump. The efficiency of
solids removal by the pump chamber insert must be at least equal to a currently
approved outlet filter device. Pump chamber inserts that do not meet these
criteria must not be approved and must not be used. The filter device used as
part of the pump chamber insert must be considered to meet the requirement of
using an outlet filter device for purposes of subsection
62-6.008(2),
F.A.C. The tank or compartment used to house the pump chamber insert must be
included in calculating the minimum effective capacity of the tank, subject to
the following conditions:
a. When placed in a
compartmentalized tank or tanks in series, the pump chamber insert must be
placed in the last chamber or tank. When placed in a single compartment tank,
the pump chamber insert must be placed as close to the outlet side of the tank
as possible. In no case must the insert be placed farther than 1/2 the distance
to the inlet as measured from the outlet of the tank. The pump chamber insert
and filter must be accessible for routine maintenance. The manufacturer must
provide instructions on how to maintain the filter unit and the insert
device.
b. Pump levels must be set
so that the high water alarm is activated when the liquid level of the tank
will exceed the height of the inlet invert of the tank. The pump-on switch must
be set to maintain the greatest possible effective capacity of the tank, and in
no case must it be set higher than 1 inch below the inlet invert. Floats used
for operation of the pump must be allowed outside the pump chamber
insert.
c. The intake openings of
the pump chamber insert must not be located within 12'' inches of the bottom of
the tank, or within 12'' inches of the liquid level line of the tank.
d. The volume discharged by the pump must not
exceed 1/4 of the average daily sewage flow in any dose.
e. A pump chamber insert must not be used
when the total absorption area for the system is greater than 1, 000' square
feet, or when automatic dosing is required.
f. For new system installations, in addition
to the requirements above, the total septic tank capacity must include the
required minimum septic tank effective capacity, which must be contained below
the pump-off switch level, plus the pumping tank capacity per Table II, plus
the required 15% airspace.
g. For
repair installations, in addition to the requirements of subparagraphs a.
through e. above, pump chamber inserts must not be used in an existing septic
tank of less than 750 gallons effective capacity. In addition, the minimum tank
liquid depth must be 36'' inches below the pump-off switch level and the
minimum effective capacity contained below the pump-off switch level must be
within two tank sizes of that required in Rule
62-6.008, F.A.C., Table II. The
total septic tank capacity must include the minimum effective capacity within
two tank sizes of required tank size, plus dosing capacity, plus dosing reserve
capacity equal to the dosing capacity, plus freeboard or air space capacity
which is equal to 15% of the minimum effective
capacity.
(10) Transportation and installation.
(a) Onsite sewage tanks must not be removed
from the manufacturer's facility until the compressive strength of the concrete
has reached 75% of the design strength. Use of concrete industry published
graphs or tables indicating compressive strength vs. concrete age for the
design mix are satisfactory proof of strength.
(b) Tanks must be installed level from end to
end and side to side. As used in this context, level includes a slope from the
inlet end to the outlet end or from side to side of the tank not exceeding
one-half inch over the entire length or width of the tank. The tank must not be
approved with any pitch upward from the inlet end to the outlet end of the
tank.
(c) If a pumping device has
been placed in the building sewer, an inlet device must be used.
(d) Cast in place tanks or tanks manufactured
with water stops below the invert of the outlet, and tanks with seams below the
invert of the outlet must be watertightness tested in accordance with ASTM
C-1227-20, Standard Specification for Precast Concrete Septic Tanks, paragraph
9.2.2, after installation in the field. This standard is incorporated by
reference in subparagraph
62-6.013(1)(b)
3., F.A.C., effective 06-21-2022.
(e) The excavation for the installation of a
tank must be level and free of debris and rocks that could damage the tank or
prevent proper leveling, backfilling or compaction. Backfill material must be
free of rocks and debris. The installer must refer to the tank manufacturer's
installation instructions to prevent the tank from settling or floating or from
being damaged or distorted.
(11) Repair of tanks - Repairs are allowed
for tanks prior to shipment per ASTM, ACI, PCA standards and publications and
National Precast Concrete Association (NPCA), Septic Tank Manufacturing Best
Practices Manual (2010), herein adopted and incorporated by reference. This
document has been deemed copyright protected and is available from the
publisher at the National Precast Concrete Association, 1320 City Centre Drive,
Suite 200, Carmel, Indiana 46032, or at publisher's website at
www.precast.org/, and is available for
inspection as provided in subsection (12) below. Tanks damaged after they leave
the manufacturer's facility may be repaired for the following defects:
(a) Chips that do not penetrate more than 1/3
of the wall thickness and cracks that occur above the invert of the outlet. For
fiberglass, polyethylene, or polypropylene tanks, holes above the invert of the
outlet with a maximum dimension of up to one inch for fiberglass and half an
inch for polyethylene or polypropylene, using procedures established by the
manufacturer to restore watertightness by a person authorized by the
manufacturer.
(b) Damaged or
missing inlet and outlet seals may be replaced using the procedure of the
document entitled "Repair of Tank Inlet and Outlet Seals", effective
06-21-2022, herein adopted and incorporated by reference. Copies of this
document are available as provided in subsection (12), below and at
http://www.flrules.org/Gateway/reference.asp?No=Ref-14368.
(c) Chips that occur below the invert of the
outlet, provided that such chips do not penetrate more than 1/3 of the wall or
bottom thickness.
(12)
All materials incorporated herein may be obtained from the Department of
Environmental Protection, Onsite Sewage Program at
www.floridadep.gov or 2600 Blair Stone
Road, MS #3596, Tallahassee, Florida 32399-2400 or Florida Department of State,
Florida Administrative Code and Register, R.A. Gray Building, 500 South
Bronough Street, Tallahassee, Florida 32399-0250. Reference materials deemed
copyright protected are available for inspection at the same
address.