Fla. Admin. Code Ann. R. 69A-46.040 - Installation Requirements for Automatic Sprinkler Systems Employing Water as the Extinguishing Agent
(1)
Fire protection system contractors installing an automatic sprinkler system
employing water as the extinguishing agent shall supervise and be responsible
for the complete system in accordance with the provisions of section
633.334, F.S. The contractor
shall be responsible for installing the complete system in compliance with the
National Fire Protection Association (NFPA) standards adopted in rule chapter
69A-3, F.A.C., except that if a contractor installs only the underground
portion of the system from the point of service to the aboveground connection
flange, in compliance with subsection
633.334(3),
F.S., the contractor shall be responsible for only that portion of the system,
and the contractor installing the remaining portion shall be responsible for
the system from the point of connection to the underground throughout the
remainder of the system.
(2) The
complete system begins at the point-of-service as defined in subsection
633.102(24),
F.S., and ends at the most remote head inside the facility.
(3) In order to ensure that sufficient water
is available at the point-of-service to provide the water inside the facility
as required by the plans, the contractor who installs the underground portion
shall be responsible for conducting the acceptance tests required by NFPA 13
and shall personally, sign and maintain on file the Contractor's Material and
Test Certificate for Underground Piping as specified in NFPA 13, as adopted in
rule chapter 69A-3, F.A.C. If the above ground pipe is installed by a
contractor other than the one who installed the underground, the contractor
shall be responsible to obtain a copy of the underground certificate from the
underground contractor and maintain it on file before connection to the
underground is made. If the contractor is unable to obtain the certificate, the
contractor shall notify the Regulatory Licensing Section.
(4) Upon completion of the final installation
of the aboveground piping, the contractor shall conduct the tests and sign and
maintain on file the Contractor's Material and Test Certificate for Aboveground
Piping as specified in NFPA 13, as adopted in rule
69A-3.012, F.A.C.
(5) Failure to complete and maintain the two
certificates described in subsections (3) and (4), above, shall be grounds for
disciplinary action as violations of section
633.334, F.S.
(6) The contractor whose name appears on the
application for the building permit shall be responsible for the acceptance
tests required in NFPA 13, as adopted in rule chapter 69A-3, F.A.C. The
contractor or authorized agent shall complete all portions of the Contractor's
Material and Test Certificate(s) that are related to the system being tested.
The contractor or authorized agent shall sign and date the test certificates.
In cases where there is no building permit, the contractor that supervised the
installation shall be responsible for the performance of these
duties.
(7) The contractor shall
maintain on file all Contractor's Material and Test Certificates, and shall
provide such to the State Fire Marshal upon his request.
(8) Upon successful completion of acceptance
tests, newly installed fire protection systems shall not require a tag until
the first inspection occurs in accordance with rule
69A-46.041,
F.A.C.
Notes
Rulemaking Authority 633.104 FS. Law Implemented 633.306, 633.334, 633.338 FS.
New 12-21-88, Amended 8-1-90, 10-20-93, 11-21-01, Formerly 4A-46.040, Amended 5-18-08, 7-19-16.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.