Ga. Comp. R. & Regs. R. 120-3-27-.21 - Grounding
(1) No overcurrent
protection device shall be installed in neutral or grounding
conductors.
(2) Where electrical
power is supplied for an amusement ride by a generating system, the generator
and all equipment shall be properly grounded.
(3) All receptacles and attachment plugs
shall be of the grounding type.
(4)
Each electrically powered amusement ride shall be effectively grounded. The
grounding shall be made effective as to all non-current carrying metal parts
which may become energized and which are exposed to contact by any
persons.
(5) Grounding which does
not have a resistance to ground of 25 ohms or less shall be augmented by one
additional electrode of any of the types specified in Section 250-53 of the
Rule referenced in Rule
120-3-27-.21.