Haw. Code R. § 12-223.1-8 - Modular steam heating, modular hot-water heating boilers, and modular water heaters
(a) Individual
modules. The following shall apply to individual modules:
(1) The individual modules shall comply with
all the requirements of the code of construction and this subsection. The
individual modules shall be limited to a maximum input of 400,000 Btu per hour
(117 kw/hr) for gas, 3 gallons/hour (11.4 l/hr) for oil, or 117 kw for
electricity;
(2) Each module of a
modular steam heating boiler shall be equipped with a:
(A) Safety valve, see section
12-223.1-9(a)(1);
(B) Blowoff valve, see section
12-223.1-13(o)(1);
and
(C) Drain valve, see section
12-223.1-13(o)(2);
and
(3) Each module of a
modular hot-water heating boiler shall be equipped with a:
(A) Safety relief valve, see section
12-223.1-9(a)(2);
and
(B) Drain valve, see section
12-223.1-13(o)(2).
(b) Assembled Modular Heating boilers. The
following shall apply to assembled modular heating boilers:
(1) The individual modules shall be
manifolded together at the job site without any intervening valves;
(2) The assembled modular steam heating
boiler shall also be equipped with a:
(A)
Feedwater connection, see Exhibit 5, titled, "Steam Boilers in Battery -Pumped
Return Acceptable Piping Installation", dated October 1, 2023, which is made a
part of this chapter and located at the end of this chapter, and Exhibit 6,
titled, "Steam Boilers in Battery - Gravity Return Acceptable Piping
Installation", dated October 1, 2023, which is made a part of this chapter and
located at the end of this chapter; and
(B) Return pipe connection, see Exhibit 5,
titled, "Steam Boilers in Battery -Pumped Return Acceptable Piping
Installation", dated October 1, 2023, which is made a part of this chapter and
located at the end of this chapter, and 6, titled, "Steam Boilers in Battery
-Gravity Return Acceptable Piping Installation", dated October 1, 2023, which
is made a part of this chapter and located at the end of this chapter;
and
(3) The assembled
modular hot-water boiler shall also be equipped with a:
(A) Makeup water connection, see Exhibit 7,
titled, "Hot Water Boilers in Battery Acceptable Piping Installation", dated
October 1, 2023, which is made a part of this chapter and located at the end of
this chapter;
(B) Provision for
thermal expansion, see Exhibit 7, titled, "Hot Water Boilers in Battery
Acceptable Piping Installation", dated October 1, 2023, which is made a part of
this chapter and located at the end of this chapter, and Exhibit 8, titled,
"Expansion Tank Capacities for Gravity Hot-Water Systems", dated October 1,
2023, which is made a part of this chapter and located at the end of this
chapter; and
(C) Stop valves
(treating the assembled modular boiler as a single unit), see Exhibit 7,
titled, "Hot Water Boilers in Battery Acceptable Piping Installation", dated
October 1, 2023, which is made a part of this chapter and located at the end of
this chapter.
(c) Modular hot-water heating boilers. The
following shall apply to modular hot-water heating boilers:
(1) Each module of a modular hot-water
heating boiler shall be equipped with a:
(A)
Pressure or altitude gage, see section
12-223.1-7(b)(1);
(B) Thermometer, see section
12-223.1-7(b)(2);
and
(C) Temperature control, see
section 12-223.1-7(b)(3)(A);
and
(2) The assembled
modular hot-water heating boiler shall be equipped with a:
(A) Temperature control, see
12-223.1-7(b)(3)(B); and
(B)
Low-water fuel cutoff, see 12-223.1-7(b)(4).
(d) Modular steam heating boilers. The
following shall apply to modular steam heating boilers:
(1) Each module of a modular steam boiler
shall be equipped with a:
(A) Steam gage, see
section 12-223.1-7(a)(1);
(B) Water-gage glass, see section
12-223.1-7(a)(2);
(C) Pressure control, see section
12-223.1-7(a)(4)(A);
and
(D) Low-water cutoff, see
section 12-223.1-7(a)(5);
and
(2) The assembled
modular steam heating boiler shall also be equipped with a pressure control,
see section
12-223.1-7(a)(4)(B).
(e) Modular water heaters. The individual
modules shall comply with all the requirements of the code of construction and
this paragraph. Each module of a modular water heater shall be equipped with a:
(1) Safety relief valve, see section
12-223.1-9(a)(3);
(2) Drain valve, see section
12-223.1-13(o)(2);
(3) Pressure or altitude gage, see section
12-223.1-7(c)(2);
(4) Thermometer, see section
12-223.1-7(c)(3);
(5) Temperature control, see section
12-223.1-7(c)(1);
and
(6) Flow-sensing device, see
section 12-223.1-7(c)(4).
(f) Assembled modular water heaters having an
aggregate input value greater than 200,000 Btu per hour or aggregate water
containing capacity greater than 120 gallons. The individual modules shall be
manifolded together at the job site with or without any intervening valves. The
assembled modular potable water heater shall be equipped with a:
(1) Safety relief valve, see section
12-223.1-9(a)(3);
(2) Drain valve, see section
12-223.1-13(o)(2);
(3) Pressure/altitude gage, see
12-223.1-7(c)(2);
(4) Thermometer,
see section
12-223.1-7(c)(3);
(5) Temperature control, see section
12-223.1-7(c)(1);
and
(6) Flow-sensing device, see
12-223.1-7(c)(4).