Ill. Admin. Code tit. 77, § 890.1140 - Special Applications and Installations
a) Atmospheric Vacuum Breaker. An atmospheric
vacuum breaker shall be installed between the control valve and the fixture in
a manner that it will not be subject to water pressure, except the pressure
incidental to water flowing to the fixture. An atmospheric vacuum breaker shall
be installed on the outlet side of the control valve.
b) Flushometer Valve. Flush valves shall be
equipped with vacuum breakers installed on the discharge side of the flushing
valve with the critical level at least 4 inches above the overflow rim of the
bowl or 4 inches above the top of the urinal. (See Appendix I.Illustration
D.)
c) Flushing Tanks. Flushing
tanks shall be equipped with anti-siphon ballcocks. The ballcocks shall be
installed with the critical level of the vacuum breaker at least 1 inch above
the full opening of the overflow pipe. If the ballcock has no hush tube, the
bottom of the water supply inlet shall be installed 1 inch above the top of the
overflow pipe. (See Section
890.650(d).)
d) Lawn Sprinklers. Any lawn sprinkler system
connected to a potable water supply shall be equipped with an RPZ. The RPZ may
be located outside provided that it is protected from freezing or is removed at
the end of the season, and it complies with Section
890.1130(g)(1).
e) Valve Outlets for Hose Attachments
1) All threaded valve outlets shall have
backflow protection in accordance with Section
890.1130. All outside threaded
valve outlets shall not be subject to freezing.
2) Yard hydrants shall be installed as
follows:
A) Potable Water. All hydrants with
threaded spigots shall have backflow protection attached to the hydrant spigot
(if threaded) and either:
i) Hydrants with
buried drain down (weep) holes shall have the weep holes protected from ground
water backup by proper open site drainage. A backflow preventer shall not be
used on the buried weep hole to protect the hydrant from ground water backup;
or
ii) A yard hydrant that
automatically drains back to a sealed container when flow is shut off, such as
a canister type hydrant.
B) Non-potable Water. One or more hydrants
may be installed for non-potable use if they are isolated from the potable
water supply by a backflow preventer device installed in accordance with
Section 890.1130(f).
The hydrants shall be clearly identified as non-potable by color (see Section
890.1120) and bear a sign that
reads as follows: "This water unsafe for drinking."
3) In a campground licensed in accordance
with the Department's rules titled Youth Camp Code or Recreational Area Code,
backflow protection is not required if the water supply line is directly
connected to a recreational vehicle and is under constant pressure.
f) Commercial Laundry Machines.
The potable water supply to commercial laundry machines shall be protected
against back siphonage by an air gap or backflow protection device. If a vacuum
breaker is used, it shall be a minimum of 26 inches above the top of the
machine.
g) Commercial Dishwashers.
Commercial dishwashers shall be equipped with an approved vacuum breaker
located in the rinse water supply line on the discharge side of the final
control valve, a minimum distance of 6 inches above the uppermost spray
outlets. The cold water or make-up water supply line shall be provided with an
air gap or a vacuum breaker located on the discharge side of the final control
valve, a minimum distance of 6 inches above the overflow level or flood
rim.
h) Aspirators. Water-operated
aspirators shall meet the following specifications:
1) The water supply line shall be equipped
with a shut-off valve.
A) If aspirators are
used in operating rooms, emergency rooms, recovery rooms, delivery rooms,
autopsy rooms, dental offices and laboratories for removing blood, pus or other
fluids, a vacuum breaker shall be installed on the discharge side of the
control valve, at ceiling height (a minimum of 7 feet, 6 inches) and the water
supply shall be protected against backflow and back siphonage by an air gap; or
an RPZ shall be used.
B) Chemical
dispensing units shall have a dedicated water supply and shut-off valves to
each unit. Each unit shall have a backflow device installed to protect against
backflow and back siphonage.
2) The aspirator water discharge shall be
provided with a 2-inch air gap to the receiving fixture.
i) Manufactured Housing and Mobile Home Units
Manufactured Prior to June 15, 1976. At the time of water service connection,
backflow protection shall be installed between the water service line and any
manufactured housing or mobile home unit that was manufactured prior to June
15, 1976. Backflow protection shall be provided by at least a dual check valve
backflow preventer assembly (DuC) conforming to ASSE 1024. This backflow
protection shall be installed in all instances where a unit manufactured prior
to June 15, 1976 is connected or re-connected to a water service line, e.g.,
for connection of a relocated unit, or re-connection of a unit that was
disconnected to allow repairs to the water line; however, backflow protection
is not required for existing units unless a new connection or re-connection to
the water service line occurs.
j)
Carbonated Beverage Dispensers Water Supply. The water supply to carbonated
beverage dispensers shall be protected by one of the following methods:
1) Air gap;
2) ASSE 1022 backflow preventer; or
3) ASSE 1022 backflow preventer with vent
port added.
k)
Water-Powered Sump Pump. Sump pumps powered by potable or reclaimed water
pressure shall be used only as an emergency backup pump. The water-powered pump
shall be equipped with a battery powered alarm having a minimum rating of 85
dBa at 10 feet. Water-powered pumps shall have a water efficiency factor of
pumping at least 1.4 gallons of water to a height of 10 feet for every gallon
of water used to operate the pump, measured at a water pressure of 60 psi.
Pumps shall be clearly labeled as to the gallons of water pumped per gallon of
potable water consumed. Water-powered stormwater sump pumps shall be equipped
with a dual check valve with atmospheric vent conforming to ASSE 1012 or CSA
B64.