Ill. Admin. Code tit. 77, § 905.80 - Re-circulating Sand Filter
a)
General. The re-circulating sand filter system (Appendix A, Illustration O)
consists of a septic tank, recirculation tank, open sand filter and flow
splitter. It may be used provided that the effluent is discharged in accordance
with the requirements of Section
905.110.
b) Septic Tank. The septic tank shall be
sized and installed as described in Section
905.40.
c) Re-circulation Tank. The re-circulation
tank volume shall be 500 gallons, and the tank shall be equivalent in strength
and materials to the septic tank as provided in Section
905.40. No baffles are
necessary. An access manhole, as described in Section
905.40(b)(7),
shall be provided for pump maintenance or replacement.
d) Sand Filter. The sand filter shall be
sized at one square foot of filter surface for every 3 gallons per day of
domestic sewage flow. Appendix A, Illustration P has a size chart for
residences based on numbers of bedrooms. Unless otherwise stated in Appendix A,
Illustration P, the sizes shown are required. The filter media shall comply
with requirements of Section
905.70(e) and
(f) and shall be 30 inches in
depth.
e) Bedding Material. The
bedding material for the collection lines shall be the same as that in a buried
sand filter. The coarse gravel shall be 3/4 to 21/2 inch diameter, and the pea
gravel shall be from 1/8 to 3/8 inches diameter. A minimum of 2 inches of
coarse gravel shall be placed on the excavation prior to placement of
collection lines.
f) Distribution
and Collection Lines. The collection lines shall be constructed of materials as
approved in Section 905.20(f) and
shall be 4 inches inside diameter perforated piping laid with perforations
facing downward. The distribution piping shall have an inside diameter of 11/2
inches. The perforated pipe shall have 1/2 to 3/4 inch diameter openings on
3-inch to 5-inch centers with 2 rows at 120° from each other. Distribution
piping shall be spaced on 3-foot centers and shall be located a minimum of 11/2
feet from sidewalls.
g) Pumps. The
pump shall be a submersible pump designed for corrosive liquids and shall have
a capacity of 15 to 25 gallons per minute at the 10-foot total dynamic head
(TDH). The pump shall be controlled by a time clock that can be set to activate
the pump at one hour or longer intervals. Pump shut-off shall be controlled by
a low level float switch that allows the entire contents of the re-circulation
tank to be pumped during each pump cycle. A high level float switch shall be
provided that energizes a visible and audible alarm to indicate pump failure or
malfunction. (See Appendix A, Illustration Q.)
h) Flow Splitter. The flow splitter shall be
designed so that re-circulation rates can be controlled between no
re-circulation and a 5:1 re-circulation ratio. An example of one type of
splitter is shown in Appendix A, Illustration O.
Notes
Amended at 37 Ill. Reg. 14994, effective August 28, 2013