This rule applies to power boilers installed prior to July 1,
1983.
(1) The use of weighted-lever
safety valves or safety valves having either the seat or disk of cast iron is
prohibited. All power boilers shall have direct, springloaded, pop-type safety
valves that conform to the construction or installation code.
(2) Each boiler shall have at least one
safety valve. All boilers with more than 500 square feet of water heating
surface or an electric power input of more than 1100 kilowatts shall have two
or more safety valves.
(3) The
safety valve or valves shall be connected to the boiler independent of any
other steam connection and attached as close as possible to the boiler without
unnecessary intervening pipe or fittings.
(4) No valves of any type shall be placed
between the safety valve and the boiler If an escape pipe is used, no valve
shall be placed between the safety valve and the atmosphere. When an escape
pipe is used, it shall be at least full size of the safety valve discharge and
fitted with an open drain to prevent water lodging in the upper part of the
safety valve or escape pipe. Any elbow on an escape pipe shall be located close
to the safety valve outlet or the escape pipe and shall be anchored and
supported securely. All safety valve discharges shall be so located or piped as
to be carried away from walkways or platforms. When the safety valve is vented
to the outside atmosphere, the second escape pipe shall be arranged as shown in
Figure 1.
Click here to
view Image
(5)
The safety valve capacity of each boiler shall be such that the safety valve or
valves will discharge all the steam that can be generated by the boiler without
allowing the pressure to rise more than 5 percent above the highest pressure to
which any valve is set and in no case to more than 6 percent above maximum
allowable working pressure.
(6) One
or more safety valves on every boiler shall be set at or below the maximum
allowable working pressure. The remaining valves may be set within a range of 3
percent above the maximum allowable working pressure, but the range setting of
all the safety valves on a boiler shall not exceed 10 percent of the highest
pressure at which any valve is set.
(7) When two or more boilers operating at
different pressures and safety valve settings are interconnected, the lowest
pressure boilers or interconnected piping shall be equipped with safety valves
of sufficient capacity to prevent overpressure, considering the maximum
generating capacity of all boilers.
(8) In those cases where the boiler is
supplied with feedwater directly from water mains without the use of feeding
apparatus (not including return traps), safety valves shall not be set at a
pressure greater than 94 percent of the lowest pressure maintained in the
supply main feeding the boiler.
(9)
The minimum safety valve relieving capacity shall be determined on the basis of
the pounds of steam generated per hour per square foot of boiler heating
surface and waterwall heating surface as given in the following table. This
method shall not be used on electric boilers, waste heat boilers and
forced-flow steam generators without a fixed steam and water line.
Minimum Pounds of Steam Per Hour Per Square Foot of Heating
Surface
Boiler Heating Surface: Firetube Boilers Watertube
Boilers
Hand Fired...................................... 5 6
Stoker Fired..................................... 5 8
Oil, Gas, or Pulverized Fuel Fires...................... 8
10
Waterwall Heating Surface:
Hand Fired...................................... 8 8
Stoker Fired..................................... 10
12
Oil, Gas, or Pulverized Fuel Fires...................... 14
16
(10) Safety valve
sizing.
a. When a boiler is fired only by a
gas having a heat value not in excess of 200 Btu's per cubic feet the minimum
safety valve relieving capacity may be based on the value given for hand-fired
boilers above.
b. The minimum
safety valve relieving capacity for electric boilers shall be 3/4 pounds per
hour per kilowatt input.
c. Maximum
steaming capacity for safety valves shall be the value stated on design
documents or shall be calculated by multiplying horsepower by 34.5.