Iowa Code r. 875-72.12 - Alterations, repairs, replacements and maintenance
(1)
General. Except as set
forth in this rule, all maintenance, repairs, replacements, and alterations
comply with the edition of ASME A17.1 currently adopted for new conveyances or
ASME A17.7-2007/CSA B44-07, as applicable. "Alterations" in 875-Chapter 71
describes alterations that require that the entire conveyance be brought into
compliance with the most current codes.
(2)
Exemption for button
renumbering. All maintenance, repairs and alterations to devices
covered by ANSI A117.1 comply with ANSI A117.1 (2017), except for requirement
407.4.7.1.2.
(3)
Sump pump
exemption. The provisions of ASME A17.1 that require a pit sump or
drain do not apply to an elevator alteration when all of the following criteria
are met:
a. No other code or rule requires
that the pit be excavated or lowered.
b. The alteration plans do not include the
excavation or lowering of the pit floor for any other reason.
c. There is evidence that groundwater has not
entered the pit previously.
d. The
location and geology of the building indicate a likelihood that groundwater
would enter the pit if the foundation or pit floor were breached to install the
pit sump or drain.
e. A description
of alternative means to maintain the pit in a dry condition is provided to the
director with the alteration permit application.
f. The director approves the alternative
means to maintain the pit in a dry condition.
g. The alternative means to maintain the pit
in a dry condition are installed or implemented as described in the alteration
permit application.
(4)
Pit excavation exemption. For elevators altered before August
1, 2018, the full length of the platform guard set forth in ASME A17.1, Rule
2.15.9.2(a), will not be required if all of the following criteria are met:
a. No other code or rule requires that the
pit be excavated or lowered.
b. The
alteration plans do not include the excavation or lowering of the pit floor for
any other reason.
c. A full-length
platform guard would strike the pit floor when the elevator is on its fully
compressed buffer.
d. The clearance
between the bottom of the platform guard and the pit floor is 2.5 centimeters
(1 inch) when the elevator is on its fully compressed buffer.
(5)
Sprinkler retrofits
and shunt trip breakers. When a sprinkler is added to a hoistway or
machine room, the conveyance shall comply with the following:
a. The installation complies with the
applicable version of ASME A17.1, Rule 2.8.3.3.
b. The elevator controls comply with the
phase I fire recall provisions of the applicable version of ASME A17.1, Rule
2.27.3.
(6)
Alterations of handicapped restricted use elevators. A
component of a handicapped restricted use elevator being altered will comply
with the portions of ASME A17.1, section
5.3, applicable to the
component. The edition of ASME A17.1 adopted by reference in rule
875-72.1 (89A) will be
applied.
(7)
Hoistway
lighting. If the controller for an elevator is being replaced,
permanent lighting shall be installed in the hoistway of the elevator.
Three-way switches to control the hoistway lighting shall be installed at the
pit access door and the top landing access door. The lighting will be
sufficient to provide 10 foot-candles of light to the center of the elevator
path measured when the car top lights are off. Engineering calculations that
prove 10 foot-candles of light are provided to the center of the elevator path
may be substituted for light meter measurements under circumstances such as a
glass back car where use of a light meter is not practical.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.