Mich. Admin. Code R. 339.5206 - Adoption; ASME code CSD-1
Rule 206.
(1)
An owner or user of a boiler shall ensure that the installation, maintenance,
operation, and testing of controls and safety devices is pursuant to
manufacturers instructions and ASME code CSD-1, 2018 edition. The code is
adopted by reference as amended in these rules and available for inspection and
purchase at the Michigan Department of Licensing and Regulatory Affairs, Bureau
of Construction Codes, 611 W. Ottawa, Lansing, Michigan 48933 or for purchase
from the ASME International, Two Park Avenue, New York, New York 10016-5990,
(800) 843-2763, https://www.asme.org, at a cost as of the
time of adoption of these rules of $103.00 for each code book.
(2) An owner or user of a boiler system shall
ensure that the maintenance and testing of controls and safety devices is
conducted by an individual with a valid mechanical contractor license with the
appropriate classification under the act. Individuals conducting maintenance
and testing must be under the guidance and supervision of a licensed mechanical
contractor.
(3) An owner or user
shall provide to the inspector, at the time of certificate inspection, evidence
showing what maintenance has been performed and what tests have been completed.
The evidence must be a dated and signed service report or checklist, listing
each control and safety device tested with the manufacturers name, model
number, set point, and actual operational test point. The service report must
include the license number and heating service classification of the mechanical
contractor who is performing or supervising the work.
(4) If an owner does not provide the
inspector with the required evidence of maintenance and testing between
certificate inspections, then the inspector may issue a certificate of
inspection for a term less than that stated under section 943 of the act, MCL
339.5943.
(5) For hot water heating and hot water
supply boilers with a BTU input of 400,000 or less, the requirements of this
subrule must be conducted once during an inspection cycle but must be performed
within 12 months before the certificate inspection required by
R 339.5213.
(6) An owner, user, or operator of a boiler
system shall ensure that the daily, weekly, and monthly operational checks are
performed and documented pursuant to the manufacturers instructions and these
rules. If the manufacturers instructions are not available, CSD-1, 2018
edition, nonmandatory appendix D contains a recommended checklist for
additional information on periodic checks.
(7) A manually operated remote shutdown
switch, as required by CSD-1, 2018 edition, must be located outside of each
exit access doorway to the boiler room. The switch may be located just inside
each exit access doorway should a possibility of tampering or weather
conditions exist. A licensee may request a deviation from the requirements of
this subrule by submitting a drawing clearly showing the deviation and stating
justification for the request to the chief inspector for review and approval
before the installation of a boiler. The chief inspector shall notify the
licensee of the approval or denial of the request.
(8) A single manually operated remote
shutdown switch may be used in a multiple boiler installation that shares a
common boiler room. Kitchen cooking boilers, steam kettles, and steam cookers
used for food preparation located in a kitchen are exempt from having a
manually operated remote shutdown switch and lockable disconnect.
(9) Where applicable, the boiler installation
must comply with the,
R 408.30901 to
R 408.30998;
R 408.30701 to
R 408.30796; and
R 408.30801 to
R 408.30880.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.