PURPOSE: This rule contains requirements for
UST systems that were in use on December 22, 1998, and were upgraded with
release prevention equipment.
PUBLISHER'S NOTE: The secretary of state has
determined that the publication of the entire text of the material which is
incorporated by reference as a portion of this rule would be unduly cumbersome
or expensive. This material as incorporated by reference in this rule shall be
maintained by the agency at its headquarters and shall be made available to the
public for inspection and copying at no more than the actual cost of
reproduction.
This note applies only to the reference material. The
entire text of the rule is printed here.
(1) Alternatives Allowed. All underground
storage tank (UST) systems which are in-use must comply with one (1) of the
following requirements:
(B) The upgrading requirements in sections
(3)-(5) of this rule.
(2)
Any UST which was not permanently closed by being removed or filled with an
inert, solid material before December 22, 1988, and that does not meet the
requirements of section (1) shall be permanently closed in accordance with the
requirements in
10 CSR 26-2.060 through
10 CSR
26-2.064. If the UST was taken out of operation by
August 28, 1989, but is still in the ground, the person or party responsible
for permanently closing the UST is/are the person(s) who owned the UST
immediately before the discontinuation of its use.
(3) Tank Upgrading Requirements. Tanks must
be upgraded to meet one (1) of the following requirements in accordance with a
code of practice developed by a nationally-recognized association or
independent testing laboratory:
(A) Interior
Lining or Tank Retrofit. A tank may be upgraded by internal lining or retrofit
if-
1. The lining is installed in accordance
with the requirements of
10 CSR
26-2.033 and the lining or retrofit meets the
following additional requirements:
A. All
linings installed or repaired on or after January 1, 2020, must meet the design
specifications of Underwriters Laboratories (UL) 1856 Outline of
Investigation for Underground Fuel Tank Internal Retrofit Systems
requirements;
B. Inspections and
repairs must be conducted by a technician who is properly certified by NACE
International or International Code Council (ICC);
C. The lining or retrofit is installed
according to manufacturer installation requirements;
D. An approved national code or standard,
including those listed in section (7) of this rule, is followed;
E. For fiberglass-reinforced plastic tanks,
all linings must be approved by the tank manufacturer and installed in
accordance with the tank manufacturer's requirements. If the tank manufacturer
is no longer available or willing to repair the tank, the tank may be lined in
accordance with-
(I) The manufacturer's
requirements, or
(II) The
Fiberglass Tank & Piping Institute T-95-1.
Remanufacturing of
Fiberglass Reinforced Plastic (FRP) Underground Storage Tanks, Revised
1995. This document is incorporated by reference without any later amendments
or modifications. To obtain a copy, contact the Fiberglass Tank and Piping
Institute,
http://www.fiber-glasstankandpipe.com;
and
(III) By a technician who is
properly certified by NACE International, International Code Council (ICC), or
the American Composites Manufacturers Association;
F. All linings must be installed, inspected,
repaired, and maintained in accordance with one (1) of the following:
(I) For UL 1856 Lining systems,
single-walled, co-structural systems and linings installed prior to January 1,
2020:
(a) A lining may only be repaired if the
tank passes an integrity test, including actual shell thickness readings for
steel tanks. Approved integrity test methods are included in section (7) of
this rule;
(b) A lining may only be
installed if the new lining meets the UL 1856 specifications and the steel tank
passes an integrity test, including actual steel shell thickness readings.
Approved integrity test methods are included in section (7) of this
rule;
(c) The lining must be
internally inspected at least every five (5) years and found to be structurally
sound with the lining still performing in accordance with the original design
specifications;
(II) For
UL 1856 Upgrade systems, double-walled, co-structural systems:
(a) A lining may only be installed or
repaired if the tank passes an integrity test, including actual shell thickness
readings for steel tanks. Approved integrity test methods are included in
section (7) of this rule; and
(b)
The lining must be internally inspected at least every five (5) years and found
to be structurally sound with the lining still performing in accordance with
the original design specifications; or
(c) The interstitial lining space is
electronically monitored, with passing sensor status reports for the most
recent twelve (12) months, in accordance with
10 CSR
26-2.043 subsection (1)(H);
(III) For UL 1856 Structural systems,
double-walled, self-structural systems-
(a)
The lining must be internally inspected at least every five (5) years and found
to be structurally sound with the lining still performing in accordance with
the original design specifications; or
(b) The interstitial lining space is
electronically monitored, with passing sensor status reports for the most
recent twelve (12) months, in accordance with
10 CSR
26-2.043 subsection
(1)(H);
G. All
interior lining inspection reports must include photographs of the tank bottom,
a representative tank side wall and a representative tank end, and
documentation of the interior lining hardness and thickness readings, in
accordance with the evaluation guidance document used;
(B) Cathodic Protection. A tank
may be upgraded by cathodic protection if the cathodic protection system meets
the requirements of the performance standards for new UST systems in
10 CSR
26-2.020(1)(A) 2.B.- D. and the
integrity of the tank is ensured using one (1) of the following methods:
1. The tank is internally inspected and
assessed to ensure that the tank is structurally sound and free of corrosion
holes prior to installing the cathodic protection system. Structural integrity
evaluations must include steel shell thickness readings and confirmation that
the steel shell does not have any holes or perforations. Approved integrity
test methods are included in section (7) of this rule;
2. The tank has been installed for less than
ten (10) years and is monitored monthly for releases in accordance with release
detection methods in
10 CSR
26-2.043(1)(E)-(I);
3. The tank has been installed for less than
ten (10) years and is assessed for corrosion holes by conducting two (2)
tightness tests that meet the requirement of release detection method in
10 CSR
26-2.043(1)(D). The first tightness
test must be conducted prior to installing the cathodic protection system. The
second tightness test must be conducted between three and six (3-6) months
following the first operation of the cathodic protection system; or
4. The tank is assessed for corrosion holes
by a method that is determined by the department to prevent releases in a
manner that is no less protective of human health and the environment than
paragraphs (3)(B)1.-3. of this rule; and
(C) Internal Lining Combined With Cathodic
Protection. A tank may be upgraded by both internal lining and cathodic
protection if-
1. The lining is installed in
accordance with the requirements of
10 CSR
26-2.033; and
(4)
Piping Upgrading Requirements. Metal piping that routinely contains regulated
substances and is in contact with an electrolyte, including, but not limited
to, soil, backfill, and/or water, must be cathodically protected and must meet
the requirements of
10 CSR
26-2.020(1)(B) 3.B.-E.
(A) New piping installed at an existing
facility must comply with the requirements of
10 CSR
26-2.020.
(5) Spill and Overfill Prevention Equipment.
To prevent spilling and overfilling associated with product transfer to the UST
system, all existing UST systems must comply with new UST system spill and
overfill prevention equipment requirements specified in
10 CSR
26-2.020(1)(C) and
10 CSR
26-2.030.
(6) Dispenser Systems. Any new dispenser
installed after July 1, 2017, must have a containment sump beneath it, in
accordance with
10 CSR
26-2.020(1)(E).
(7) The following codes and standards may be
used to comply with this rule:
(A) American
Petroleum Institute Standard 1631,
Interior Lining and Periodic
Inspection of Underground Storage Tanks, revised 2001. This document
is incorporated by reference without any later amendments or modifications. To
obtain a copy, contact the American Petroleum Institute, 1220 L Street NW,
Washington, DC 20005, (202) 682-8000,
www.api.org/standards/;
(B) NACE International RP 0285-2002,
Corrosion Control of Underground Storage Tank Systems by Cathodic
Protection, revised 2002. This document is incorporated by reference
without any later amendments or modifications. To obtain a copy, contact NACE
International, Box 218340, Houston, TX 77218-8340, (713) 492-0535,
www.nace.org;
(C) American Petroleum Institute Publication
1632,
Cathodic Protection of Underground Petroleum Storage Tanks and
Piping Systems, revised 2002. This document is incorporated by
reference without any later amendments or modifications. To obtain a copy,
contact the American Petroleum Institute, 1220 L Street NW, Washington, DC
20005, (202) 682-8000,
www.api.org/stan-dards/;
(D) American Society for Testing and
Materials G158-98 (2010)
Standard Guide for Three Methods of Assessing
Buried Steel Tanks, revised 2010, Method B only. Methods A and C may
not be used to evaluate the integrity of a steel tank. This document is
incorporated by reference without any later amendments or modifications. To
obtain a copy, contact the American Society for Testing and Materials, 100 Barr
Harbor Drive, West Conshohocken, PA 19428-2959, (610) 832-9500,
www.astm.org;
(E) National Leak Prevention Association
Standard 631,
Spill Prevention, Minimum 10 Year Life Extension of
Existing Steel Underground Tanks by Lining Without the Addition of Cathodic
Protection, revised 1999. This standard may only be used for interior
lining application and inspection, not for inspection of the steel tank
integrity. This document is incorporated by reference without any later
amendments or modifications. To obtain a copy, contact the National Leak
Prevention Association, (815) 301-2785,
www.nlpa-online.org;
(F) Ken Wilcox Associates Recommended
Practice,
Recommended Practice for Inspecting Buried Lined Steel Tanks
Using a Video Camera, September 28, 1999. This document is
incorporated by reference without any later amendments or modifications. To
obtain a copy, contact Ken Wilcox Associates, 1125 Valley Ridge Drive, Grain
Valley, MO 64029, (816) 443-2494,
www.kwaleak.com; and
(G) Underwriters Laboratory (UL)
1856
Outline of Investigation for Underground Fuel Tank Internal Retrofit
Systems, June 2013. This document is incorporated by reference without
any later amendments or modifications. To obtain a copy, contact the
Underwriters' Laboratories, 333 Pfingsten Road, Northbrook, IL 60062-2096,
(847) 272-8800,
www.ul.com.