N.M. Admin. Code § 17.9.568.11 - IEEE 1547-2018 ADOPTION
A. Beginning on March 28, 2023 (or another
date set by commission order), generating facilities shall be required to
comply with IEEE 1547-2018, and shall conform with the following minimum
requirements.
(1)
Abnormal performance
requirements: Category III ride through capabilities must be supported
for inverter-based generating facilities. Rotating generating facilities must
meet category I ride-through capabilities.
(2)
Normal performance
requirements: Inverter-based generating facilities shall meet reactive
power requirements with category B. Rotating generating facilities must meet
category A.
B. Each
utility shall post its preferred default settings in their public facing
Technical Interconnection and Interoperability Requirements (TIIR) document. As
applicable the following shall be identified in the TIIR documents:
(1) voltage and frequency trip
settings;
(2) frequency droop
settings;
(3) activated reactive
power control function and default settings;
(4) voltage active power (volt-watt) mode
activation and default settings;
(5) communication protocols and ports
requirements.
C. TIIR
documents shall be created through a technical advisory group process and
submitted to the commission for approval. Subsequent changes to TIIR documents
shall also be submitted to the commission for approval.