(A)
Section 5101 General
(1)
5101.1 Scope. The
provisions of this rule, the building code and NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code shall apply to the manufacturing, storage and
display of aerosol products. Manufacturing of aerosol products using hazardous
materials shall also comply with rule
1301:7-7-50
of the Administrative Code.
(2)
5101.2 Permit
required. Permits shall be required as set forth in rule
1301:7-7-01
of the Administrative Code.
(3)
5101.3 Material
Safety Data Sheets. Material Safety Data Sheet (MSDS) information for aerosol
products displayed shall be kept on the premises at an approved
location.
(4)
5101.4 Containers. Metal aerosol containers shall be
limited to a maximum size of 33.8 fluid ounces (1000 ml). Plastic aerosol
containers shall be limited to a maximum 4 fluid ounces (118 ml) except as
provided in paragraph (D)(1)(a)(5104.1.1) of this rule. Glass aerosol
containers shall be limited to a maximum 4 fluid ounces (118
ml).
(B)
Section 5102 Definitions
(1)
5102.1
Definitions. The following terms are defined in rule
1301:7-7-02 of the
Administrative Code.
"Aerosol."
"Level 1 aerosol
products."
"Level 2 aerosol
products."
"Level 3 aerosol
products."
"Aerosol container."
"Aerosol warehouse."
"Propellant."
"Retail display area."
(C)
Section 5103 Classification of aerosol products
(1)
5103.1
Classification levels. Aerosol products shall be classified as Level 1, 2 or 3
in accordance with Table 5103.1 of this rule and NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code. Aerosol products in cartons that are not identified
in accordance with this paragraph shall be classified as Level 3.
Table 5103.1 Classification of aerosol
products
|
Chemical heat of
combustion
|
Aerosol
classification
|
|
Greater than
(Btu/lb)
|
Less than or equal to (Btu/
lb)
|
|
0
|
8,600
|
1
|
|
8,600
|
13,000
|
2
|
|
13,000
|
-----
|
3
|
For SI: 1 British thermal unit per
pound = 0.002326 KJ/g.
(2)
5103.2
Identification. Cartons shall be identified on not less than one side with the
classification level of the aerosol products contained within the carton as
follows:
"LEVEL AEROSOLS"
(D)
Section 5104 Inside storage of aerosol products
(1)
5104.1 General.
The inside storage of Level 2 and 3 aerosol products shall comply with
paragraphs (D)(2)( 5104.2) to (D)(7)( 5104.7) of this rule and NFPA 30B as
listed in rule
1301:7-7-80
of the Administrative Code. Level 1 aerosol products and those aerosol products
covered by paragraph (D)(1)(a)(510411) of this rule shall be considered
equivalent to a Class III commodity and shall comply with the requirements for
palletized or rack storage in NFPA 13 as listed in rule
1301:7-7-80
of the Administrative Code.
(a)
5104.1.1 Plastic containers. Aerosol products in
plastic containers larger than 4 fluid ounces (118 ml), but not to exceed 33.8
fluid ounces (1000 ml), shall be allowed only where in accordance with this
paragraph. The commodity classification shall be Class III commodities, as
defined in NFPA 13 as listed in rule
1301:7-7-80
of the Administrative Code where any of the following conditions are met:
(i)
Base product has
no fire point where tested in accordance with ASTM D 92 as listed in rule
1301:7-7-80
of the Administrative Code, and nonflammable propellant.
(ii)
Base product has
no sustained combustion as tested in accordance with Appendix H, "Method of
Testing for Sustained Combustibility," in DOTn 49 CFR Part 173 as listed in
rule
1301:7-7-80
of the Administrative Code, and nonflammable propellant.
(iii)
Base product
contains up to 20 per cent by volume ( 15.8 per cent by weight) of ethanol
and/or isopropyl alcohol in an aqueous mix, and nonflammable
propellant.
(iv)
Base product contains 4 per cent by weight or less of
an emulsified flammable liquefied gas propellant within an aqueous base. The
propellant shall remain emulsified for the life of the product. Where such
propellant is not permanently emulsified, the propellant shall be
nonflammable.
(2)
5104.2 Storage in
Groups A, B, E, F, I and R. Storage of Level 2 and 3 aerosol products in
occupancies in Groups A, B, E, F, I and R shall be limited to the following
maximum quantities:
1.
A net weight of 1,000 pounds (454 kg) of Level 2
aerosol products.
2.
A net weight of 500 pounds (227 kg) of Level 3 aerosol
products.
3.
A combined net weight of 1,000 pounds (454 kg) of Level
2 and 3 aerosol products.
The maximum quantity shall be increased
100 per cent where the excess quantity is stored in storage cabinets in
accordance with paragraph (D)(3)(b)(5704.3.2) of rule
1301:7-7-57
of the Administrative Code.
(a)
5104.2.1 Excess storage. Storage of quantities
exceeding the maximum quantities indicated in paragraph (D)(2)(5104.2) of this
rule shall be stored in separate inside flammable liquid storage rooms in
accordance with paragraph (D)(5)( 5104.5) of this rule.
(3)
5104.3 Storage in general purpose warehouses. Aerosol
storage in general purpose warehouses utilized only for warehousing-type
operations involving mixed commodities shall comply with paragraph
(D)(3)(a)(5104.3.1) or (D)(3)(b)(5104.3.2) of this rule.
(a)
5104.3.1
Nonsegregated storage. Storage consisting of solid pile, palletized or rack
storage of Level 2 or 3 aerosol products not segregated into areas utilized
exclusively for the storage of aerosols shall comply with Table 5104.3.1 of
this rule.
Table 5104.3.1 Nonsegregated storage of
Level 2 and 3 aerosol products in general purpose warehousesb
|
Less than or equal to
(Btu/lb)
|
Maximum net weight per floor
(pounds)b
|
|
Palletized or solid-pile
storage
|
Rack storage
|
|
Unprotected
|
Protecteda
|
Unprotected
|
Protecteda
|
|
2
|
2,500
|
12,000
|
2,500
|
24,000
|
|
3
|
1,000
|
12,000
|
1,000
|
24,000
|
|
Combination 2 and
3
|
2,500
|
12,000
|
2,500
|
24,000
|
For SI: 1 foot = 304.8 mm, 1 pound =
0.454 kg, 1 square foot = 0.0929 m2.
a.
Approved automatic
sprinkler system "'protection and storage arrangements shall comply with NFPA
30B as listed in rule
1301:7-7-80
of the Administrative Code. Sprinkler system protection shall extend 20 feet
beyond the storage area containing the aerosol products.
b.
Storage quantities
indicated are the maximum permitted in any 50,000-square-foot
area.
(b)
5104.3.2 Segregated storage. Storage of Level 2 and 3
aerosol products segregated into areas utilized exclusively for the storage of
aerosols shall comply with Table 5104.3.2 of this rule and paragraphs
(D)(3)(b)(i)(5104.3.2.1) and (D)(3)(b)(ii)(5104.3.2.2) of this rule.
Table 5104.3.2 Segregated storage of
Level 2 and 3 aerosol products in general purpose warehouses
|
Storage
separation
|
Maximum segregated storage
areaa
|
Sprinkler
requirements
|
|
Percentage of building area
(per cent)
|
Area limitation (square
feet)
|
|
Separation areae,
f
|
15
|
20,000
|
Notes b, c
|
|
Chain-link fence enclosured
|
20
|
20,000
|
Notes b, c
|
|
1-hour fire-resistance-rated
interior walls
|
20
|
30,000
|
Note b
|
|
2-hour fire-resistance-rated
interior walls
|
25
|
40,000
|
Note b
|
|
3-hour fire-resistance-rated
interior walls
|
30
|
50,000
|
Note b
|
For SI: 1 foot = 304.8 mm, 1 square
foot = 0.0929 m2.
a.
The maximum
segregated storage area shall be limited to the smaller of the two areas
resulting from the percentage of building area limitation and the area
limitation.
b.
Automatic sprinkler system protection in aerosol
product storage areas shall comply with NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code and be approved. Building areas not containing
aerosol product storage shall be equipped throughout with an approved automatic
sprinkler system in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
c.
Automatic
sprinkler system protection in aerosol product storage areas shall comply with
NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code and be approved. Sprinkler system protection shall
extend a minimum 20 feet beyond the aerosol storage area.
d.
Chain-link fence
enclosures shall comply with paragraph (D)(3)(b)(i)(5104.3.2.1) of this
rule.
e.
A separation area shall be defined as an area extending
outward from the periphery of the segregated aerosol product storage area as
follows:
1.
The
limits of the aerosol product storage shall be clearly marked on the
floor.
2.
The separation distance shall be not less than 25 feet
and maintained clear of all materials with a commodity classification greater
than Class III in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code.
f
Separation areas
shall only be permitted where approved.
(i)
5104.3.2.1
Chain-link fence enclosures. Chain-link fence enclosures required by Table
5104.3.2 of this rule shall comply with the following:
(a)
The fence shall
not be less than No. 9 gage steel wire, woven into a maximum 2-inch (51 mm)
diamond mesh.
(b)
The fence shall be installed from the floor to the
underside of the roof or ceiling above.
(c)
Class IV and
high-hazard commodities shall be stored outside of the aerosol storage area and
not less than 8 feet (2438 mm) from the fence.
(d)
Access openings
in the fence shall be provided with either self- or automatic-closing devices
or a labyrinth opening arrangement preventing aerosol containers from rocketing
through the access openings.
(e)
Not less than two
means of egress shall be provided from the fenced
enclosure.
(ii)
5104.3.2.2 Aisles. The minimum aisle requirements for
segregated storage in general purpose warehouses shall comply with Table
5104.3.2.2 of this rule.
Table 5104.3.2.2 Segregated storage
aisle widths and distance to aisles in general purpose warehouses
|
Storage
condition
|
Minimum aisle width
(feet)
|
Maximum distance from storage
to aisle (feet)
|
|
Solid pile or
palletizeda
|
4 feet between
piles
|
25
|
|
Racks with ESFR
sprinklersa
|
4 feet between racks and
adjacent Level 2 and 3 aerosol product storage
|
25
|
|
Racks without ESFR
sprinklersa
|
8 feet between racks and
adjacent Level 2 and 3 aerosol product storage
|
25
|
For SI: 1 foot = 304.8 mm.
a.
Sprinklers shall
comply with NFPA 30B as listed in rule
1301:7-7-80
of the Administrative
Code.
(4)
5104.4 Storage in
aerosol warehouses. The total quantity of Level 2 and 3 aerosol products in a
warehouse utilized for the storage, shipping and receiving of aerosol products
shall not be restricted in structures complying with paragraphs
(D)(4)(a)(5104.4.1) to (D)(4)(d)(5104.4.4) of this rule.
(a)
5104.4.1
Automatic sprinkler system. Aerosol warehouses shall be protected by an
approved wet-pipe automatic sprinkler system in accordance with NFPA 30B as
listed in rule
1301:7-7-80
of the Administrative Code. Sprinkler protection shall be designed based on the
highest classification level of aerosol product present.
(b)
5104.4.2 Pile and
palletized storage aisles. Solid pile and palletized storage shall be arranged
so the maximum travel distance to an aisle is 25 feet (7620 mm). Aisles shall
have a minimum width of 4 feet (1219 mm).
(c)
5104.4.3 Rack
storage aisles. Rack storage shall be arranged with a minimum aisle width of 8
feet (2438 mm) between rows of racks and 8 feet (2438 mm) between racks and
adjacent solid pile or palletized storage. Where early suppression
fast-response (ESFR) sprinklers provide automatic sprinkler protection, the
minimum aisle width shall be 4 feet (1219 mm).
(d)
5104.4.4
Combustible commodities. Combustible commodities other than flammable and
combustible liquids shall be permitted to be stored in an aerosol
warehouse.
Exception: Flammable and combustible
liquids in 1-quart (946 mL) metal containers and smaller shall be permitted to
be stored in an aerosol warehouse.
(5)
5104.5 Storage in
inside flammable liquid storage rooms. Inside flammable liquid storage rooms
shall comply with paragraph (D)(3)(g)(5704.3.7) of rule
1301:7-7-57
of the Administrative Code. The maximum quantities of aerosol products shall
comply with paragraph (D)(5)(a)(5104.5.1) or (D)(5)(b)(5104.5.2) of this
rule.
(a)
5104.5.1 Storage rooms of 500 square feet or less. The
storage of aerosol products in flammable liquid storage rooms less than or
equal to 500 square feet (46 m2) in area shall not
exceed the following quantities:
(i)
A net weight of 1,000 pounds (454 kg) of Level 2
aerosol products.
(ii)
A net weight of 500 pounds (227 kg) of Level 3 aerosol
products.
(iii)
A combined net weight of 1,000 pounds (454 kg) of Level
2 and 3 aerosol products.
(b)
5104.5.2 Storage
rooms greater than 500 square feet. The storage of aerosol products in
flammable liquid storage rooms greater than 500 square feet (46 m2) in area shall not exceed
the following quantities:
(i)
A net weight of 2,500 pounds (1135 kg) of Level 2
aerosol products.
(ii)
A net weight of 1,000 pounds (454 kg) of Level 3
aerosol products.
(iii)
A combined net weight of 2,500 pounds (1135 kg) of
Level 2 and 3 aerosol products.
The maximum aggregate storage quantity
of Level 2 and 3 aerosol products permitted in separate inside storage rooms
protected by an approved automatic sprinkler system in accordance with NFPA 30B
as listed in rule
1301:7-7-80
of the Administrative Code shall be 5,000 pounds (2270
kg).
(6)
5104.6 Storage in
liquid warehouses. The storage of Level 2 and 3 aerosol products in liquid
warehouses shall comply with NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code. The storage shall be located within segregated
storage areas in accordance with paragraph (D)(3)(b)(5104.3.2) of this rule and
paragraphs (D)(6)(a)(5104.6.1) to (D)(6)(c)(5104.6.3) of this rule.
(a)
5104.6.1
Containment. Spill control or drainage shall be provided to prevent the flow of
liquid to within 8 feet (2438 mm) of the segregated storage
area.
(b)
5104.6.2 Sprinkler design. Sprinkler protection shall
be designed based on the highest level of aerosol product
present.
(c)
5104.6.3 Opening protection into segregated storage
areas. Fire doors or gates opening into the segregated storage area shall
either be self-closing or provided with automatic-closing devices activated by
sprinkler water flow or an approved fire detection system.
(7)
5104.7
Storage in Group M occupancies. Storage of Level 2 and 3 aerosol products in
occupancies in Group M shall comply with Table 5104.7 of this rule. Retail
display shall comply with paragraph (F)(5106) of this rule.
Table 5104.7 Maximum quantities of
Level 2 and 3 aerosol products in retail storage areas
|
Maximum net weight per floor
(pounds)
|
|
|
Segregated
storage
|
|
Floor
|
Nonsegregated
storagea,b
|
Storage
cabinetsb
|
Separated from retail
areac
|
|
Basement
|
Not permitted
|
Not permitted
|
Not permitted
|
|
Ground floor
|
2,500
|
5,000
|
Note d
|
|
Upper floors
|
500
|
1,000
|
Note d
|
For SI: 1 pound = 0.454 kg, 1 square
foot = 0.0929 m2.
a.
The total
aggregate quantity on display and in storage shall not exceed the maximum
retail display quantity indicated in paragraph (F)(3)( 5106.3) of this
rule.
b.
Storage quantities indicated are the maximum permitted
in any 50,000-square-foot area.
c.
The storage area
shall be separated from the retail area with a 1-hour fire-resistance-rated
assembly.
d.
See Table 5104.3.2 of this rule.
(E)
Section 5105 Outside storage
(1)
5105.1 General.
The outside storage of Level 2 and 3 aerosol products, including storage in
temporary storage trailers, shall be separated from exposures in accordance
with Table 5105.1 of this rule.
Table 5105.1 Distance to exposures for
outside storage of Level 2 and 3 aerosol products
|
Exposure
|
Minimum distance from aerosol
storage (feet)a
|
|
Public alleys, public ways,
public streets
|
20
|
|
Buildings
|
50
|
|
Exit discharge to a public
way
|
50
|
|
Lot lines
|
20
|
|
Other outside
storage
|
50
|
For SI: 1 inch = 25.4 mm, 1 foot =
304.8 mm.
a.
The minimum separation distance indicated is not
required where exterior walls having a 2-hour fire-resistance rating without
penetrations separate the storage from the exposure. The walls shall extend not
less than 30 inches above and to the sides of Level 2 and 3 aerosol
products.
(F)
Section 5106
Retail display
(1)
5106.1 General. This paragraph shall apply to the
retail display of 500 pounds (227 kg) or more of Level 2 or 3 aerosol
products.
(2)
5106.2 Aerosol display and normal merchandising not
exceeding 8 feet (2438 mm) high. Aerosol display and normal merchandising not
exceeding 8 feet (2438 mm) in height shall be in accordance with paragraphs
(F)(2)(a)(5106.2.1) to (F)(2)(d)(5106.2.4) of this rule.
(a)
5106.2.1 Maximum
quantities in retail display areas. Aerosol products in retail display areas
shall not exceed quantities needed for display and normal merchandising and
shall not exceed the quantities in Table 5106.2.1 of this rule.
Table 5106.2.1 Maximum quantities of
Level 2 and 3 aerosol products in retail display areas
|
Maximum net weight per floor
(pounds)b
|
|
Floor
|
Unprotecteda
|
Protected in accordance with
paragraph (F)(2)(5106.2)a,c of this
rule
|
Protected in accordance with
paragraph (F)(3)( 5106.3)c of this
rule
|
|
Basement
|
Not allowed
|
500
|
500
|
|
Ground
|
2,500
|
10,000
|
10,000
|
|
Upper
|
500
|
2,000
|
Not allowed
|
For SI: 1 pound = 0.454 kg, 1 square
foot = 0.0929 m2.
a.
The total quantity
shall not exceed 1,000 pounds net weight in any one 100-square-foot retail
display area.
b.
Per 25,000-square-foot retail display
area.
c.
Minimum Ordinary Hazard Group 2 wet-pipe automatic
sprinkler system throughout the retail sales occupancy.
Table 5106.4 Maximum storage quantities
for storage areas adjacent to retail display of Level 2 and Level 3
aerosols
|
Maximum net weight per floor
(pounds)
|
|
Floor
|
Unseparateda,b
|
Separated
|
|
Storage
cabinetsb
|
1-hour occupancy
separation
|
|
Basement
|
Not allowed
|
Not allowed
|
Not allowed
|
|
Ground
|
2,500
|
5,000
|
In accordance with Sections
6.3.4.3 and 6.3.4.4 of NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code
|
|
Upper
|
500
|
1,000
|
In accordance with Sections
6.3.4.3 and 6.3.4.4 of NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code
|
For SI: 1 pound = 0.454 kg, 1 square
foot = 0.0929 m2.
a.
The aggregate
quantity in storage and retail display shall not exceed the quantity limits for
retail display.
b.
In any 50,000-square-foot area.
(b)
5106.2.2 Display of containers. Level 2 and 3 aerosol
containers shall not be stacked more than 6 feet (1829 mm) high from the base
of the aerosol array to the top of the aerosol array unless the containers are
placed on fixed shelving or otherwise secured in an approved manner. Where
storage or retail display is on shelves, the height of such storage or retail
display to the top of aerosol containers shall not exceed 8 feet (2438
mm).
(c)
5106.2.3 Combustible cartons. Aerosol products located
in retail display areas shall be removed from combustible cartons.
Exceptions:
1.
Display areas that
use a portion of combustible cartons that consist of only the bottom panel and
not more than 2 inches (51 mm) of the side panel are allowed.
2.
Where the display
area is protected in accordance with Tables 6.3.2.7 (a) to 6.3.2.7 (l) of NFPA
30B as listed in rule
1301:7-7-80
of the Administrative Code, storage of aerosol products in combustible cartons
is allowed.
(d)
5106.2.4 Retail display automatic sprinkler system.
When an automatic sprinkler system is required for the protected retail display
of aerosol products, the wet-pipe automatic sprinkler system shall be in
accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule
1301:7-7-09
of the Administrative Code. The minimum system design shall be for an Ordinary
Hazard Group 2 occupancy. The system shall be provided throughout the retail
display area.
(3)
5106.3 Aerosol display and normal merchandising
exceeding 8 feet (2438 mm) high. Aerosol display and merchandising exceeding 8
feet in height shall be in accordance with paragraphs (F)(3)(a)(5106.3.1) to
(F)(3)(c)(5106.3.3) of this rule.
(a)
5106.3.1 Maximum quantities in retail display areas.
Aerosol products in retail display areas shall not exceed quantities needed for
display and normal merchandising and shall not exceed the quantities in Table
5106.2.1 of this rule, with fire protection in accordance with paragraph
(F)(3)(b)(5106.3.2) of this rule.
(b)
5106.3.2
Automatic sprinkler protection. Aerosol display and merchandising areas shall
be protected by an automatic sprinkler system based on the requirements set
forth in Tables 6.3.2.7 (a) to 6.3.2.7 (l) of NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code and the following:
(i)
Protection shall
be based on the highest level of aerosol product in the array and the packaging
method of the storage located more than 6 feet (1829 mm) above the finished
floor.
(ii)
When using the cartoned aerosol table's of NFPA 30B as
listed in rule
1301:7-7-80
of the Administrative Code, uncartoned or display-cut Level 2 and 3 aerosols
shall be permitted not more than 6 feet (1829 mm) above the finished
floor.
(iii)
The design area for Level 2 and 3 aerosols shall extend
not less than 20 feet (6096 mm) beyond the Level 2 and 3 aerosol display and
merchandising areas.
(iv)
Where ordinary and high-temperature ceiling sprinkler
systems are adjacent to each other, noncombustible draft curtains shall be
installed at the interface.
(c)
5106.3.3
Separation of Level 2 and 3 aerosol areas. Separation of Level 2 and 3 aerosol
areas shall comply with the following:
(i)
Level 2 and 3
aerosol display and merchandising areas shall be separated from each other by
not less than 25 feet (7620 mm). See Table 5106.2.1 of this
rule.
(ii)
Level 2 and 3 aerosol display and merchandising areas
shall be separated from flammable and combustible liquids storage and display
areas by one or a combination of the following:
(a)
Segregating areas
from each other by horizontal distance of not less than 25 feet (7620
mm).
(b)
Isolating areas from each other by a noncombustible
partition extending not less than 18 inches (457 mm) above the
merchandise.
(c)
In accordance with paragraph (F)(5)( 5106.5) of this
rule.
(iii)
Where paragraph (b) above is used to separate Level 2
or 3 aerosols from flammable or combustible liquids, and the aerosol products
are located within 25 feet (7620 mm) of flammable or combustible liquids, the
area below the noncombustible partition shall be liquid tight at the floor to
prevent spilled liquids from flowing beneath the aerosol
products.
(4)
5106.4 Maximum
quantities in storage areas. Aerosol products in storage areas adjacent to
retail display areas shall not exceed the quantities in Table 5106.4 of this
rule.
(5)
5106.5 Special protection design for Level 2 and 3
aerosols adjacent to flammable and combustible liquids in double-row racks. The
display and merchandising of Level 2 and 3 aerosols adjacent to flammable and
combustible liquids in double-row racks shall be in accordance with paragraphs
(F)(5)(a)(5106.5.1) to (F)(5)(h)(5106.5.8) of this rule or paragraph
(F)(3)(c)(510633) of this rule.
(a)
5106.5.1 Fire protection. Fire protection for the
display and merchandising of Level 2 and 3 aerosols in double-row racks shall
be in accordance with Table 7.4.1 and Figure 7.4.1 of NFPA 30B as listed in
rule
1301:7-7-80
of the Administrative Code.
(b)
5106.5.2 Cartoned
products. Level 2 and 3 aerosols displayed or merchandised more than 8 feet
(2438 mm) above the finished floor shall be in cartons.
(c)
5106.5.3
Shelving. Shelving in racks shall be limited to wire mesh shelving having
uniform openings not more than 6 inches (152 mm) apart, with the openings
comprising not less than 50 per cent of the overall shelf area.
(d)
5106.5.4 Aisles.
Racks shall be arranged so that aisles not less than 71/2 feet (2286 mm) wide are
maintained between rows of racks and adjacent solid-piled or palletized
merchandise.
(e)
5106.5.5 Flue spaces. Flue spaces in racks shall comply
with the following:
(i)
Transverse flue spaces-Nominal 3-inch (76 mm)
transverse flue spaces shall be maintained between merchandise and rack
uprights.
(ii)
Longitudinal flue spaces-Nominal 6-inch (152 mm)
longitudinal flue spaces shall be maintained.
(f)
5106.5.6
Horizontal barriers. Horizontal barriers constructed of minimum 3/8-inch-thick
(10 mm) plywood or minimum 0.034 -inch ( 0.086 mm) (No. 22 gage) sheet metal
shall be provided and located in accordance with Table 7.4.1 and Figure 7.4.1
of NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code where in-rack sprinklers are
installed.
(g)
5106.5.7 Class I, II, III, IV and plastic commodities.
Class I, II, III, IV and plastic commodities located adjacent to Level 2 and 3
aerosols shall be protected in accordance with NFPA 13 as listed in rule
1301:7-7-80
of the Administrative Code.
(h)
5106.5.8
Flammable and combustible liquids. Class I, II, IIIA and IIIB liquids shall be
allowed to be located adjacent to Level 2 and 3 aerosol products where both of
the following conditions are met:
(i)
Class I, II, IIIA and IIIB liquid containers:
Containers for Class I, II, IIIA and IIIB liquids shall be limited to
1.06 -gallon (4 L)
metal-relieving and nonrelieving style containers and 5.3 -gallon (20 L)
metal-relieving style containers.
(ii)
Fire protection
for Class I, II, IIIA and IIIB liquids: Automatic sprinkler protection for
Class I, II, IIIA and IIIB liquids shall be in accordance with rule
1301:7-7-57
of the Administrative Code.
(G)
Section 5107
Manufacturing facilities
(1)
5107.1 General. Manufacturing facilities shall be in
accordance with NFPA 30B as listed in rule
1301:7-7-80
of the Administrative Code.
Replaces: 1301:7-7-28.
Notes
Ohio Admin. Code 1301:7-7-51
Effective:
12/15/2017
Five Year Review (FYR) Dates:
12/15/2022
Promulgated
Under: 119.03
Statutory
Authority: 3737.22,
3737.82,
3737.83
Rule
Amplifies: 3737.22,
3737.82,
3737.83
Prior
Effective Dates: 07/01/1979, 06/01/1985, 06/15/1992, 07/01/1993, 09/01/1995,
03/30/1998, 09/01/2005, 07/01/2007,
11/01/2011