(A) Except as otherwise noted, the
definitions in rule
3745-81-01 of the Administrative
Code shall apply to this chapter.
For the purposes of
this rule, "week" means a seven day period beginning on Sunday and ending on
the following Saturday.
(B)
Except as otherwise noted, analyses required by this rule shall be conducted in
accordance with methods as specified in rule
3745-81-27 of the Administrative
Code. In addition, analysis for parameters listed in the table in this
paragraph shall be conducted in a laboratory certified in accordance with
Chapter 3745-89 of the Administrative Code:
|
Parameter
|
Application
|
|
Total alkalinity
|
Precipitative softening or membrane technology; daily
monitoring.
|
|
Phenol alkalinity
|
Precipitative softening; daily monitoring.
|
|
Stability
|
Precipitative softening or membrane technology; weekly
monitoring.
|
|
Copper
|
All.
|
|
Fluoride
|
All.
|
|
Iron
|
For split sample or weekly analysis.
|
|
Manganese
|
For split sample or weekly analysis.
|
|
pH
|
Precipitative softening or membrane technology; daily
monitoring. Surface water treatment plant; daily monitoring.
|
|
Total hardness
|
Precipitative softening or membrane technology; daily
monitoring.
|
|
Total phosphorus
|
All.
|
(C)
Disinfection.
(1) Except as prescribed in rule
3745-81-72 of the Administrative
Code, noncommunity public water systems serving a population of at least one
thousand people and all community public water systems shall maintain a minimum
chlorine residual of at least two-tenths milligram per liter
(0.2 mg/L) free chlorine, or one milligram per
liter combined chlorine measured at representative points throughout the
distribution system. All other noncommunity public water systems that provide
water treated with chlorine for disinfection purposes shall maintain the
chlorine residual levels as described in this rule. The director may require
higher residuals as necessary to compensate for pH, temperature, or other
characteristics of the delivered water.
[Comment: Rule
3745-81-72 of the Administrative
Code establishes similar but separate requirements for disinfection of systems
using a surface water source. These two requirements are not inconsistent and
failure to comply with either is considered a separate violation with different
consequences. Contact your district office representative if you have questions
or require clarification.]
(2) Noncommunity public water systems serving
a population of at least one thousand people and all community public water
systems shall install and place in operation equipment capable of meeting
disinfection requirements of this rule.
(3) A system is exempt from maintaining a
chlorine residual as required in paragraph (C)(1) of this rule if, with written
approval of the director, it uses chlorine dioxide as a primary disinfectant in
accordance with the terms of the approval.
[Comment: Plan approval requirements
for a system treating with chlorine dioxide will include minimum chlorine
dioxide residual requirements for the system and any consecutive
systems.]
(4) At
times of actual or threatened outbreak of waterborne disease as defined in rule
3745-81-01 of the Administrative
Code, or water supply emergency as determined by the director in accordance
with section
6109.05 of the Revised Code, the
director may require a public water system subject to paragraph (C) (1) of this
rule to maintain a minimum chlorine residual of at least one milligram per
liter free chlorine, or six milligrams per liter combined chlorine measured at
representative points throughout the distribution system, despite possible
resulting tastes or odors in the delivered water.
(5)
"Finished
water storage facilities," means a tank, reservoir, or other facility used to
store water that will undergo no further treatment except residual
disinfection, aeration or recirculation. Finished water storage
facilities serving noncommunity water systems serving a population of at least
one thousand people and all community water systems, prior to being placed into
service or being returned to service after repairs, inspections, painting,
cleaning, or other activities that might lead to contamination, shall complete
the following:
(a) Meet the requirements of
"American Water Works Association Standard C652-02 Disinfection of
Water-Storage Facilities" (2002)
(2019).
(b) Be monitored for chlorine residual and
comply with the minimum chlorine residual established in paragraph (C)(1) of
this rule and the MRDL established in paragraph (C) of rule
3745-81-10 of the Administrative
Code.
(6) Water mains
serving noncommunity water systems serving a population of at least one
thousand people and all community water systems, prior to being placed into
service or being returned to service after repairs, inspections, or other
activities that might lead to contamination, unless a minimum pressure of
twenty pounds per square inch gauge at ground level is maintained at all points
in the distribution system, shall complete the following:
(a) Meet the requirements of "American Water
Works Association Standard C651-14 Disinfecting Water Mains" (2014).
(b) Be monitored for chlorine residual and
comply with the minimum chlorine residual established in paragraph (C)(1) of
this rule and the MRDL established in paragraph (C) of rule
3745-81-10 of the Administrative
Code.
(D)
Approval of chemicals and components. All chemicals, substances, and materials
added to or brought in contact with water in or intended to be used in a public
water system or used for the purpose of treating, conditioning, altering, or
modifying the characteristics of such water shall be shown by either the
manufacturer, distributor, or purveyor to be non-toxic and harmless to humans
when used in accordance with the formulation and concentration as specified by
the manufacturer, and shall be certified as meeting the "American National
Standards Institute/National Sanitation Foundation
/Standards
Council of Canada (ANSI/NSF
/CAN)" standards
in paragraphs (D)(1) to (D)(3) of this rule. Certification shall be from an
"ANSI" accredited product certification organization.
(1) All chemicals shall be certified as
meeting the specification of "ANSI/NSF/ CAN
Standard 60 Drinking Water Treatment Chemicals - Health Effects
(2009)
(2020)."
(2) All components installed by a public
water system shall be certified as meeting the specifications of "ANSI/NSF/CAN Standard 61 Drinking Water System Components -
Health Effects (2010)
(2020)."
If certification to "ANSI/NSF/ CAN Standard 61"
is not available for a component, an alternate component with "ANSI/NSF/CAN Standard 61" certification must be used. In cases
where no alternate "ANSI/NSF/CAN Standard 61"
component exists, the director may accept another component on a case by case
basis until the "ANSI/NSF/CAN Standard 61"
certified component is available.
(3) Replacement of an existing component that
is not certified to "ANSI/NSF/ CAN Standard 61
Drinking Water System Components - Health Effects (2010)
(2020)" may be
required if the director determines the component may pose a risk to human
health, safety or the environment.
(E) Minimum pressure.
Community
All
water systems shall maintain a minimum pressure of twenty pounds per square
inch gauge at ground level at all points in the distribution system under all
conditions of flow other than conditions caused by line breaks, extreme fire
flows, or other extraordinary circumstances.
[Comment: Required responses to
conditions caused by line breaks, extreme fire flows, or other extraordinary
circumstances are found in rule
3745-83-02 of the Administrative
Code.]
(F) Operational
analyses.
(1) Alkalinity.
(a) Total alkalinity.
(i) A public water system that provides
precipitative softening as defined in rule
3745-7-01 of the Administrative
Code or membrane technology to reduce hardness shall monitor for total
alkalinity daily at each entry point to the distribution system.
(ii) A public water system that adjusts the
alkalinity of the water for optimization of corrosion control pursuant to the
lead and copper requirements in rules
3745-81-82 and
3745-81-87 of the Administrative
Code shall monitor for total alkalinity at least once every two weeks at
regular intervals at each entry point to the distribution system.
[Comment: In addition to the monitoring requirements above,
public water systems exceeding the lead and copper action level that adjust the
alkalinity of the water for the purpose of providing optimal corrosion control
treatment pursuant to rules
3745-81-82 and
3745-81-87 of the Administrative
Code shall also monitor in accordance with the requirements of those
rules.]
(b)
Phenolphthalein (or phenol) alkalinity. A public water system that provides
precipitative softening as defined in rule
3745-7-01 of the Administrative
Code shall monitor for phenolphthalein alkalinity daily at each entry point to
the distribution system.
(c)
Stability. A public water system that provides precipitative softening as
defined in rule
3745-7-01 of the Administrative
Code or membrane technology to reduce hardness shall monitor for stability at
least weekly at each entry point to the distribution system.
(2) Chlorine residual.
(a) A public water system that provides water
treated with chlorine shall monitor for free or combined chlorine at least once
every day that water is available to the public at each entry point to the
distribution system and a representative point or points in the distribution
system
unless otherwise specified by the
director.
A noncommunity ground water system
whose distribution system is solely interior plumbing in a single building only
needs to collect one representative sample daily.
(i)
A daily entry
point sample is not required for a noncommunity ground water system that
consists of a single building or any consecutive system receiving finished
water that is not treated further by the consecutive water system unless
otherwise specified by the director.
(ii)
If the director
determines a water system's distribution sampling location or locations do not
result in representative distribution samples, the water system shall select
additional or different locations that result in representative distribution
samples.
(b) A
public water system that uses chlorine solely for the oxidation of iron,
manganese or hydrogen sulfide and is not required to maintain a residual in the
distribution system does not have to perform the monitoring in paragraph
(F)(2)(a) of this rule.
[Comment: In addition to the requirements in this paragraph, a
public water system that uses a surface source, in whole or in part, shall also
conduct disinfection monitoring in accordance with rule
3745-81-74 of the Administrative
Code. A public water system that uses a ground water source and provides 4-log
inactivation of viruses shall also conduct disinfection monitoring in
accordance with rule
3745-81-43 of the Administrative
Code.]
(3)
Copper. A public water system that intends to apply a copper compound to the
water supply source shall notify the director of their intent to apply the
compound, and monitor for copper at least weekly, at each entry point to the
distribution system for at least one month after the compound has been
applied.
(4) Fluoride.
(a) A public water system that adds fluoride
to the water supply shall monitor for fluoride in accordance with the
following:
(i) At least once every day that
water is available to the public at each entry point to the distribution
system.
(ii) Prior to fluoridation
at least once per month.
(b) Samples shall be analyzed as soon as
possible, but in no case later than forty-eight hours after the time of
collection.
(5) Iron.
A community public water system that provides treatment to
reduce iron shall monitor for iron at least at each entry point to the
distribution system.
(a) Community
systems serving up to and including two hundred fifty persons shall monitor
either of the following:
(i) Weekly with an
in-house test kit in accordance with paragraph (F)(5) (c) of this rule and one
split sample monthly by a state certified laboratory.
(ii) Weekly by a state certified
laboratory.
(b)
Community systems serving greater than two hundred fifty persons shall monitor
either of the following:
(i) A minimum of five
days per week with an in-house test kit in accordance with paragraph (F)(5)(c)
of this rule and one split sample monthly by a state certified
laboratory.
(ii) Weekly by a state
certified laboratory.
(c) An iron test kit shall have a minimum
detection level of 0.2 milligrams per liter. Furthermore, the deviation of the
split sample shall not be greater than 0.2 milligrams per liter. If the
deviation is greater, then the public water system shall cease monitoring with
the test kit and substitute with weekly monitoring at a state certified
laboratory. A public water system may resume monitoring with their test kit
once the deviation of a split sample is no greater than 0.2 milligrams per
liter. The director may accept an alternate collection frequency and deviation
from in-house test kits for split sampling requirements.
(6) Manganese.
A
All community and nontransient
noncommunity public water systems
system that add
manganese as part of the treatment process or
provides
provide
treatment to reduce
for manganese, shall
monitor for manganese at least at each entry point to the distribution system
at the frequency in paragraphs (F)(6)(a) and (F)(6)(b)
of this rule. Public water systems that add manganese as part of the treatment
process but do not provide treatment for manganese are only required to comply
with this paragraph when manganese is added..
(a)
Community systems serving up to and including two hundred and fifty persons
and all nontransient noncommunity systems shall
monitor either of the following:
(i) Weekly
with an in-house test kit in accordance with paragraph (F) (6)(c) of this rule
and one split sample monthly by a certified laboratory.
(ii) Weekly by a state certified
laboratory.
(b)
Community systems serving greater than two hundred fifty persons shall monitor
either of the following:
(i) A minimum of five
days per week with an in-house test kit in accordance with paragraph (F)(6)(c)
of this rule and one split sample monthly by a certified laboratory.
(ii) Weekly by a state certified
laboratory.
(c) A
manganese test kit shall have a minimum detection level of 0.02 milligrams per
liter. Furthermore, the deviation of the split sample shall be no greater than
0.04 milligrams per liter. If it is greater, then the public water system shall
cease monitoring with the test kit and substitute with weekly monitoring at a
state certified laboratory. A public water system may resume monitoring with
their test kit once a deviation of the split sample is no greater than 0.04
milligrams per liter. The director may accept an alternate collection frequency
and deviation from in-house test kits for split sampling
requirements.
(7)
Orthophosphate.
A public water system that adds
orthophosphate to the water for the purpose of providing corrosion control
treatment for purposes other than compliance with the lead and copper rules
shall monitor for orthophosphate at least monthly at each entry point to the
distribution system.
[Comment: Additional monitoring
requirements for public water systems that add orthophosphate to the water for
the purpose of providing optimal corrosion control treatment can be found in
rules 3745-81-82 and
3745-81-87 of the Administrative
Code.]
(a) A public water system that adds
orthophosphate to the water for the purpose of providing corrosion control
treatment for purposes other than compliance with the lead and copper rules
shall monitor at least monthly at each entry point to the distribution
system.
(b) A public water system that adds
orthophosphate to the water supply for optimization of corrosion control
pursuant to the lead and copper requirements of rules 3745-81-82 and 3745-81-87
of the Administrative Code shall monitor for orthophosphate at least once every
two weeks at regular intervals at each entry point to the distribution
system.
[Comment: In addition to the
monitoring requirements above, public water systems exceeding the lead and
copper action level that add orthophosphate to the water for the purpose of
providing optimal corrosion control treatment pursuant to rules 3745-81-82 and
3745-81-87 of the Administrative Code shall also monitor in accordance with the
requirements of those rules.]
(8) pH.
A public water system that adjusts the
pH of the water supply for stabilization or that employs precipitative
softening as defined in rule
3745-7-01 of the Administrative
Code or membrane technology to reduce hardness shall monitor for pH at least
once every day that water is available to the public at each entry point to the
distribution system.
(a) A public water system that
adjusts the pH of the water supply for stabilization shall monitor for pH at
least once every day that water is available to the public at each entry point
to the distribution system.
(b) A public water system that
employs precipitative softening as defined in rule 3745-7-01 of the
Administrative Code or membrane technology to reduce hardness shall monitor for
pH at least once every day that water is available to the public at each entry
point to the distribution system.
(c) A public water system that uses
a surface water source, in whole or in part, shall also conduct pH monitoring
in accordance with rule 3745-81-74 of the Administrative Code.
(d) A public water system that
adjusts the pH of the water for optimization of corrosion control pursuant to
the lead and copper requirements of rules 3745-81-82 and 3745-81-87 of the
Administrative Code shall monitor for pH at least once every two weeks at
regular intervals at each entry point to the distribution
system.
[Comment: In addition to
the
Additional monitoring requirements
for water systems that adjust the pH of water can be
found in rules 3745-81-43, 3745-81-74, 3745- 81-82 and
3745-81-87 of the Administrative
Code.
above, public water systems exceeding
the lead and copper action level that adjust the pH of the water for the
purposes of providing optimal corrosion control treatment pursuant to rules
3745-81-82 and 3745-81-87 of the Administrative Code shall also monitor in
accordance with the requirements of those rules. A public water system that
uses a ground water source and provides 4-log inactivation of viruses shall
also conduct disinfection monitoring in accordance with rule 3745-81-43 of the
Administrative Code.
(9) Total hardness.
(a) A community public water system serving
up to and including two hundred fifty persons that provides
ion
cation
exchange treatment to reduce hardness shall monitor for total hardness at least
monthly at each entry point to the distribution system.
(b) A community public water system serving
greater than two hundred fifty persons that provide ion exchange treatment to
reduce hardness shall monitor for total hardness at least weekly at each entry
point to the distribution system.
(c) A public water system that provides
precipitative softening treatment as defined in rule
3745-7-01 of the Administrative
Code or that provides membrane technology to reduce hardness shall monitor for
total hardness at least daily at each entry point to the distribution
system.
(10) Total
phosphorus. A public water system that adds phosphate to the water supply
for purposes other than corrosion control,
shall monitor for total phosphorus at least monthly at each entry point to the
distribution system.
(G)
The director may require additional monitoring as needed to assess operational
performance than is otherwise specified in this rule, including but not limited
to operational monitoring required to assess the effectiveness of treatment for
contaminants regulated in Chapter 3745-81 of the Administrative Code. The
director shall notify the public water system of additional monitoring required
under this paragraph in writing or via plan approval issued in accordance with
Chapter 3745-91 of the Administrative Code.
(H) Maintenance of facilities and equipment.
(1) The owner and operator shall ensure that
all facilities and equipment necessary for the treatment and distribution of
water shall be maintained, at a minimum so as to function as
intended.
(2) In the event that the
treatment facilities or equipment no longer function as intended, corrective
action (which may include additional maintenance or modifications of the public
water system) shall be taken by the owner.
(3) The owner and operator shall document the
completion of the above referenced maintenance in accordance with Chapter
3745-7 of the Administrative Code.
(I) Reports.
(1) In addition to any other reporting
requirement of Chapter 3745-81 of the Administrative Code, the owner or
operator of a public water system required to monitor under paragraphs (F) and
(G) of this rule shall prepare and submit an operation report for each month of
operation on forms acceptable to the director and in accordance with
instructions provided by the director. The director may require that the report
include the following:
(a) General operation
data, including but not limited to, identification of the operating source at a
given time, number of hours of operation, filter run times, backwash duration,
filter backwash recycle percentages, head loss, membrane pressure drop, cartridge filter pressure drop,
permeate and concentrate flow, interruptions in treatment, equipment
inspection/ maintenance dates, minimum system pressure, pre and intermediate
tap sampling results, and deviations from normal day-to-day
operations.
(b) A summary of
samples analyzed, including distribution system sampling and chlorine residual
sampling.
(c) Information on daily
water treatment and system pumpage.
(d) Information on chemical application,
including but not limited to, chemical feed pump ranges, chemical dosages,
chemical feed rates, pre, intermediate or post treatment application changes in
chemical type, location, and dosage due to emergencies, and seasonal
variations.
(e) Analysis of general
parameters relating to the quality of the treated drinking water.
(f) Source water levels, including but not
limited to, low and high levels in flowing in streams, lakes and reservoirs,
static and drawdown levels in production and monitoring wells under any
conditions including flooding and drought periods.
(g) Such other information as may be
necessary or desirable for the director to carry out the director's duties
under Chapter 6109. of the Revised Code.
(2) The operation report shall be signed by
the operator of record designated in accordance with rule
3745-7-02 of the Administrative
Code. If an operator of record is not required by rule
3745-7-02 of the Administrative
Code, the operation report shall be signed by an individual designated by the
public water system owner.
(3) The
operation report shall be submitted electronically via a method acceptable to
the director no later than the tenth of the month following the month for which
the report was prepared.
(4) The
owner or operator shall report to the appropriate Ohio environmental protection
agency district office as soon as possible, but within twenty-four hours, the
discovery of any serious plant or distribution system breakdown or condition
causing or likely to cause any of the following:
(a) Any discharge of water not in accordance
with Chapter 6109. of the Revised Code or the rules adopted
thereunder.
(b) Any major
interruption in service or disinfection.
(c) Any hazard for employees, consumers, the
public or the environment.
(5) Records of operation reports for each
month of operation shall be kept for not less than ten years, except for lead
and copper data which shall be kept for not less than twelve years.
[Comment: This rule incorporates the "American Water Works"
standards C651-14 and C652-02
C652-19 by reference. Copies may be obtained from the
"AWWA Bookstore, 6666 West Quincy Avenue, Denver, Co, 80235, 1-800-926-7337,
www.awwa.org." These standards are
available for review at "Ohio EPA, Lazarus Government Center, 50 W. Town
Street, Suite 700, Columbus, OH, 43215."]
[Comment: This rule incorporates the ANSI/NSF/CAN standards 60 and 61 by reference. Copies may be
obtained from "NSF International, 789 Dixboro Road, P.O. Box 130140, Ann Arbor,
MI, 48113-0140, (734) 769-8010, www.nsf.org." These standards are available
for review at "Ohio EPA, Lazarus Government Center, 50 W. Town Street, Suite
700, Columbus, OH, 43215."]
Notes
Ohio Admin. Code
3745-83-01
Effective:
8/29/2022
Five Year Review (FYR) Dates:
4/8/2022 and
08/29/2027
Promulgated
Under: 119.03
Statutory
Authority: 6109.04
Rule
Amplifies: 6109.04,
6109.13
Prior
Effective Dates: 11/26/1980, 09/13/1993, 01/01/1999, 04/21/2001, 08/03/2004,
10/01/2006, 04/19/2012, 03/04/2016