Chapter 10 of the International
Building Code, 2021 edition, as incorporated by reference and modified in
Section 101.1.1 of this code, is further modified as follows:
(A)
Modify
Section 1001.1 to add the following
sentence at the end of the paragraph:
Where Chapter 11 and this chapter have
provisions relating to the same content, both chapters apply.
(B)
Modify Table 1006.3.4(1), footnote 'a' to add the following
before the first sentence:
a.
Except as otherwise provided in Section
903.2.8,
(C)
Modify Table 1006.3.4(2), footnote 'a' to add the
following before the first sentence:
a.
Except as
otherwise provided in Section 903.2.8,
(D)
Modify
Section 1010.2.1 to add a new exception as follows:
5.
Temporary
door locking devices
used in accordance
with section 1010.2.16.
(E)
Modify
Section 1010.2.2 to add an exception that reads:
Exception:
Non-fixed portions of door or gate
hardware
, including
keys, access cards and
temporary door
locking devices.
(F)
Modify
Section 1010.2.4 to add a new item that reads:
11.
Temporary
door locking devices
used in accordance
with section 1010.2.16.
(G)
Modify
Section 1010.2.13.1 to add items 9 and 10 and an exception that applies to the
section to read as follows:
9.
The procedures for the operation(s) of the unlocking
system is to be described and
approved
as part of
the emergency planning and preparedness required by Chapter 4 of the
International Fire Code
.
10.
All clinical staff are to have the keys, codes or other
means necessary to operate the locking devices.
Exception:
In Group I-2 occupancies, items 1 through 3 do not
apply to doors to areas where persons, because of clinical needs, require
restraint or containment as part of the function of a mental
hospital.
(H)
Add Section
1010.2.16 to read as follows:
1010.2.16
Temporary door locking devices
.
A
temporary door locking
device
, designed and used to keep
intruders from entering the room, is to be permitted when
approved
by the
building official
and noted on the certificate of
occupancy
in Groups
A, B, E, F, H, I-4, M, S, and U occupancies where the requirements of sections
1010.2.16.1 and 1010.2.16.2 are met.
1010.2.16.1
Conditions of use.
A
temporary door
locking device
is to only be used on
doors under the conditions in either 1010.2.16.1.1 or 1010.2.16.1.2, based
upon
occupancy
:
1010.2.16.1.1
Conditions of use in
school
buildings
.
1.
Proof is provided
by the
administrative authority of a
school building
that a school safety
plan has been adopted and filed pursuant to section
3313.536 of the Revised Code;
and
2.
The
temporary door
locking device
is to only be used in an
Emergency situation and during active shooter drills; and
3.
The
temporary door locking device
is engaged only by a staff member of the
school building
; and
4.
The
temporary
door locking device
is to only be
engaged for a finite period of time as determined by the
administrative authority of a school building
in accordance with the school safety plan adopted
pursuant to section 3313.536 of the Revised Code;
and
5.
Proof is provided by the
administrative authority of a school building
that police and fire officials having jurisdiction for
the
school building
have been notified prior to the use of the
temporary door locking
device
; and
6.
In-service
training on the use of the
temporary door
locking device
is provided for school
staff members and records verifying this training is to be maintained on file
and provided to the fire official upon request.
1010.2.16.1.2
Conditions of use in Groups A, B, F, H, I-4, M, S, and U
occupancies.
(1)
The device is to only be engaged for a finite period of
time, in an emergency situation or during active shooter drills;
and
(2)
The device is to only be used by the owner of the
building
or a person authorized by the owner; and
(3)
The owner of
a
building
is to notify the police chief, or equivalent, of the
law enforcement agency that has jurisdiction over the
building
, and the
fire chief, or equivalent, of the fire department that serves the political
subdivision in which the
building
is located,
prior to the use of such devices in a
building
;
and
(4)
The owner is to provide training to any person who may
use the device on its use and maintain a record verifying this training on
file.
1010.2.16.2
Operational requirements.
The
temporary
door locking device
is to comply with
the following:
1.
The device should be capable of being removed or
disengaged from outside the room by authorized personnel.
2.
The removal of
the
temporary door locking
device
, after it is engaged, is to not
require more than one operation.
Exception:
Two operations may be permitted to remove a
temporary door locking
device
, after it is engaged, if
the
building
is equipped throughout with an automatic sprinkler
system in accordance with section 903.3.1.1.
3.
Modifications are
not to be made to listed panic
hardware
,
fire door hardware
or door closers.
4.
Modifications
to
fire door
assemblies are to be in accordance with NFPA
80.
5.
The
temporary
door locking devices
are not to be
permanently mounted to the door.
Exception:
Individual parts of the
temporary door locking device
assembly such as bolts, stops, brackets, pins, etc.
that do not prevent normal ingress and egress through the door may be
permanently mounted provided that when such parts are mounted on a
labeled
fire door assembly
such installation does not affect the fire rating of
the
fire door assembly
.
Provisions of the "Americans with
Disabilities Act of 1990," 104 Stat. 327,
42 U.S.C.A.
12101, as amended, may apply to the use of
the
temporary door locking
device
but are outside the scope of this
code.
(I)
Modify
Section 1011.16 to add an exception that
reads as follows:
Exception:
Ladders complying with ASME A17.1 for elevator pit
access.
(J)
Replace Table 1020.2 with the
following:
TABLE 1020.2
CORRIDOR FIRE-RESISTANCE
RATING
OCCUPANCY
|
OCCUPANT
LOAD SERVED BY CORRIDOR
|
REQUIRED
FIRE-RESISTANCE RATING (hours)
|
Without
sprinkler system or provided with a partial sprinkler
system
|
With
sprinkler system
|
Type of
sprinkler system
|
13D
|
13R
|
13
|
H-1, H-2,
H-3
|
All
|
NP
|
NP
|
NP
|
1
|
H-4, H-5
|
Greater than
30
|
NP
|
NP
|
NP
|
1
|
A, B, E, F, M, S,
U
|
Greater than
30
|
1
|
NP
|
NP
|
0
|
R
|
Greater than
10
|
1
|
1
|
0.5
|
0.5
|
I-1
|
All
|
NP
|
1
|
1
|
1
|
I-2a
|
All
|
NP
|
NP
|
NP
|
0
|
I-3
|
All
|
NP
|
NP
|
NP
|
1b
|
I-4
|
All
|
1
|
NP
|
1
|
0
|
NP = Not Permitted
a. For requirements for occupancies in
Group I-2, see Sections
407.2 and
407.3.
b. For a reduction in the
fire-resistance rating for occupancies in Group I-3, see Section
408.8.
c. Buildings equipped throughout with
an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2
where allowed.
d. Group R-3 and R-4 buildings equipped
throughout with an automatic sprinkler system in accordance with Section
903.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler
systems are permitted in accordance with Section 903.3.1.3.
(K)
Replace Section
1027.2 with the
following:
1027.2
Use in a means of egress.
Exterior exit stairways are not to be used as an
element of a required
means of
egress
for Group I-2, I-4 and daycare
facilities in Group E occupancies. For occupancies in other than Group I-2, I-4
and daycare facilities in Group E exterior exit stairways and ramps are to be
permitted as an element of a required
means of egress
for
buildings
not
exceeding six stories above grade plane or that are not
high-rise buildings
.
Replaces: 4101:1-10-01
Notes
Ohio Admin. Code 4101:1-10-01
Effective:
3/1/2024
Five Year Review (FYR) Dates:
03/01/2029
Promulgated
Under: 119.03
Statutory Authority: 3781.10(A)(1), 3781.106
Rule Amplifies: 3781.10, 3781.106, 3781.11, 3791.04
Prior Effective Dates: 01/01/1994, 07/01/1995, 02/01/1996,
03/01/1998, 01/01/2002, 03/01/2005, 09/06/2005, 07/01/2007, 11/01/2007,
11/01/2011, 03/15/2012, 03/01/2013, 07/01/2014, 04/18/2016, 11/01/2017,
08/01/2018