Or. Admin. Code § 340-150-0310 - Spill and Overfill Prevention Equipment and Testing Requirements
(1) An owner and
permittee must install, operate and maintain, spill prevention equipment, such
as a spill catchment basin or a spill bucket, that will prevent the release of
a regulated substance to the environment when the transfer hose is detached
from the fill pipe.
(2) An owner
and permittee must install, operate, and maintain overfill prevention equipment
and follow fill procedures, that prevent any of the fittings located on top of
the UST from being exposed to a regulated substance due to overfilling; and
(a) Automatically shuts off flow into the UST
when the UST is no more than 95 percent full; or
(b) Alerts the person depositing the
regulated substance into the UST when the UST is no more than 90 percent full
by restricting the flow into the tank or by triggering a high level
alarm.
(3) For all UST
systems installed, or overfill equipment replaced, on or after March 1, 2003,
an owner and permittee must be able to provide visual verification that the
overfill equipment functions as section (2) of this rule requires. For overfill
equipment installed before March 1, 2003, an owner and permittee must be able
to demonstrate to DEQ that the equipment functions properly by any method DEQ
deems acceptable.
(4) An owner or
permittee cannot install flow restrictors in vent lines as an overfill
prevention method. Additionally, if a flow restrictor fails to function
properly, it cannot be repaired.
(5) In addition to the overfill requirements
of section (2) of this rule, an owner and permittee must:
(a) Measure the volume of regulated substance
in each UST to confirm that the volume available is greater than the volume of
the regulated substance to be deposited into the UST before each deposit is
made; and
(b) Develop and implement
procedures to ensure that each deposit of a regulated substance into the UST is
monitored constantly to prevent overfilling and spilling.
(6) An owner and permittee may use the codes
and procedures listed in Appendix C of this division to comply with the
requirements of this rule. [View a PDF of Appendix C by clicking on the
"Tables" link at the end of this rule.]
(7) Spill and overfill prevention equipment
is not required if the UST system is filled by deposits of a regulated
substance of no more than 25 gallons at one time (a waste oil tank may be one
example).
(8) Spill prevention
equipment, such as a catchment basin, spill bucket, or other spill containment
device, and containment sumps used for interstitial monitoring of piping, must
prevent releases to the environment by meeting one of the following:
(a) If the equipment is double walled, owners
and permittees must ensure that it is operating properly and will prevent
releases to the environment, by monitoring the integrity of both walls every 30
days. If the owner and permittee discontinues monitoring under this section,
the owner and permittee must conduct a test under paragraph (A), or (B) or (C)
below, within 30 days of discontinuing periodic monitoring and every three
years thereafter; or
(b) The spill
prevention equipment and containment sumps used for interstitial monitoring of
piping are tested at least once every three years to ensure the equipment is
liquid tight by using vacuum, pressure, or liquid testing. This testing must
comply with one of the following criteria:
(A) Requirements the manufacturer developed.
However, owners and operators may use this option only if the manufacturer has
developed requirements;
(B) Code of
practice developed by a nationally recognized association or independent
testing laboratory; or
(C)
Requirements DEQ determined are no less protective of human health and the
environment than the requirements listed in paragraphs (8)(b)(A) and (8)(b)(B)
of this section.
(9) Overfill prevention equipment must be
inspected at least once every three years. At a minimum, the inspection must
ensure that overfill prevention equipment is set to activate at the correct
level specified in OAR
340-150-0310 and will activate
when a regulated substance reaches that level. Inspections must be conducted as
set forth in paragraph (8)(a) through (c) of this rule.
(10) Owners and permittees must begin meeting
the requirements of sections (8) and (9) by conducting the initial spill
prevention equipment test and overfill prevention equipment inspection not
later than October 1, 2020.
(11)
Owners and permittees must maintain the following records for spill and
overfill prevention equipment:
(a) All
records of testing or inspection for three years; and
(b) For spill prevention equipment not tested
every three years, documentation showing that the prevention equipment is
double walled and the integrity of both walls is periodically monitored must be
maintained for as long as the equipment is periodically monitored.
(c) An owner and permittee must have the
records available for review by DEQ upon request.
(12) An owner and permittee may use the codes
and procedures listed in Appendix C of this division to comply with the
requirements of this rule.
[Note: View a PDF of Appendix C by clicking on the "Tables" link below.]
Notes
To view tables referenced in rule text, click here to view rule.
Statutory/Other Authority: ORS 466.706 - 466.835, 466.994 & 466.995
Statutes/Other Implemented: ORS 466.746 & 466.765