Or. Admin. Code § 340-150-0420 - Release Detection Requirements for Hazardous Substance UST Systems
(1) An owner and
permittee of an UST system containing a hazardous substance other than
petroleum must provide release detection that meets the requirements of this
rule.
(2) Secondary containment
systems. An owner and permittee may use the provisions of
40 CFR §
265.193
, "Containment and Detection
of Releases" to comply with this section of the rule. Secondary containment
systems must be designed, constructed and installed to:
(a) Contain regulated substances released
from the UST system until they are detected and removed; and
(b) Prevent the release of regulated
substances to the environment at any time during the operational life of the
UST system.
(3)
Multiwalled USTs must be designed, constructed and installed to:
(a) Contain a release from any portion of the
inner tank within the outer wall; and
(b) Detect the failure of the inner
wall.
(4) External
liners (including vaults) must be designed, constructed and installed to:
(a) Contain 100 percent of the capacity of
the largest tank within its boundary;
(b) Prevent the interference of precipitation
or groundwater intrusion with the ability to contain or detect a release of
regulated substances; and
(c)
Surround the tank completely (i.e., it is capable of preventing lateral as well
as vertical migration of regulated substances).
(5) Underground piping must be equipped with
secondary containment that satisfies the requirements of section (2) of this
rule (e.g., trench liners, jacketing of double walled pipe). In addition,
underground piping that conveys regulated substances under pressure must be
equipped with an automatic line leak detector in accordance with OAR
340-150-0410(2).
(6) An owner and permittee must monitor the
UST system for releases every 30 days and record the results for each
month.
(7) An owner and permittee
must retain at a minimum the most current 12 consecutive months of release
detection records.
(8) An owner and
permittee must report to the department any release detection failure
indicating the possibility of a release within 24 hours as a suspected release
(OAR 340-150-0500) and immediately
begin investigation in accordance with
340-150-0510.
(9) An owner and permittee may use an
alternative method of release detection if the proposed method is approved by
the department in writing before installation of the UST system or addition of
the release detection method. To obtain approval from the department, an owner
and permittee must submit the following information for review:
(a) Technical, scientific data and reports
that demonstrate that the proposed alternate method can detect a release of the
stored hazardous substance as effectively as any of the methods allowed in OAR
340-150-0450 through
340-150-0470 can detect a
release of petroleum; and
(b)
Information on the effective corrective action technologies, health and
environmental risks and chemical and physical properties of the stored
substance and the geologic characteristics of the UST facility.
Notes
Publications: Publications referenced are available from the agency.
Stat. Auth.: ORS 466.706 - ORS 466.835, ORS 466.994 & ORS 466.995
Stats. Implemented: ORS 466.746 & ORS 466.765
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.