Or. Admin. Code § 340-230-0120 - Solid and Infectious Waste Incinerators: Design and Operation
(1) Temperature and
Residence Time. Each incinerator must be designed and operated to maintain
combustion gases at a minimum temperature of 1,800° F. for at least one
second residence time. For a multi-chamber incinerator, these parameters must
be met after the primary combustion chamber, which must be maintained at no
less than 1,000° F.
(2)
Auxiliary Burners. Each incinerator must be designed and operated with
automatically controlled auxiliary burners capable of maintaining the
combustion chamber temperatures specified in section (1) of this rule, and must
have sufficient auxiliary fuel capacity to maintain said
temperatures.
(3) Interlocks. Each
incinerator must be designed and operated with an interlock system that:
(a) Prevents charging until the final
combustion chamber reaches 1,800° F.;
(b) For batch-fed incinerators, prevents
recharging until each combustion cycle is complete;
(c) Ceases charging if the incinerator
temperature falls below either 1,800° F. for any continuous 15-minute
period; and
(d) Ceases charging if
carbon monoxide levels exceed 150 ppm, corrected to seven percent O2 over a
continuous 15-minute period. Existing incinerators may request from the
Department, and the Department may grant, an exemption for installing an
interlock system, if it can be shown to the satisfaction of the Department that
such a system would not allow sufficient flexibility in operation, or that
significant technical or economic constraints would prevent
retrofitting.
(4) Air
Locks. All infectious waste facilities with mechanically fed incinerators must
be designed and operated with an air lock control system to prevent opening the
incinerator to the room environment. The volume of the loading system must be
designed so as to prevent overcharging to assure complete combustion of the
waste.
(5) Flue Gas Outlet
Temperature. Each incinerator must be designed and operated such that the flue
gas temperature at the outlet from the primary control device does not exceed
350° F., unless it can be demonstrated that a greater collection of
condensible matter can be achieved at a higher outlet temperature.
(6) Combustion efficiency. Except during
periods of startup and shutdown, all waste incinerators must achieve a
combustion efficiency of 99.9 percent based on a running eight-hour average,
computed as follows: [Table not included. See ED. NOTE.]
(7) Stack Height. All incinerator stacks must
be designed in accordance with Good Engineering Practice (GEP) as defined in
40
CFR 51.100(ii) and
51.118,
in order to assure compliance with applicable air standards, and to avoid the
flow of stack pollutants into any building ventilation intake plenum.
(8) Operator Training and Certification. Each
incinerator must be operated at all times under the direction of one or more
individuals who have received training necessary for proper operation. A
description of the training program must be submitted to the Department for
approval. A satisfactory training program consists of any of the following:
(a) Certification by the American Society of
Mechanical Engineers (ASME) for solid waste incinerator operation; or
(b) For infectious waste incineration,
successful completion of EPA's Medical Waste Incinerator Operator training
course; or
(c) Other certification
or training by a qualified organization as to proper operating practices and
procedures, which has been pre-approved by the Department before enrollment. In
addition, the owner or operator of an incinerator facility must develop and
submit a manual for proper operation and maintenance, to be reviewed with
employees responsible for incinerator operation on an annual basis.
(9) In cases where incinerator
operation may cause odors that unreasonably interfere with the use and
enjoyment of property, the Department may require by permit the use of good
practices and procedures to prevent or eliminate those odors.
[NOTE: View a PDF of Section (6) formula by clicking on "Tables" link below.]