This rule provides additional requirements for work on
underground electrical installations.
(1) Access. The employer must ensure that
employees use a ladder or other climbing device to enter and exit a manhole or
subsurface vault exceeding 1.22 meters (4 feet) in depth. No employee may climb
into or out of a manhole or vault by stepping on cables or hangers.
(2) Lowering equipment into manholes.
(a) Equipment used to lower materials and
tools into manholes or vaults must be capable of supporting the weight to be
lowered and must be checked for defects before use.
(b) Before anyone lowers tools or material
into the opening for a manhole or vault, each employee working in the manhole
or vault must be clear of the area directly under the opening.
(3) Attendants for manholes and
vaults.
(a) While work is being performed in
a manhole or vault containing energized electric equipment, an employee with
first-aid and cardiopulmonary resuscitation training must be available on the
surface in the immediate vicinity of the manhole or vault entrance to render
emergency assistance.
(b)
Occasionally, the employee on the surface may briefly enter a manhole or vault
to provide nonemergency assistance.
Note 1 to paragraph (3)(b):
437-002-2304(7)
of Division 2/RR may also require an attendant and does not permit this
attendant to enter the manhole or vault.
Note 2 to paragraph (3)(b):
437-002-2311(1)(b)
of Division 2/RR requires employees entering manholes or vaults containing
unguarded, uninsulated energized lines or parts of electric equipment operating
at 50 volts or more to be qualified.
(c) For the purpose of inspection,
housekeeping, taking readings, or similar work, an employee working alone may
enter, for brief periods of time, a manhole or vault where energized cables or
equipment are in service if the employer can demonstrate that the employee will
be protected from all electrical hazards.
(d) The employer must ensure that employees
maintain reliable communications, through two-way radios or other equivalent
means, among all employees involved in the job.
(4) Duct rods. The employer must ensure that,
if employees use duct rods, the employees install the duct rods in the
direction presenting the least hazard to employees. The employer must station
an employee at the far end of the duct line being rodded to ensure that the
employees maintain the required minimum approach distances.
(5) All primary cables must be permanently
and plainly identified by tags or other methods at both ends.
(6) Multiple cables. When multiple cables are
present in a work area, the employer must identify the cable to be worked by
electrical means, unless its identity is obvious by reason of distinctive
appearance or location or by other readily apparent means of identification.
The employer must protect cables other than the one being worked from damage.
(7) Moving cables. Except when
paragraph (8)(b) of this rule permits employees to perform work that could
cause a fault in an energized cable in a manhole or vault, the employer must
ensure that employees inspect energized cables to be moved for abnormalities.
(8) Protection against faults.
(a) Where a cable in a manhole or vault has
one or more abnormalities that could lead to a fault or be an indication of an
impending fault, the employer must deenergize the cable with the abnormality
before any employee may work in the manhole or vault, except when service-load
conditions and a lack of feasible alternatives require that the cable remain
energized. In that case, employees may enter the manhole or vault provided the
employer protects them from the possible effects of a failure using shields or
other devices that are capable of containing the adverse effects of a fault.
The employer must treat the following abnormalities as indications of impending
faults unless the employer can demonstrate that the conditions could not lead
to a fault: Oil or compound leaking from cable or joints, broken cable sheaths
or joint sleeves, hot localized surface temperatures of cables or joints, or
joints swollen beyond normal tolerance.
(b) If the work employees will perform in a
manhole or vault could cause a fault in a cable, the employer must deenergize
that cable before any employee works in the manhole or vault, except when
service-load conditions and a lack of feasible alternatives require that the
cable remain energized. In that case, employees may enter the manhole or vault
provided the employer protects them from the possible effects of a failure
using shields or other devices that are capable of containing the adverse
effects of a fault.
(9)
Sheath continuity. When employees perform work on buried cable or on cable in a
manhole or vault, the employer must maintain metallic-sheath continuity, or the
cable sheath must be treated as energized.