This rule applies to work on or near exposed live parts.
(1) General.
(a) Only qualified employees may work on or
with exposed energized lines or parts of equipment.
(b) Only qualified employees may work in
areas containing unguarded, uninsulated energized lines or parts of equipment
operating at 50 volts or more.
(c)
Electric lines and equipment must be considered and treated as energized unless
they have been deenergized in accordance with
437-002-2303 Hazardous Energy
Control, or
437-002-2312, of Division 2/RR.
(2) Two worker rules.
(a) Not fewer than two qualified employees
may work on lines or equipment energized at more than 600 volts while
performing the following types of work:
(A)
Installation, removal, or repair of lines energized at more than 600 volts,
(B) Installation, removal, or
repair of deenergized lines if an employee is exposed to contact with other
parts energized at more than 600 volts,
(C) Installation, removal, or repair of
equipment, such as transformers, capacitors, and regulators, if an employee is
exposed to contact with parts energized at more than 600 volts,
(D) Work involving the use of mechanical
equipment, other than insulated aerial lifts, near parts energized at more than
600 volts, and
(E) Other work that
exposes an employee to electrical hazards greater than, or equal to, the
electrical hazards posed by operations listed specifically in paragraphs
(2)(a)(A) through (2)(a)(E) of this section.
(b) The following exceptions to the
two-worker rule in
437-002-2311(2)(a)(A) through
(2)(a)(E) apply:
(A) When re-fusing circuits with a live-line
tool.
(B) When operating switches
by means of operating handles or live-line tools, excluding installation or
removal of load break elbows with live line tools, addressed in paragraph
(2)(b)(E) of this rule.
(C) When a
qualified apprentice is assigned to work with a journeyman for the purpose of
training.
(D) When installing or
removing a live-line clamp connection with an approved live-line tool on single
phase line or apparatus, providing that the connection or disconnection does
not interrupt or pick up a load.
(E) Routine circuit switching, including
installation or removal of a load break elbow with a live line tool on a single
phase line or apparatus, with only one potential primary source.
(i) Authorized employees must conduct an
inspection to determine that conditions on the site allow for safe work.
Conditions include the following examples:
(I) Physical condition of the cable, elbows,
apparatus, and switching equipment.
(II) Environmental and work conditions, such
as limited visibility, bad weather, restricted working space, and poor
lighting.
(III) Service life of
the elbow, power cable, and apparatus.
(ii) When an employee requests a second
worker on site, a second worker must be provided.
(F) Emergency repairs to the extent necessary
to safeguard the general public.
(G) Work performed with live-line tools when
the position of the employee is such that he or she is neither within reach of,
nor otherwise exposed to contact with, energized parts.
(c) Proximity. Workers within reach of each
other must not work on different phases of the same circuit, on different
circuits, or on one energized phase and a ground conductor at the same time.
(3) Minimum approach
distances.
(a) The employer must establish
minimum approach distances no less than the distances computed by Table RR-2
for ac systems or Table RR-7 for dc systems.
(b) For voltages over 72.5 kilovolts, the
employer must determine the maximum anticipated per-unit transient overvoltage,
phase-to-ground, through an engineering analysis or assume a maximum
anticipated per-unit transient overvoltage, phase-to-ground, in accordance with
Table RR-8. When the employer uses portable protective gaps to control the
maximum transient overvoltage, the value of the maximum anticipated per-unit
transient overvoltage, phase-to-ground, must provide for five standard
deviations between the statistical sparkover voltage of the gap and the
statistical withstand voltage corresponding to the electrical component of the
minimum approach distance. The employer must make any engineering analysis
conducted to determine maximum anticipated per-unit transient overvoltage
available upon request to employees and to Oregon OSHA for examination and
copying.
Note to paragraph (3)(b): See Appendix B to
Division 2/RR for information on how to calculate the maximum anticipated
per-unit transient overvoltage, phase-to-ground, when the employer uses
portable protective gaps to reduce maximum transient overvoltages.
(c) The employer must ensure that
no employee approaches or takes any conductive object closer to exposed
energized parts than the employer's established minimum approach distance,
unless:
(A) The employee is insulated from
the energized part. Rubber insulating gloves or rubber insulating gloves and
sleeves worn in accordance with paragraph (4) of this rule constitutes
insulation of the employee from the energized part upon which the employee is
working provided that the employee has control of the part in a manner
sufficient to prevent exposure to uninsulated portions of the employee's body;
or
(B) The energized part is
insulated from the employee and from any other conductive object at a different
potential.
(C) Live-line barehand
work is prohibited in Oregon.
(4) Type of insulation: Adequate barriers and
clearances.
(a) Protective equipment and
devices must be installed or removed with:
(A) Rubber gloves or hot sticks on conductors
or equipment energized at 5,000 volts or less.
(B) Live line tools for conductors or
equipment energized in excess of 5,000 volts.
(C) Rubber protective equipment may be
considered as adequate barriers when used on voltages for which it is rated.
Rubber gloves may be used as additional protection from accidental contact only
on voltages above 5,000 and not over 15,000 volts phase to ground.
(D) Rubber gloves cannot be used as primary
protection on voltages over 5,000 volts.
(E) Fixed protective guards and barriers,
when installed and maintained according to the manufacturer's guidelines, may
be considered as providing adequate clearance.
(b) When an employee uses rubber insulating
gloves as insulation from energized parts (under paragraph (3)(c)(A) of this
rule), the employer must ensure that the employee also uses rubber insulating
sleeves. However, an employee need not use rubber insulating sleeves if:
(A) Exposed energized parts on which the
employee is not working are insulated from the employee; and
(B) When installing insulation for purposes
of paragraph (4)(b)(A) of this rule, the employee installs the insulation from
a position that does not expose their upper arms to contact with other
energized parts.
(c)
When an employee uses rubber insulating gloves or rubber insulating gloves and
sleeves as insulation from energized parts (under paragraph (3)(c)(A) of this
rule), the employer must ensure that the employee:
(A) Puts on the rubber insulating gloves and
sleeves in a position where they cannot reach into the minimum approach
distance, established by the employer under paragraph (3)(a) of this rule; and
(B) Does not remove the rubber
insulating gloves and sleeves until they are in a position where they cannot
reach into the minimum approach distance, established by the employer under
paragraph (3)(a) of this rule.
(5) Working position.
(a) The employer must ensure that each
employee, to the extent that other safety-related conditions at the worksite
permit, works in a position from which a slip or shock will not bring the
employee's body into contact with exposed, uninsulated parts energized at a
potential different from the employee's.
(b) When an employee performs work near
exposed parts energized at more than 600 volts, but not more than 72.5
kilovolts, and is not wearing rubber insulating gloves, being protected by
insulating equipment covering the energized parts, performing work using
live-line tools, the employee must work from a position where he or she cannot
reach into the minimum approach distance, established by the employer under
paragraph (3)(a) of this rule.
(6) Making connections. The employer must
ensure that employees make connections as follows:
(a) In connecting deenergized equipment or
lines to an energized circuit by means of a conducting wire or device, an
employee must first attach the wire to the deenergized part;
(b) When disconnecting equipment or lines
from an energized circuit by means of a conducting wire or device, an employee
must remove the source end first; and
(c) When lines or equipment are connected to
or disconnected from energized circuits, an employee must keep loose conductors
away from exposed energized parts.
(7) Conductive articles. When an employee
performs work within reaching distance of exposed energized parts of equipment,
the employer must ensure that the employee removes or renders nonconductive all
exposed conductive articles, such as keychains or watch chains, rings, or wrist
watches or bands, unless such articles do not increase the hazards associated
with contact with the energized parts.
(8) Protection from flames and electric arcs.
(a) The employer must assess the workplace to
identify employees exposed to hazards from flames or from electric arcs.
(b) For each employee exposed to
hazards from electric arcs, the employer must make a reasonable estimate of the
incident heat energy to which the employee would be exposed.
Note 1 to paragraph (8)(b): Appendix E to Division
2/RR provides guidance on estimating available heat energy. Oregon OSHA will
deem employers following the guidance in Appendix E to Division 2/RR to be in
compliance with paragraph (8)(b) of this rule. An employer may choose a method
of calculating incident heat energy not included in Appendix E to Division 2/RR
if the chosen method reasonably predicts the incident energy to which the
employee would be exposed.
Note 2 to paragraph (8)(b): This paragraph does
not require the employer to estimate the incident heat energy exposure for
every job task performed by each employee. The employer may make broad
estimates that cover multiple system areas provided the employer uses
reasonable assumptions about the energy-exposure distribution throughout the
system and provided the estimates represent the maximum employee exposure for
those areas. For example, the employer could estimate the heat energy just
outside a substation feeding a radial distribution system and use that estimate
for all jobs performed on that radial system.
(c) The employer must ensure that each
employee who is exposed to hazards from flames or electric arcs does not wear
clothing that could melt onto their skin or that could ignite and continue to
burn when exposed to flames or the heat energy estimated under paragraph (8)(b)
of this rule.
Note to paragraph (8)(c) of this rule: This
paragraph prohibits clothing made from acetate, nylon, polyester, rayon and
polypropylene, either alone or in blends, unless the employer demonstrates that
the fabric has been treated to withstand the conditions that may be encountered
by the employee or that the employee wears the clothing in such a manner as to
eliminate the hazard involved.
(d) The employer must ensure that the outer
layer of clothing worn by an employee, except for clothing not required to be
arc rated under paragraphs (8)(e)(A) through (8)(e)(E) of this rule, is flame
resistant under any of the following conditions:
(A) The employee is exposed to contact with
energized circuit parts operating at more than 600 volts,
(B) An electric arc could ignite flammable
material in the work area that, in turn, could ignite the employee's clothing,
(C) Molten metal or electric arcs
from faulted conductors in the work area could ignite the employee's clothing,
or
Note to paragraph (8)(d)(C): This paragraph does
not apply to conductors that are capable of carrying, without failure, the
maximum available fault current for the time the circuit protective devices
take to interrupt the fault.
(D) The incident heat energy estimated under
paragraph (8)(b) of this rule exceeds 2.0 cal/cm2.
(e) The employer must ensure that each
employee exposed to hazards from electric arcs wears protective clothing and
other protective equipment with an arc rating greater than or equal to the heat
energy estimated under paragraph (8)(b) of this rule whenever that estimate
exceeds 2.0 cal/cm2. This protective equipment must cover the employee's entire
body, except as follows:
(A) Arc-rated
protection is not necessary for the employee's hands when the employee is
wearing rubber insulating gloves with protectors or, if the estimated incident
energy is no more than 14 cal/cm2, heavy-duty leather work gloves with a weight
of at least 407 gm/m2 (12 oz/yd2),
(B) Arc-rated protection is not necessary for
the employee's feet when the employee is wearing heavy-duty work shoes or
boots,
(C) Arc-rated protection is
not necessary for the employee's head when the employee is wearing head
protection meeting
437-002-0134(9)
and
437-003-0134(9)
if the estimated incident energy is less than 9 cal/cm2 for exposures involving
single-phase arcs in open air or 5 cal/cm2 for other exposures,
(D) The protection for the employee's head
may consist of head protection meeting
437-002-0134(9)
and
437-003-0134(9),
and a faceshield with a minimum arc rating of 8 cal/cm2 if the estimated
incident-energy exposure is less than 13 cal/cm2 for exposures involving
single-phase arcs in open air or 9 cal/cm2 for other exposures, and
(E) For exposures involving single phase arcs
in open air, the arc rating for the employee's head and face protection may be
4 cal/cm2 less than the estimated incident energy.
Note to paragraph (8): See Appendix E to Division
2/RR for further information on the selection of appropriate protection.
(9) Fuse
handling. When an employee must install or remove fuses with one or both
terminals energized at more than 300 volts, or with exposed parts energized at
more than 50 volts, the employer must ensure that the employee uses tools or
gloves rated for the voltage. When an employee installs or removes
expulsion-type fuses with one or both terminals energized at more than 300
volts, the employer must ensure that the employee wears eye protection meeting
the requirements of Division 2/I and Division 3/E, uses a tool rated for the
voltage, and is clear of the exhaust path of the fuse barrel.
(10) Covered (non-insulated) conductors. The
requirements of this section that pertain to the hazards of exposed live parts
also apply when an employee performs work in proximity to covered
(non-insulated) wires.
(11)
Non-current-carrying metal parts. Non-current-carrying metal parts of equipment
or devices, such as transformer cases and circuit-breaker housings, must be
treated as energized at the highest voltage to which these parts are exposed,
unless the employer inspects the installation and determines that these parts
are grounded before employees begin performing the work.
(12) Opening and closing circuits under load.
(a) The employer must ensure that devices
used by employees to open circuits under load conditions are designed to
interrupt the current involved.
(b) The employer must ensure that devices
used by employees to close circuits under load conditions are designed to
safely carry the current involved.
(13) Safety Watch
(a) A qualified safety watch must be provided
in areas where inadvertent motions, movements, or tool use would violate
Minimum Approach Distances (MAD). The safety watch's sole duty is to keep
constant watch over persons working within the MAD, to warn them of danger, and
to stop the work when necessary.
(b) The foreman or other worker in charge of
the work being performed is responsible for the designation of the safety
watch. It is the responsibility of the worker in charge to select a qualified
worker who is capable and familiar with the work.
(c) The worker in charge may act as a safety
watch providing no other duties interfere. If the worker in charge is
distracted or must leave the immediate vicinity, that worker must either
designate another qualified person as the safety watch or order the work
stopped.
(d) Use of vehicles, gin
poles, cranes, and other equipment in restricted or hazardous areas must at all
times be monitored by a qualified safety watch other than the equipment
operator. Tables RR-2 through RR-8.