(2) Definitions.
(a) Appurtenances -- All devices such as
pumps, compressors, safety relief devices, liquid-level gaging devices, valves
and pressure gages.
(b) Capacity --
Total volume of the container in standard U.S. gallons.
(c) Certified -- See universal definitions in
Subdivision 4/B, OAR
437-004-0100.
(d) Code -- The Boiler and Pressure Vessel
Code, Section VIII, Unfired Pressure Vessels of the American Society of
Mechanical Engineers (ASME) -- 1968.
(e) Container -- Includes all vessels, tanks,
cylinders, or spheres used for transportation, storage, or application of
anhydrous ammonia.
(f) Cylinder --
A container of 1,000 pounds of water capacity or less built according to
Department of Transportation specifications.
(g) Design pressure -- is identical to the
term "Maximum Allowable Working Pressure" used in the Code.
(h) DOT -- U.S. Department of
Transportation.
(i) DOT
specifications -- Regulations of the Department of Transportation in 49 CFR
Chapter
I.
(j) Farm vehicle
(implement of husbandry) -- A vehicle for use on a farm with a container of not
more than 1,200 gallons water capacity on it.
(k) Labeled -- See universal definitions in
Subdivision 4/B, OAR
437-004-0100.
(l) Listed -- See universal definitions in
Subdivision 4/B, OAR
437-004-0100.
(3) Basic rules.
(a) Approval of equipment and systems. All
systems, equipment and appurtenances must comply with one of the following
three paragraphs.
(A) If installed before
February 8, 1973, it must comply with American National Standard for the
Storage and Handling of Anhydrous Ammonia, K61.1-1999 or CGA
G-2.1-1999.
(B) It must be listed
and labeled by a nationally recognized testing laboratory as defined in
29 CFR
1910.7.
(C) A registered engineer may test and
certify custom designed and custom built systems as meeting the criteria in OAR
437-004-0800(3)(a)(A).
This certification must be on file with the employer for agency review. The
certification must detail the test criteria, data and results along with the
qualifications of the person doing the test.
(b) Requirements for construction, original
test and recertification of non-refrigerated containers.
(A) Only competent persons and/or companies
may design, install and maintain non-refrigerated containers.
(B) Containers used with systems in OAR
437-004-0800(4), (7), (8) and
(9) must comply with the Code (Boiler and
Pressure Vessel Code, Sec VIII, Unfired Pressure Vessels of the American
Society of Mechanical Engineers (ASME) -- 1968). Construction under Table UW 12
at a basic joint efficiency of less than 80 percent is not
authorized.
(C) Containers more
than 36 inches in diameter or 250 gallons water capacity must comply with one
or more of the following:
(i) Containers must
be stress relieved after fabrication according to the Code; or
(ii) Cold-form heads must be stress relieved;
or
(iii) Use only hot-formed
heads.
(D) Paragraph (B)
above does not prohibit the continued use or reinstallation of containers
constructed and maintained according to the 1949, 1950, 1952, 1956, 1959, and
1962 editions of the Code or any revisions in effect at the time of
fabrication.
(E) Welding to the
shell, head or any other part of the container subject to internal pressure
must comply with the Code. Other welding is permitted only on saddle plates,
lugs or brackets attached to the container by the container
manufacturer.
(F) Containers used
with systems in OAR
437-004-0800(5)
must comply with DOT specifications.
(c) Marking of
containers. Keep the original markings on refrigerated and non-refrigerated
containers as they were at the time of installation.
(d) Location of containers.
(A) When selecting the location for the
storage container consider the physiological effects as well as adjacent fire
hazards. Locate containers outside buildings unless the building was built for
this purpose.
(B) Locate permanent
storage containers 50 feet from a dug well or other sources of potable water
supply, unless the container is a part of a water-treatment
installation.
(C) Keep storage
areas free of readily ignitible materials such as waste, weeds and long dry
grass.
(e) Container
appurtenances.
(A) Design appurtenances to
stand the maximum working pressure of that part of the system on which they are
installed. Make appurtenances from material proved suitable for anhydrous
ammonia service.
(B) All
connections to containers except safety relief devices, gaging devices, or
those fitted with a .0550-inch orifice must have shutoff valves as close to the
container as practicable.
(C)
Excess flow valves where required by these standards must close automatically
at the rated flows of vapor or liquid specified by the manufacturer. The
connections and line including valves and fittings protected by an excess flow
valve must have a larger capacity than the rated flow of the excess flow valve
so that the valve will close in case of failure of the line or
fittings.
(D) Liquid-level gaging
devices that require bleeding of the product to the atmosphere and are built so
that outward flow will not be more than that passed by a .0550-inch opening do
not need excess flow valves.
(E)
Openings from the container or through fittings attached directly on the
container to which pressure gage connections are made need do not need excess
flow valves if they are not larger than .0550-inch.
(F) Excess flow and back pressure check
valves where required by this section must be inside the container or if
outside as close as practicable to where the line enters the container. In the
latter case installation must prevent strain beyond the excess flow or back
pressure check valve from causing a break between the container and the
valve.
(G) Excess flow valves must
have a bypass not to exceed a .0400-inch opening to allow equalization of
pressures.
(H) All excess flow
valves must have plain and permanent markings with the name or trademark of the
manufacturer, the catalog number, and the rated capacity.
(f) Piping, tubing and fittings.
(A) All piping, tubing and fittings must be
made of material suitable for anhydrous ammonia service.
(B) All piping, tubing and fittings must be
designed for a pressure not less than the maximum pressure under which they
might operate.
(C) All refrigerated
piping must conform to the Refrigeration Piping Code, American National
Standard, B31.5-1966 with addenda B31.5a-1968 as it applies to
ammonia.
(D) Piping on
non-refrigerated systems must be at least American Society for Testing and
Materials (ASTM) A-53-69 Grade B Electric Resistance Welded and Electric Flash
Welded Pipe or equal. For welded or welded and flanged joints the pipe must be
at least schedule 40. For threaded joints the pipe must be at least schedule
80. Do not back-weld threaded connections. Do not use brass, copper or
galvanized steel pipe.
(E) Do not
use tubing made of brass, copper, or other material subject to attach by
ammonia.
(F) Do not use cast iron
fittings but this does not prohibit the use of fittings made specifically for
ammonia service or malleable, nodular, or high strength gray iron meeting
American Society for Testing and Materials (ASTM) A47-68, ASTM 395-68 or ASTM
A126-66 Class B or C.
(G) Use joint
compounds that are resistant to ammonia.
(g) Hose specifications.
(A) Hose used in ammonia service must conform
to the joint Agricultural Ammonia Institute -- Rubber Manufacturers Association
Specifications for Anhydrous Ammonia Hose.
(B) Hose subject to container pressure must
be designed for a minimum working pressure of 350 p.s.i.g. and a minimum burst
pressure of 1,750 p.s.i.g. Hose assemblies, when made up, must be capable of
withstanding a test pressure of 500 p.s.i.g.
(C) Hose and hose connections on the
low-pressure side of flow control or pressure-bleeding valves must have a
bursting pressure rating of not less than five times the pressure setting of
the safety relief devices protecting that part of the system but not less than
125 p.s.i.g. All connections must not leak when connected.
(D) Where using hose to transfer liquid from
one container to another, "wet" hose is recommended. Such hose must have
approved shutoff valves at the discharge end. Prevent excessive pressure in the
hose.
(E) On all hose 1/2-inch
outside diameter and larger, used for the transfer of anhydrous ammonia liquid
or vapor, there must be etched, cast, or impressed at 5-foot intervals the
following information.
NOTE: "Anhydrous Ammonia" xxx p.s.i.g. (maximum
working pressure), manufacturer's name or trademark, year of
manufacture.
NOTE: In place of this requirement the same
information may be on a nameplate permanently attached to the hose.Table 1
Footnotes
(h)
Safety relief devices.
(A) Every container in
systems covered by OAR
437-004-0800(4), (7), (8) and
(9) must have one or more safety relief
valves of the spring-loaded or equivalent type. The discharge from
safety-relief valves must vent away from the container, upward and unobstructed
to the atmosphere. All relief-valve discharge openings must have suitable rain
caps that allow free discharge of the vapor and prevent entrance of water.
Accumulated condensation must drain away. The rate of the discharge must comply
with
Table 1.
(B)
Container safety-relief valves must be set to start-to-discharge as follows,
with relation to the design pressure of the container: [Table not included. See
ED. NOTE.]
(C) Safety relief
devices in systems covered by OAR
437-004-0800(4), (7), (8) and
(9) must discharge at not less than the rates
in (3)(h)(A) above before the pressure is in excess of 120 percent (not
including the 10 percent tolerance in (3)(h)(B) above) of the maximum permitted
start-to-discharge pressure setting of the device.
(D) Arrange safety relief valves to minimize
the possibility of tampering. If the pressure setting adjustment is external,
the relief valves must have a means of sealing the adjustment.
(E) Shutoff valves must not be between the
safety relief valves and the container; except, that a shutoff valve may be
where the arrangement of this valve is such as to always afford full required
capacity flow through the relief valves.
(F) Safety relief valves must have direct
communication with the vapor space of the container.
(G) Each container safety relief valve used
with systems covered by OAR
437-004-0800(4), (7), (8) and
(9) must have plain and permanent markings
with the symbol "NH3" or "AA"; with the pressure in pounds-per-square-inch at
which the valve is set to start-to-discharge; with the actual rate of discharge
of the valve at its full open position in cubic feet per minute of air at 60
degrees F. and atmospheric pressure; and the manufacturer's name and catalog
number.
Example: "NH3 250-4050 Air" indicates that the
valve is suitable for use on an anhydrous ammonia container, is set to
start-to-discharge at a pressure of 250 p.s.i.g., and that its rate of
discharge at full open position is 4,050 cubic feet per minute of air.
(H) There must be no connection on
either the upstream or downstream side that restricts the flow capacity of the
relief valve.
(I) A hydrostatic
relief valve must be between each pair of valves in the liquid ammonia piping
or hose to relieve into the atmosphere at a safe location.
(i) General.
(A) All stationary storage installations must
have at least two readily accessible suit- able gas masks. Full face masks with
ammonia canisters, not cartridges, approved by the National Institute of
Occupational and Safety and Health (NIOSH), are suitable for emergency action
for most leaks, particularly those that are outdoors. For protection in
concentrated ammonia atmospheres the use of self-contained breathing air
apparatus is mandatory. Refer to OAR
437-004-1041 Respiratory
Protection, Division 4/I for additional requirements for personal protective
equipment.
(B) Stationary storage
installations must have an easily accessible shower or a 50-gallon drum of
water.
(C) Each vehicle
transporting ammonia in bulk except farm applicator vehicles must carry a
container of at least 5 gallons of water and a full face mask.
(j) Charging of containers.
(A) The filling densities for unrefrigerated
containers must not be more than the following:
(B) Aboveground uninsulated containers may be
charged 87.5 percent by volume if the temperature of the anhydrous ammonia
being charged is not lower that 30 degrees F. or if the charging of the
container stops at the first indication of frost or ice formation on its
outside surface and does not resume until the frost or ice is gone.
(k) Transfer of liquids.
(A) Anhydrous ammonia must always be at a
temperature suitable for the material of construction and the design of the
receiving container.
(B) The
employer must require the continuous presence of an attendant in the vicinity
of the operation during ammonia transfer.
(C) Charge and use containers only with
authorization of the owner.
(D)
Gage and charge containers only in the open atmosphere or in buildings or areas
for that purpose.
(E) Pumps used
for transferring ammonia must be made for that purpose.
(i) Pumps must be designed for at least 250
p.s.i.g. working pressure.
(ii)
Positive displacement pumps must have, installed off the discharge port, a
constant differential relief valve discharging into the suction port of the
pump through a line of sufficient size to carry the full capacity of the pump
at relief valve setting, which setting and installation must be according to
the pump manufacturer's recommendations.
(iii) On the discharge side of the pump,
before the relief valve line, there must be a pressure gage graduated from 0 to
400 p.s.i.
(iv) Plant piping must
have shutoff valves as close as practical to pump
connections.
(F)
Compressors for transferring or refrigerating ammonia must be recommended for
ammonia service by the manufacturer.
(i)
Compressors must be designed for at least 250 p.s.i.g. working
pressure.
(ii) Plant piping must
have shutoff valves located as close as practical to compressor
connections.
(iii) A relief valve
large enough to discharge the full capacity of the compressor must be connected
to the discharge before the shutoff valve.
(iv) Compressors must have pressure gages at
suction and discharge graduated to at least 1 1/2 times the maximum
pressure.
(v) Adequate means, such
as a drainable liquid trap, must be on the compressor suction to minimize the
entry of liquid into the compressor.
(G) In case the hose breaks, loading and
unloading systems must have suitable devices to prevent emptying of the storage
or supply container. Backflow check valves or properly sized excess flow valves
must be where necessary to provide this protection. If such valves are not
practical, remotely operated shutoff valves may are acceptable.
(l) Tank car unloading
points and operations.
(A) Unloading of tank
cars must conform to the applicable recommendations in DOT
regulations.
(B) The employer must
insure that unloading operations are done by reliable persons properly
instructed and with the authority to monitor careful compliance with all
applicable procedures.
(C) Caution
signs must be on the track or car to give warning to people approaching the car
from the open end or ends of the siding. They must be left up until after the
car is empty and disconnected from discharge connections. Signs must be metal
or other suitable material, at least 12 inches by 15 inches and bear the words
"STOP -- Tank Car Connected" or "STOP -- Men at Work" the word, "STOP," being
in letters at least 4 inches high and the other words in letters at least 2
inches high.
(D) The track of a
tank car siding must be substantially level.
(E) Set the brakes and block the wheels on
cars during unloading.
(m) Liquid-level gaging device.
(A) Each container except those filled by
weight must have an approved liquid-level gaging device. A thermometer well
must be in containers without a fixed liquid-level gaging device.
(B) All gaging devices must be arranged so
that the maximum liquid level to which the container is filled is readily
determined.
(C) Gaging devices that
require bleeding of the product to the atmosphere such as the rotary tube,
fixed tube, and slip tube devices must have a maximum opening of the bleed
valve not larger than .0550-inch unless they have an excess flow valve. (This
requirement does not apply to farm vehicles used for the application of ammonia
as in OAR
437-004-0800(9).)
(D) Gaging devices must have a design
pressure equal to or greater than the design pressure of their host
container.
(E) Fixed tube
liquid-level gages must indicate the container's 85 percent fill level of its
water capacity.
(F) Use columnar
gage glasses only on stationary storage installations. They must have shutoff
valves with metallic handwheels, excess-flow valves and extra heavy glass
adequately protected with a metal housing applied by the gage manufacturer.
They must be shielded from the direct rays of the sun.
(n) Electrical equipment and wiring.
(A) Electrical equipment and wiring for use
in ammonia installations must be general purpose or weather resistant as
appropriate.
(B) Electrical systems
must comply with 4/S.
(4) Systems using stationary,
non-refrigerated storage containers.
(a)
Applies to all storage containers except portable DOT containers.
(A) The minimum design pressure and
construction for non-refrigerated containers is 250 p.s.i.g.
(B) Each filling connection must have a
combination back-pressure check valve and excess-flow valve; one double or two
single back-pressure check valves; or a positive shutoff valve in conjunction
with either an internal back-pressure check valve or an internal excess flow
valve.
(C) All liquid and vapor
connections to containers except filling pipes, safety relief connections, and
liquid-level gaging and pressure gage connections with orifices not larger than
.0550-inch required in OAR
437-004-0800(3)(e)(D) and
(E) must have excess-flow valves.
(D) Each storage container must have a
pressure gage graduated from 0 to 400 p.s.i. Gages must be designated for use
in ammonia service.
(E) All
containers must have vapor return valves.
(b) Safety-relief devices.
(A) Every container must have one or more
safety-relief valves of the spring-loaded or equivalent type according to OAR
437-004-0800(b)(9).
(B) The rate of discharge of spring-loaded
safety relief valves on underground containers may be a minimum of 30 percent
of the rate of discharge in Table 1. After installation, do not uncover
containers with this protection until empty of liquid ammonia. Consider
containers that may contain liquid ammonia before being installed underground
and before being completely covered with earth to be aboveground containers
when determining the rate of discharge requirements of the safety-relief
valves.
(C) On underground
installations where there is a probability of the manhole or housing becoming
flooded, the discharge from vent lines must be above the high water level. All
manholes or housings must have ventilated louvers or their equivalent, the area
which equal or exceed the combined discharge areas of safety-relief valves and
vent lines that discharge their content into the manhole housing.
(D) Do not restrict vent pipes. They may not
be a smaller diameter than the relief-valve outlet connection.
(E) Vent pipes from two or more safety-relief
devices on the same unit, or similar lines from two or more different units may
run into a common discharge header, if the capacity of the header is at least
equal to the sum of the capacities of the individual discharge lines.
(c) Reinstallation of containers.
(A) Containers that were installed
underground must not be reinstalled above-ground or underground, unless they
withstand hydrostatic pressure retests at their original rating required by the
code under which they were made. They must show no serious corrosion.
(B) Containers reinstalled above-ground, must
have safety devices or gaging devices that comply with OAR
437-004-0800(i)
and this paragraph respectively for
above-ground containers.
(d) Installation of storage containers.
(A) Above-ground containers, except as in
(4)(d)(E) below must have substantial concrete or masonry supports, or
structural steel supports on firm concrete or masonry foundations. All
foundations must extend below the frost line.
(B) Horizontal above-ground containers must
be on foundations that permit expansion and contraction. Containers must have
supports that prevent the concentration of excessive loads on the supporting
portion of the shell. That part of the container in contact with foundations or
saddles must have corrosion protection.
(C) The top of underground containers must be
below the frost line and at least 2 feet below the surface. If ground
conditions make compliance with these requirements impracticable, installation
methods must prevent physical damage. It is not necessary to cover the part of
the container where there are manhole and other connections. Anchor or weight
containers when necessary to prevent floating.
(D) Underground containers must be on a firm
foundation (firm earth is OK) and surrounded with compacted earth or sand. The
container must have a corrosion resisting protective coating. This coating must
remain undamaged when placing the container into the ground.
(E) Containers with foundations (portable or
semi-portable tank containers with suitable steel "runners" or "skids" and
commonly known in the industry as "skid tanks") must comply with OAR
437-004-0800(4)(a)(A).
(F) There must be secure anchorage or
adequate pier height to prevent container flotation where high flood water
might occur.
(G) The distance
between underground containers of over 2,000 gallons capacity must be at least
5 feet.
(e) Protection
of appurtenances.
(A) Protect valves,
regulators, gages and other appurtenances against tampering and physical
damage. This also applies during transit of containers.
(B) All connections to underground containers
must be within a dome, housing, or manhole and with access by means of a
substantial cover.
(f)
Damage from vehicles. Protect ammonia systems from vehicle damage.
(4) Refrigerated storage systems.
(a) Container design.
(A) The design temperature must be the
minimum temperature to which the container will be refrigerated.
(B) Containers with a design pressure more
than 15 p.s.i.g. must comply with OAR
437-004-0800(3)(b),
and the materials must be from those in
API Standard 620,
Recommended Rules for Design and Construction of Large, Welded,
Low-Pressure Storage Tanks, Fourth Edition, 1970, Tables 2.02,
R2.2, R2.2(A), R2.2.1, or
R2.3.
(C) Containers with a design pressure of 15
p.s.i.g. and less must comply with the applicable requirements of API Standard
620 including its Appendix R.
(D) Use the Code as a guide to select
austenitic steels or non-ferrous materials to build containers for use at the
design temperature.
(E) The filling
density for refrigerated storage containers must be such that the container
will not be liquid full at a liquid temperature corresponding to the vapor
pressure at the start-to-discharge pressure setting of the safety-relief
valve.
(b) Installation.
(A) Containers must be on suitable
non-combustible foundations.
(B)
There must be adequate protection against flotation or other water damage where
high flood water might occur.
(C)
Containers for product storage at less than 32 degrees F. must have protection
from freezing and consequent frost heaving.
(c) Shutoff valves. When operating conditions
make it advisable, there must be a check valve on the fill connection and a
remotely operated shutoff valve on other connections below the maximum liquid
level.
(d) Safety relief devices.
(A) Set safety relief valves to
start-to-discharge at a pressure not more than the design pressure of the
container. The valves must prevent a maximum pressure in the container of more
than 120 percent of the design pressure. Relief valves for refrigerated storage
containers must be self-contained spring-loaded, weight-loaded, or
self-contained pilot-operated type.
(B) The total relieving capacity must be the
larger of:
(i) Possible refrigeration system
upset such as (1) cooling water failure, (2) power failure, (3) instrument air
or instrument failure, (4) mechanical failure of any equipment, (5) excessive
pumping rates.
(ii) Fire exposure
determined by Compressed Gas Association (CGA) S-1, Part 3, Safety Relief
Device Standards for Compressed Gas Storage Containers, 1959, except that "A"
must be the total exposed surface area in square feet up to 25 feet above grade
or to the equator of the storage container if it is a sphere, whichever is
greater. If the relieving capacity required for fire exposure is greater than
that required by OAR
437-004-0800(a),
the additional capacity may be provided by weak roof to shell seams in
containers operating at essentially atmospheric pressure and having an
inherently weak roof-to-shell seam. The weak roof-to-shell seam is not to
provide any of the capacity required in OAR
437-004-0800(a).
(C) If vent lines conduct the vapors from the
relief valve, the back pressure under full relieving conditions must not be
more than 50 percent of the start-to-discharge pressure for pressure balanced
valves or 10 percent of the start-to-discharge pressure for conventional
valves. The vent lines must prevent accumulation of liquid in the lines.
(D) The valve or valve
installation must provide weather protection.
(E) Atmospheric storage must have vacuum
breakers. Ammonia gas, nitrogen, methane, or other inert gases are acceptable
to provide a pad.
(e)
Protection of container appurtenances. Protect appurtenances against tampering
and physical damage.
(f)
Reinstallation of refrigerated storage containers. When reinstalling containers
that require field fabrication, reconstruct and reinspect them according to
their original construction requirements. Pressure retest the containers and if
rerating is necessary, it must comply with applicable requirements.
(g) Damage from vehicles. Protect containers
from damage by vehicles.
(h)
Refrigeration load and equipment.
(A) Compute
the total refrigeration load as the sum of the following:
(i) Load imposed by heat flow into the
container caused by the temperature differential between design ambient
temperature and storage temperature.
(ii) Load imposed by heat flow into the
container caused by maximum sun radiation.
(iii) Maximum load imposed by filling the
container with ammonia warmer than the design storage
temperature.
(B) A single
refrigeration system may serve more than one storage container.
(i) Compressors.
(A) There must be a minimum of two
compressors either of which must be large enough to handle the loads. Where
there are more than two compressors, there must be minimum standby equipment
equal to the largest normally operating equipment. Filling compressors are
acceptable as standby equipment for holding compressors.
(B) Compressors must be able to operate with
a suction pressure at least 10 percent below the minimum setting of the safety
valve(s) on the storage container and must withstand a suction pressure at
least equal to 120 percent of the design pressure of the container.
(j) Compressor drives.
(A) Each compressor must have its individual
driving unit.
(B) There must be an
emergency power source that can handle the loads unless facilities are
available to safely dispose of vented vapors while the refrigeration system is
not operating.
(k)
Automatic control equipment.
(A) The
refrigeration system must have suitable controls to govern the compressor
operation.
(B) There must be an
emergency alarm system to function in case the container pressure rises to the
maximum allowable operating pressure.
(C) An emergency alarm and shut-off must be
in the condenser system to respond to excess discharge pressure caused by
failure of the cooling medium.
(D)
All automatic controls must be prevent operation of alternate compressors
unless the controls will function with the alternate compressors.
(l) Separators for compressors. An
entrainment separator of suitable size and design pressure must be in the
compressor suction line of lubricated compression. The separator must have a
drain and gaging device.
(m)
Condensers. The condenser system may be air or water cooled or both. The
condenser must have minimum design pressure of at least 250 p.s.i.g. There must
be a way to purge noncondensibles either manually or automatically.
(n) Receiver and liquid drain. A receiver
must have a liquid-level control to discharge the liquid ammonia to storage.
The receiver must be able to operate at least 250 p.s.i.g. and have the
necessary connections, safety valves, and gaging device.
(o) Insulation. Insulated refrigerated
containers and pipelines must have covers of a material of suitable quality and
thickness for the temperatures. Weatherproofing must be flame
retardant.
(6) Tank motor
vehicles for the transportation of ammonia.
(a) This paragraph applies to containers and
equipment on tank motor vehicles including semitrailers and full trailers used
to transport ammonia. This paragraph does not apply to farm vehicles. For
requirements covering farm vehicles, refer to OAR
437-004-0800(8) and
(9). Paragraph (b) below applies to this
paragraph unless otherwise noted. Containers and pertinent equipment for tank
motor vehicles for the transportation of anhydrous ammonia, must also comply
with DOT requirements.
(b) Design
pressure and construction of containers.
(A)
The minimum design pressure for containers must comply with DOT
regulations.
(B) The shell or head
thickness of containers must be at least 3/16-inch.
(C) All container openings, except safety
relief valves, liquid-level gaging devices, and pressure gages, must have
labels that designate whether they communicate with liquid or vapor
space.
(c) Container
appurtenances.
(A) Protect appurtenances from
physical damage.
(B) All
connections to containers, except filling connections, safety relief devices,
and liquid-level and pressure gage connections, must have suitable automatic
excess flow valves, or may have quick-closing internal valves, that must remain
closed except during delivery operations. The control mechanism for such valves
may have a secondary control remote from the delivery connections and such
control mechanism must have a fusible section (melting point 208 degrees F. to
220 degrees F.) that permits the internal valve to close automatically in case
of fire.
(C) Filling connections
must have automatic back-pressure check valves, excess-flow valves, or
quick-closing internal valves, to prevent back-flow in case the filling
connection breaks. You do not need an automatic valve where the filling and
discharge connect to a common opening in the container shell and that opening
has a quick-closing internal valve as in OAR
437-004-0800(f)(3)(ii).
(D) All containers must be capable of spray
loading (filling in the vapor space) or with an approved vapor return valve of
adequate capacity.
(d)
Piping and fittings.
(A) Securely mount all
piping, tubing, and fittings and protect them from damage. Protect hoses while
the vehicle is moving.
(e) Safety relief devices.
(A) The discharge from safety relief valves
must vent upward away from the container and to the open air in such a manner
as to prevent any impingement of escaping gas. Use loose-fitting rain caps.
Size of discharge lines from safety valves must not be smaller than the nominal
size of the safety-relief valve outlet connection. Condensate that accumulates
in the discharge pipe must drain off.
(B) Any part of liquid ammonia piping that
may close at both ends must have a hydrostatic relief valve.
(f) Transfer of liquids.
(A) Determine the content of tank motor
vehicle containers by weight, by a suitable liquid-level gaging device, or
other approved methods. If using a liquid-level measurement, the container must
have a thermometer well. This volume when converted to weight must not be more
than the filling density specified by the DOT.
(B) Any pump, except a constant speed
centrifugal pump, must have a suitable pressure actuated bypass valve
permitting flow from discharge to suction when the discharge pressure rises
above a pre-determined point. Pump discharge must also have a spring-loaded
safety relief valve set at a pressure not more than 135 percent of the setting
of the bypass valve or more than 400 p.s.i.g., whichever is larger.
(C) Compressors must have manually operated
shutoff valves on both suction and discharge connections. Pressure gages of
bourdon-tube type must be on the suction and discharge of the compressor before
the shutoff valves. The compressor must not operate if either pressure gage is
removed or is inoperative. A spring-loaded, safety-relief valve capable of
discharging to atmosphere the full flow of gas from the compressor at a
pressure not more than 300 p.s.i.g. must be between the compressor discharge
and the discharge shutoff valve.
(D) Valve functions have clear and legible
identification by metal tags or nameplates permanently affixed to each
valve.
(g) Full trailers
and semitrailers.
(A) Securely attach full
trailers to the vehicle drawing them with suitable drawbars and a safety chain
(or chains) or safety cables.
(B)
Every full trailer or semitrailer must have reliable brakes that operate from
the driver's seat.
(C) Every full
trailer must have self-energizing brakes.
(D) Full trailers must follow substantially
in the path of their towing vehicle and will not whip or swerve dangerously
from side to side.
(E) Where using
a fifth wheel, securely fasten it to both units, and use a positive locking
mechanism that prevents separation of the two units except by manual
release.
(h) Protection
against collision. Each tank motor vehicle must have properly attached bumpers
or chassis extension that protects the tank, piping, valves, and fittings from
physical damage.
(i) Chock blocks.
There must be at least two chock blocks. Use these blocks to prevent rolling
during loading and unloading.
(j)
Portable tank containers (skid tanks). Where these tanks are for farm storage
they must comply with OAR
437-004-0800(4)(a)(A).
When portable tank containers substitute for cargo tanks and are permanently on
tank motor vehicles for the transportation of ammonia, they must comply with
the requirements of this paragraph.
(7) Systems on farm vehicles other than for
the application of ammonia.
(a) Application.
This paragraph applies to containers of 1,200 gallons capacity or less and
equipment on farm vehicles (implements of husbandry) not used to apply ammonia
to the soil. OAR
437-004-0800(4)
applies unless otherwise noted.
(b) Design pressure and classification of
containers.
(A) The minimum design pressure
for containers is 250 p.s.i.g.
(B)
Container shell or head thickness must be at least 3/16-inch.
(c) Mounting containers.
(A) A suitable "stop" or "stops" must be on
the vehicle or on the container so that the container does not be come loose
from its mounting.
(B) At one or
more places on each side of the container, a "hold down" device must anchor the
container to the vehicle.
(C) When
containers are on four-wheel trailers, the weight must be even over both
axles.
(d) Container
appurtenances.
(A) All containers must have a
fixed liquid-level gage.
(B) All
containers with a capacity more than 250 gallons must have a pressure gage with
a dial graduated from 0-400 p.s.i.
(C) The filling connection must have a
combination back-pressure check valve and excess-flow valve; one double or two
single back-pressure check valves; or a positive shutoff valve in conjunction
with either an internal back-pressure check valve or an internal excess flow
valve.
(D) All containers with a
capacity more than 250 gallons must be equipped for spray loading or have an
approved vapor return valve.
(E)
All vapor and liquid connections except safety-relief valves and those
specifically exempted in ANSI K61.1-1966, must have approved excess-flow valves
or quick-closing internal valves that, except during operating periods, must be
closed.
(F) Fittings must have
protection from damage by a metal box or cylinder with an open top fastened to
the container or by rigid guards welded to the container on both sides of the
fittings or by a metal dome. If there is a metal dome, the relief valve must
vent through the dome.
(G) If there
is a liquid withdrawal line in the bottom of a container, its connections,
including hose, must not be lower than the lowest horizontal edge of the
vehicle axle.
(H) Secure both ends
of the hose while in transit.
(e) Marking the container. The words,
"Caution - Ammonia" must be on each side and the rear end of the container in
letters at least 4 inches high or its markings must comply with DOT
regulations.
(f) Farm vehicles. All
vehicles must carry a container of at least 5 gallons of water for washing
ammonia from the skin.
(8) Systems on farm vehicles for the
application of ammonia.
(a) This applies to
systems using containers of 250 gallons capacity or less on farm vehicles
(implements of husbandry) used to apply ammonia to the soil. OAR
437-004-0800(4)
applies unless otherwise noted. Larger
containers must comply with ANSI K61.1-1966.
(b) Design pressure and classification of
containers.
(A) The minimum design pressure
for containers is 250 p.s.i.g.
(B)
The shell or head thickness of a container is less than 3/16-inch.
(c) Mounting of containers. All
containers and flow-control devices must have secure mountings.
(d) Container valves and accessories.
(A) Each container must have a fixed
liquid-level gage.
(B) The filling
connection must have a combination back-pressure check valve and an excess-flow
valve; one double or two single back-pressure check valves: or a positive
shut-off valve in conjunction with an internal back-pressure check valve or an
internal excess-flow valve.
(C) You
can fill the applicator tank by venting to open air if the bleeder valve
orifice is not more than 7/16-inch in diameter.
(D) Regulation equipment may connect directly
to the tank coupling or flange only with a flexible connection between the
regulating equipment and the rest of the liquid withdrawal system. Otherwise,
connect the regulating equipment flexibly to the container shutoff
valve.
(E) There need be no excess
flow valve in the liquid withdrawal line if the controlling orifice between the
contents of the container and the outlet of the shutoff valve is not more than
7/16-inch in diameter.