25 Pa. Code § 78.64 - Containment around oil tanks
(a) If
an owner or operator uses a tank with a capacity of at least 660 gallons or
tanks with a combined capacity of at least 1,320 gallons to contain oil
produced from a well, the owner or operator shall construct and maintain a dike
or other method of secondary containment which satisfies the requirements under
40 CFR 112 (relating to oil pollution prevention) around the tank or tanks
which will prevent the tank contents from entering waters of this
Commonwealth.
(b) The containment
area provided by the dikes or other method of secondary containment shall have
containment capacity sufficient to hold the volume of the largest single tank,
plus a reasonable allowance for precipitation based on local weather conditions
and facility operation.
(c) Prior to
drainage of accumulated precipitation from containment structures, the
containment area shall be inspected and accumulations of oil picked up and
returned to the tank or disposed of in accordance with approved
methods.
(d) After complying with
subsection (c), drainage of containment facilities is acceptable if:
(1) The accumulation in the containment
facility consists of only precipitation directly to the containment facility
and drainage will not cause a harmful discharge or result in a sheen.
(2) The containment drain valve is opened and
resealed, or other drainage procedure, as applicable, is conducted under
responsible supervision.