34 Pa. Code § 14.11 - Submission of application
Applications for the written approval required by § 14.3 (relating to scope of approval required) shall be made on a form to be supplied by the fire marshal and shall contain the following information:
(1) Detailed specifications as to the type of
equipment to be installed.
(2)
Detailed specifications and a sketch or plan as to the location of the
equipment or installation described in paragraph (1) shall contain the
following items and information:
(i) A sketch
in duplicate shall accompany the application for underground installation of
individual tanks having a capacity of 5,000 gallons or less.
(ii) A scaled drawing of 20 feet to the inch
covering a radius of not less than 150 feet shall be submitted in duplicate for
all underground installations of individual tanks having a capacity of more
than 5,000 gallons.
(iii) A scaled
drawing of 40 feet to the inch covering a radius of not less than 300 feet
shall be submitted in duplicate for all aboveground installations.
(iv) Plans and sketches required by this
section shall include the location of tanks, drawing-off devices, location of
attended self-service consoles and emergency controls, including main power
shut-off switch or switches, course of piping, existing tanks, if any, pump
house, unloading sidings, streets and roadways, the extent of property lines,
position, and description of buildings within the prescribed radii, the slope
or grade of the land together with any waterways, streams or other special
topographical features.
(3) The application shall be signed by the
applicant or an authorized representative.