34 Pa. Code § 14a.44 - Manner and limitations of storage
(a) Flammable or combustible liquids,
including stock for sale, shall not be stored near exits, stairways, or
corridors leading to the exits or stairways.
(b) The storage of flammable or combustible
liquids in closed containers shall comply with the following occupancy
provisions, except that the fire marshal may impose a quantity limitation or
require greater protection if he determines that an unusual hazard to life or
property is involved, or he may authorize an increase of the given amounts if
the type construction, fire protection provided, or other factors substantially
reduce the hazard:
(1) Dwellings and
residential buildings containing not more than two dwelling units and attached
and detached garages. Storage in excess of 5 gallons of class I liquid is
prohibited. Storage in excess of 20 gallons of class II or class III liquids
combined is prohibited. Flammable or combustible liquids shall be stored in
closed metal containers, safety cans, or approved nonmetallic containers. No
individual container shall exceed 5 gallons capacity. Flam- mable and
combustible liquids shall not be transferred or dispensed from containers to
fuel tanks, reservoir tanks, or other containers inside of buildings. This
section does not pertain to supply tanks connected by piping to oil burners or
power devices. See §
14a.161 (relating to general
provisions).
(2)
[Reserved].
(3) Hospitals, nursing
homes and related health care facilities. Inside storage, handling, use and
fire control of flammable or combustible liquids throughout this Commonwealth
shall be in accordance with 28 Pa. Code (relating to health and
safety).
Notes
This section cited in 34 Pa. Code § 14a.33 (relating to class II and class III liquids); 34 Pa. Code § 14a.41 (relating to scope); 34 Pa. Code § 14a.45 (relating to fire safety rules); 34 Pa. Code § 14a.141 (relating to scope and application); and 34 Pa. Code § 14a.151 (relating to scope and application).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.