34 Pa. Code § 39.125 - Guarding live parts in battery room
(a) The arrangement of cells and connections
shall be such that no two current-carrying parts between which a voltage
exceeding 150 exists, shall be closer than three feet, if the parts are so
exposed that persons are liable to make accidental contact with both at the
same time.
(b) No conductor above
150 volts to ground shall be placed in any passageway, unless guarded or
isolated by elevation.