(1)
(a) All community water systems which are
designated as a surface supply or groundwater under the direct influence of
surface water and classified as a filtration system and all iron removal plants
which use gravity filters must have an operator in attendance and responsible
for the treatment process when the plant is in operation. Gravity iron removal
plants and groundwater under the direct influence of surface water filtration
plants which have installed continuous monitoring equipment including equipment
for turbidity and chlorine residual with alarms and/or shutdown ability may
seek written approval from the Department to operate the treatment plant in an
automated mode without an operator in attendance. All iron removal plants with
pressure filters and using a groundwater source from an approved sand and
gravel formation will not be required to have an operator in attendance during
all periods of operation provided suitable protection, acceptable to the
Department, is provided.
(b)
Non-community water systems which are classified as a surface supply will be
required to have a full time operator in attendance unless certain continuous
monitoring equipment is installed.
(c) Pursuant to T.C.A. §
68-221-904,
all operators in direct responsible charge of a water supply system, including
the treatment plant and/or distribution system, must be certified by the
Department as competent to operate the water supply system.
(d) Because the proper operation and
maintenance of water systems is critical to a system's ability to provide safe
water to the public and to comply with these rules, all water supply systems
must comply with the provisions of Chapter 0400-49-01. A violation of those
rules is a violation of this rule as well.
(2)
(a) All
community water systems and those non-community water systems classified as a
surface source shall compile and maintain accurate daily operating records of
the water works system on forms prepared and furnished by the Department. The
daily operating records shall be submitted in a timely manner so they are
received by the Department no later than ten days after the end of the
reporting month. Any special reports, deemed necessary by the Department to
assure continuous satisfactory operation of the water system, shall be
submitted to the Department.
(b)
Water systems which desire to use their own forms to report the daily operating
results to the Department must have prior written approval of the form from the
Department.
(3) All
water quality tests, other than those listed in Rule
0400-45-01-.06
shall be made in accordance with the latest edition of "Standard Methods for
the Examination of Water and Wastewater" or alternate methods acceptable to the
Department. The schedule of laboratory tests followed in controlling the
operation of a waterworks system will vary with the character of the water;
therefore, all waterworks systems must have the equipment necessary to perform
all laboratory tests pertinent to the control of the plant or system operation,
and the equipment shall be maintained in good working order at all times.
Laboratory tests pertinent to proper operation shall be prescribed by the
Department for each community water system.
(4) Chlorine is the recommended disinfection
agent. Other agents will be considered by the Department provided they are
effective and testing procedures for their effectiveness are recognized in the
latest edition of "Standard Methods for the Examination of Water and
Wastewater". All community water systems, using ground water as a raw water
source and serving more than 50 connections or 150 persons shall continuously
chlorinate (unless other disinfection methods are approved) and shall maintain
a free chlorine residual in all parts of the distribution system in the amount
of not less than 0.2 mg/l. Public Water Systems using surface water shall
continuously chlorinate and maintain a free chlorine residual of 0.2 mg/l in
all parts of the distribution system. The residual disinfectant concentration
specified by this rule shall not be less than 0.2 mg/l in more than 5 percent
of the samples each month, for any two consecutive months the system serves
water to the public. All public water systems serving 50 or fewer connections
that do not disinfect shall install continuous disinfection if the system fails
to comply with the maximum contaminant level for coliform, experiences a
disease outbreak or is directed to install disinfection by the
department.
(5) All systems
submitting samples for microbiological examination to the State laboratory must
submit said sample in the bottle(s) provided by the State and return the
samples to the proper State laboratory in the shipping carton provided by the
State. The cost of postage for shipping the sample to the proper State
laboratory shall be paid by the supplier of water. All samples submitted for
microbiological examination must be collected and mailed to arrive at the
proper State laboratory not later than Thursday noon of any week. Thirty hours
is the limit allowed from the time of collection to the time of examination at
the proper state laboratory.
(6)
(a) Pursuant to T.C.A. §
68-221-711(6),
the installation, allowing the installation, or maintenance of any
cross-connection, auxiliary intake, or bypass is prohibited unless the source
and quality of water from the auxiliary supply, the method of connection, and
the use and operation of such cross-connection, auxiliary intake, or bypass has
been approved by the Department. The arrangement of sewer, soil, or other drain
lines or conduits carrying sewage or other wastes in such a manner that the
sewage or waste may find its way into any part of the public water system is
prohibited.
(b)
1. All community water systems must adopt an
ordinance or policy outlining the prohibitions in subparagraph (a) of this
paragraph and submit a copy of the executed ordinance or policy to the
Department for written approval. All community water systems shall develop a
written plan for a cross-connection control program to detect and eliminate or
protect the system from hazards associated with cross-connections. The written
plan must be approved by the Department.
2. After adoption and approval of the
cross-connection ordinance or policy and plan, each community water system must
establish an ongoing program to detect and eliminate or protect the system from
hazards associated with cross-connections. Records of the cross-connection
control program must be maintained by the supplier of water and shall include
such items as date of inspection, person contacted, recommendations, follow-up,
and testing results.
3.
Cross-connection plans and policies shall present information in conformance
with the "Cross-Connection Control Manual and Design Criteria for
Cross-Connection Control Plans, Ordinances and Policies" as published by the
Department.
4. Community water
systems shall ensure that cross-connections between the distribution system and
a consumer's plumbing are surveyed and/or inspected and determined not to exist
or contain a significant risk or are eliminated or controlled by the
installation of an approved backflow preventer commensurate with the degree of
hazard.
5. Non-community water
systems shall ensure that unprotected cross-connections are not allowed to
exist within the water system. The non-community water system shall conduct
periodic inspections of the water system and maintain a statement of inspection
completion to include acknowledgement of the hazards associated with
cross-connections.
(7) All community water systems shall prepare
and maintain an emergency operations plan in order to safeguard the water
supply and to alert the public of unsafe drinking water in the event of natural
or man-made disasters. Emergency operation plans shall be consistent with
guidelines established by the Department and shall be reviewed and approved in
writing by the Department. Systems shall include a drought management plan as a
part of the emergency operations plan. The emergency operations plan, including
the drought management portion, shall be reviewed, updated, and submitted to
the Department at least once every three years. The drought management plan
portions of the emergency operations shall be submitted for approval as
follows:
(a) Systems serving 3,000 or more
connections including consecutive systems: June 30, 2016.
(b) Systems serving more than 1,000
connections and less than 3,000 connections including consecutive systems: June
30, 2017.
(c) Systems serving 1,000
connections or less: June 30, 2018.
(8)
(a)
General-Public water systems, construction contractors, and engineers shall
follow and document sanitary practices used in inspecting, constructing or
repairing water lines, finished water storage facilities, water treatment
facilities, and wells. Public water systems, construction contractors, and
engineers shall follow the latest edition of the AWWA standards C-651, C-652,
C-653, C-654, or equivalent methods provided the method has been approved in
writing by the Department and is available during the inspection, construction,
maintenance, or repair activity. In lieu of following AWWA standards or
approved equivalent methods, public water systems, construction contractors,
and engineers may write their own disinfection standard operating procedures.
Disinfection standard operating procedures shall be approved in writing by the
Department and be available during the inspection, construction, maintenance,
or repair activity.
The documentation shall include disinfection
procedures used, bacteriological sample results, construction logs, and repair
logs and may include photographs where appropriate. All wells, pipes, tanks,
filters, filter media and other materials shall be properly disinfected prior
to being placed in service. Any disinfectant used to disinfect shall be NSF
approved or plain household bleach and used in a manner that assures sufficient
contact time and concentration to inactivate any pathogens present.
Bacteriological results including line repair records indicating adequacy of
disinfection shall be maintained on file by the public water system for five
years. Procedures to ensure that water containing excessive concentrations of
disinfectant is not supplied to the customers or discharged in such manner as
to harm the environment shall be implemented.
All materials used
for new or repaired water lines, storage facilities, water treatment
facilities, and wells will be inspected prior to use for any evidence of gross
contamination. Any contamination observed shall be removed and the materials
protected during installation.
(b) Bacteriological Sampling of New
Facilities-Bacteriological samples will be collected and analyzed to verify the
effectiveness of the disinfection practices prior to placing new facilities in
service. Bacteriological samples for finished water storage facilities, water
treatment facilities, and wells shall be collected as specified by AWWA
standards C-652, C-653, and C-654.
Adequacy of disinfection of new lines
shall be demonstrated by collecting two sets of microbiological samples 24
hours apart or collecting a single set of microbiological samples 48 hours or
longer after flushing the highly chlorinated water from the lines. In either
case microbiological samples in each set will be collected at approximately
2,500-foot intervals with samples near the beginning point, the end point, and
at the end of each branch line, unless written approval of alternate sampling
frequency and distance between sampling points has been obtained from the
Department. If the newly constructed facility yields positive bacterial
samples, the line shall be flushed, and re-sampled. If subsequent samples are
positive, the line shall be re-disinfected, flushed and sampled again.
(c) Bacteriological Sampling of
Existing Facilities
1. Finished water storage
facilities, water treatment facilities, and wells that have been compromised
and potential contamination is introduced during inspection or repair shall be
disinfected, flushed, and sampled as specified by AWWA standards C-652, C-653,
and C-654. Bacteriological samples shall be collected from a location
representing the water contained in the compromised facility. The repaired
facility may be returned to service prior to obtaining bacteriological
results.
2. Drinking water mains
where positive pressure has not been maintained during inspection or repair
shall be disinfected and flushed prior to being placed back in service.
Disinfection and flushing shall be in accordance with AWWA standard C-651 or
other method approved in writing by the Department. Bacteriological samples
shall be collected immediately after the repair is completed and from a
location representing the water contained in the repaired main. The repaired
main may be returned to service prior to obtaining bacteriological results. If
the repaired main has been placed back into service and yields positive
bacteriological samples, the main shall be flushed and re-sampled. One sample
is to be collected at the original positive site, one sample is to be collected
upstream of the repair and one sample is to be collected in the downstream area
of the repair. Sampling shall continue until the water is coliform
free.
3. If one-half or more of the
bacteriological samples collected from the repaired facility are total coliform
positive, the system shall notify the Department within 30 days that it has
reviewed its disinfection and sampling practices in an attempt to identify why
the positive samples occurred and revise its disinfection and sampling plans
accordingly.
4. If any public water
system collects a fecal coliform positive repeat sample or E-coli positive
repeat sample or a total coliform positive repeat sample following an initial
positive fecal coliform or E-coli sample collected from the repaired facility,
the system shall notify the Department within 24 hours and issue a Tier 1
public notice using the language specified in Appendix B of Rule
0400-45-01-.19.
(d) Inspectors, contractors,
operators, public water systems or engineers that fail to document and follow
adequate disinfection procedures, and fail to collect bacteriological samples
during repairs, inspections or maintenance activities that potentially would
compromise the microbial quality of the water shall issue a boil water advisory
to the customers served by that portion of the public water system prior to
returning the facility to service. The boil water advisory shall remain in
effect until satisfactory microbial tests results and written approval from the
Department are obtained.
(9) All community water systems shall be
operated and maintained to provide minimum positive pressure of twenty (20) psi
throughout the distribution system. No person shall install or maintain a water
service connection to any premises where a booster pump has been installed
unless such booster pump is equipped with a low pressure cut-off mechanism
designed to cut off the booster pump when the pressure on the suction side of
the pump drops to twenty (20) psi gauge.
(10) All community water systems having more
than 50 service connections shall establish and maintain an adequate flushing
program. The flushing program established shall help ensure that dead end and
low usage mains are flushed periodically, drinking water standards are met,
sediment and air removal and the free chlorine residual specified under
paragraph (4) of this rule is maintained. Records of each flushing are to be
maintained by the water system. These records shall include date, time,
location, persons responsible and length of flushing. In addition to the above
information, the free chlorine residual will have to be measured and recorded
on the end of dead end mains after being flushed.
(11) All community public water systems
serving more than 50 connections and which have their own source of water shall
be required to install, operate and maintain duplicate disinfection equipment.
Duplicate disinfection equipment means at least two chlorine cylinders
connected to at least two chlorinators. Each set of chlorine cylinders consists
of one or more cylinders which may be connected together by an automatic
switchover valve. The two sets of chlorine cylinders may tee in to a common
feed line leading to the chlorinators, but may not be connected together by an
automatic switchover valve. The two sets of chlorine cylinders must be weighed
independently and operated simultaneously. At least two chlorinators must be
operated at all times with each feeding a part of the required dosage. The
chlorinators may discharge to a common manifold piping network to allow
multiple injection points. Facilities may be exempt from simultaneously
operating duplicate disinfection equipment if the facility has a reliable
chlorine residual analyzer with an alarm notifying a manned control center
capable of immediately shutting down the treatment facility. Facilities, which
are staffed during the time water is treated, can use one set of chlorine
cylinders with the automatic switchover device provided the free chlorine
residual is checked at the facility every two hours. A reliable free chlorine
residual analyzer with an alarm system to a manned control center may be used
for unmanned facilities that desire to use one set of chlorine cylinders with
the automatic switchover device.
Community public water systems serving
more than 50 service connections which use a hypochlorinator shall be required
to have two solution pumps, two tanks for bleach solution and operate both
units at the same time. Noncommunity systems and community systems serving less
than 50 connections which use a hypochlorinator and show deficiencies in the
disinfection process shall also be required to have duplicate disinfection
units.
(12) All public
water systems which utilize a filtration system shall use the following bed
specifications and not exceed the following rates of filtration.
(a) Rapid Sand Filtration - 2.0 gallons per
minute per square foot for turbidity removal, 3.0 gallons per minute per square
foot for iron removal.
There must be 30 inches of sand media with an
effective size of 0.35 mm to 0.55 mm and a uniformity coefficient not greater
than 1.70
(b) High Rate
Filtration - 4.0 gallons per minute per square foot for turbidity removal, 4.0
gallons per minute per square foot for iron removal.
There must be 30
inches of dual media with 10 to 12 inches of sand and 18 to 20 inches of
anthracite. The sand shall have an effective size of 0.35 mm to 0.55 mm and a
uniformity coefficient not greater than 1.70. The anthracite shall have an
effective size of 0.8 mm to 1.2 mm with a uniformity coefficient not greater
than 1.85.
(c) Existing
water systems with rapid sand filters and approved for higher rates of
filtration by the Department will be allowed to continue at that rate provided
the drinking water standards are met. The water supplier must be able to
document that the Department approved the system for the higher rate.
(d) All mixed media filter beds will be at
least 30 inches in depth and approved by the Department.
(e) Filtration rates above 4.0 gallons per
minute per square foot will be considered on an individual basis. The
Department will take into account the raw water characteristics, the treatment
units, operational history, and operating personnel.
(13) All community water systems serving 50
connections or more shall install duplicate pumps for the raw water, finished
water, and distribution pumping stations. A water system will not be required
to have duplicate pumps in a distribution pumping station under the following
conditions: limited number of service connections, availability of replacement
pumps, maintaining adequate flows and pressures without the pumping station,
and for emergency use only. All community public water systems using ground
water supplies and having more than 50 service connections must have duplicate
wells and/or duplicate pumps in a spring supply unless fed by gravity
flow.
(14) All community water
systems serving 50 connections or more are required to have 24 hours of
distribution storage based on the average daily demand for the past twelve
months. Distribution storage must be located so that the instantaneous demand
can be met in all areas at any time.
(a)
Systems which purchase water for resale may utilize the storage of the supplier
provided the supplier has adequate distribution storage. Water systems that
have large ground storage tanks will be given credit for distribution storage
provided auxiliary power is available to pump water to the distribution
system.
(b) Systems which have more
than three (3) treatment facilities, have more than one source of water, and
which have special power arrangements so that it is unlikely that all units
would be down at the same time are not required to have distribution storage
provided the peak demand can be met.
(c) Water systems which have an average daily
demand of 10 million gallons or more are not required to have 24 hours of
distribution storage provided the system has adopted a contingency plan for
emergencies that has been approved by the Department. The contingency plan must
demonstrate the water system is able to provide residential service to all
customers for a 24 hour period during any emergency involving the shut down of
the treatment facility.
(d) Public
water systems which utilize wells and provide only disinfection, pH adjustment,
corrosion inhibitor and/or fluoridation as treatment, may use the capacity of
the wells and the plant as part of the distribution storage under the following
conditions:
1. The existing distribution
storage tank(s) are adequate to meet the peak demands on the system,
2. The well(s), disinfection equipment and
other pumping facilities needed to supply water to the distribution storage
tank are equipped with an auxiliary power source with automatic controls,
and
3. The well field capacity is
determined by removing the largest well from consideration.
(e) Public water systems may take
into account private distribution storage facilities in the following manner:
1. Private distribution storage may be
counted as water system storage provided the private storage tank floats on the
water utility's system and the water used serves both the private and utility
system demand.
2. The water utility
may reduce the amount of needed distribution storage by subtracting the average
daily volume of any water user that has its own storage tank. This can be done
provided the private storage tank is used on a daily basis.
3. Private distribution storage tanks used
strictly for fire protection by the private owner cannot be in the water
systems distribution storage capacity.
(15) All community water systems serving 50
or more service connections must have and maintain up-to-date maps of the
distribution system. These maps must show the locations of the water mains,
sizes of mains, valves, blow-offs or flush hydrants, air-release valves, and
fire hydrants. One up-to-date copy of the overall system distribution map(s) is
to be submitted to the Division of Water Resources every five years.
(16) All vents on wells, springs, storage
tanks, overflows and clearwells shall be properly screened. All overflows on
springs and tanks shall be screened and protected.
(17) All buildings and equipment used in and
for the production and distribution of water (to include chemical and other
storage buildings) must be well maintained and be reliable and fit for the
purpose for which they are used. This includes, but is not limited to:
(a) When a water treatment plant is not
producing water and an operator is not in attendance, plant entrances must be
locked.
(b) Equipment such as
chemical feeders, pumps, turbidimeters, pumpage meters, alarm systems, and air
tanks shall be maintained and in good working condition. Pumps, tanks, hoses,
and other equipment used by system personnel shall be disinfected and dedicated
to its use if it comes into contact with water that may be consumed by
humans.
(c) Duplicate or backup
equipment shall be available as necessary to maintain the production of water
meeting drinking water standards. Backup equipment or alternate treatment means
shall be available for feeding all chemicals critical for adequate water
treatment.
(18) All
community water systems planning to or having installed hydrants must protect
the distribution system from contamination. All water mains designed for fire
protection must be six inches or larger and be able to provide 500 gallons per
minute with 20 pounds per square inch residual pressure. Fire hydrants shall
not be installed on water mains less than six inches in diameter or on water
mains that cannot produce 500 gpm at 20 psi residual pressure unless the tops
are painted red. Out of service hydrants shall have tops painted black or
covered with a black shroud or tape.
Existing Class C hydrants (hydrants
unable to deliver a flow of 500 gallons per minute at a residual pressure of 20
pounds per square inch (psi) shall have their tops painted red by January 1,
2008.
The water system must provide notification by certified mail
at least once every five years beginning January 1, 2008, to each fire
department that may have reason to utilize the hydrants, that fire hydrants
with tops painted red (Class C hydrants) cannot be connected directly to a
pumper fire truck. Fire Departments may be allowed to fill the booster tanks on
any fire apparatus from an available hydrant by using the water system's
available pressure only (fire pumps shall not be engaged during refill
operations from a Class C hydrant).
(19) Before any new or modified community
water treatment facility can be placed in service, it must be inspected and
approved in writing by the Department.
(20) Each public water system adjusting the
fluoride content to the finished water must monitor for fluoride quarterly
using a certified laboratory and the calculation of the fluoride level will be
by running annual average. If the quarterly analysis of a water sample from a
public water system by a certified laboratory confirms that the level of
fluoride in the sample exceeds 1.5 mg/L, the public water system must provide
notification to its customers of the exceedance in the same manner as
prescribed in paragraph (8) of Rule
0400-45-01-.19.
The water system must begin monthly fluoride monitoring using a certified
laboratory for analysis. Once the monthly analyses confirm that the fluoride
level is less than 1.5 mg/L for three (3) consecutive months, the public water
system may resume quarterly monitoring for fluoride.
The
recommended level of fluoridation in the finished water is 0.7 mg/l. Any public
water system which determines to initiate or permanently cease fluoridation
treatment of its water supply shall notify its customers, the local
environmental field office within the Department of Environment and
Conversation, and the Commissioner of the Department of Health in the manner
and within the timeframe as specified by T.C.A. §
68-221-708(c).
(21) New or modified turbidity removal
facilities may not be placed into operation until the facility and the operator
have been approved by the Department for the turbidity analysis.
(22) All pipe, pipe or plumbing fitting or
fixture, solder, or flux which is used in the installation or repair of any
public water system shall be lead free. The term "lead free" shall have the
meaning given it in T.C.A. §
68-221-703.
(23) All dead end water mains and all low
points in water mains shall be equipped with a blow-off or other suitable
flushing mechanism capable of producing velocities adequate to flush the
main.
(24) All community water
systems must establish and maintain a file for customer complaints. This file
shall contain the name of the person with the complaint, date, nature of
complaint, date of investigation and results or actions taken to correct any
problems.
(25) The Department may,
upon written notice, require confirmation of any sampling results and also may
require sampling and analysis for any contaminant when deemed necessary by the
Department to protect the public health or welfare.
(26) Those public water systems required to
monitor for turbidity and chlorine residual must have the laboratory approved
by the Department before the results of these analyses can be accepted for
compliance purposes.
(27) By
December 30, 1991, or 18 months after the determination that a ground water
system is influenced by surface water, all public water systems classified as a
ground water system impacted by surface water shall utilize treatment
techniques which achieve:
(a) At least 99.9
percent (3 log) removal and/or inactivation of Giardia lamblia cysts between a
point where the raw water is not subject to recontamination by surface water
runoff and a point downstream before or at the first customer.
(b) At least 99.99 percent (4 log) removal
and/or inactivation of viruses between a point where the raw water is not
subject to recontamination by surface water runoff and a point downstream
before or at the first customer.
(28) All public water systems using surface
water shall provide disinfection to control the biological quality of the
water. Due consideration shall be given to the contact time of the disinfectant
in the water with relation to pH, ammonia, taste producing substances,
temperature, presence and type of pathogens, and trihalomethane formation
potential. All disinfection basins must be designed to prevent water
short-circuiting the system. The disinfectant will be applied in the manner
needed to provide adequate contact time.
(29) All community water systems using ground
water as the raw water source serving water to more than 50 connections or 150
people will apply the disinfectant in the manner needed for adequate contact
time. Contact time for ground water systems shall not be less than 15 minutes
prior to the first customer.
(30)
Any surface supplied public water system or ground water systems under the
direct influence of surface water required to filter shall employ filtration in
combination with disinfection that will achieve 99.9% (3 log) and 99.99% (4
log) inactivation of Giardia lamblia and viruses respectively between a point
where the raw water is not subject to recontamination by surface water runoff
and a point downstream before or at the first customer. For the purposes of
determining removal or inactivation efficiencies for Giardia lamblia and
viruses table 0400-45-01-.17(30) 1. and 0400-45-01-.17(30) 2. shall apply. The
free residual disinfectant concentration in the water entering the distribution
system cannot be less than 0.2 mg/l for more than four hours.
TABLE
0400-45-01-.17(30) 1.
Assumed Log Removals by Filtration Method
and Required Levels of Disinfection
Treatment
|
Assumed Log
Removal
|
Required Minimum Level of
Disinfection
|
Giardia
|
Viruses
|
Giardia
|
Viruses
|
Conventional filtration
|
2.5
|
2.0
|
0.5
|
2.0
|
Direct
filtration
|
2.0
|
1.0
|
1.0
|
3.0
|
Slow Sand filtration
|
2.0
|
2.0
|
1.0
|
2.0
|
Diatomaceous Earth filtration
|
2.0
|
1.0
|
1.0
|
3.0
|
TABLE
0400-45-01-.17(30) 2.
CT Values for Achieving 1-Log Inactivation
of 1
Giardia Cysts
|
pH
|
Temperature
|
0.5oC
|
5oC
|
10oC
|
15oC
|
Free
Chlorine 2,3
|
6
|
55
|
39
|
29
|
19
|
7
|
79
|
55
|
41
|
26
|
8
|
115
|
81
|
61
|
41
|
9
|
167
|
118
|
88
|
59
|
Ozone
|
0.97
|
0.63
|
0.48
|
0.32
|
Chlorine
dioxide
|
1270
|
735
|
615
|
500
|
1 Values to achieve 0.5 log
inactivation are one half those shown in the table.
2 CT values are for 2.0 mg/l free
chlorine.
3 CT values for other
concentrations of free chlorine may be taken from Appendix E of the guidance
manual for Compliance with the "Filtration and Disinfection Requirements For
Public Water Systems Using Surface Water Sources," October, 1989, Edition,
Science and Technology Branch Criteria and Standards Division, Office of
Drinking Water, USEPA, Washington, D.C.
(31) Each public water system must certify
annually in writing to the Department that when acrylamide and epichlorohydrin
are used in drinking water systems, the combination (or product) of dose and
monomer level does not exceed the levels specified as follows:
Acrylamide=0.05% dosed at 1 ppm (or equivalent) Epichlorohydrin=0.01%
dosed at 20 ppm (or equivalent)
Public water systems can rely on
manufacturer's or third parties' certification for complying with this
requirement.
(32) New
service taps on existing mains that must be uncovered to make the tap, shall be
flushed and the free chlorine residual measured and recorded prior to
connecting the service lines. These records shall be retained until the next
sanitary survey or for three years.
(33) All public water systems shall properly
maintain their distribution system finished water storage tanks and clearwells.
Each community water system shall establish and maintain a maintenance file on
each of its distribution storage tanks and clearwells. These maintenance files
must be available for inspection by Department personnel. These files must
include records of all routine water storage tank and clearwell inspections by
system personnel, any reports of detailed professional inspections of the water
storage facilities by contractor personnel, dates and details of routine tank
cleanings and surface flushings, and dates and details of all tank and
clearwell maintenance activities. The tank and clearwell inspection records
shall include dates of the inspections; the sanitary, coating and structural
conditions of the water storage facility; and all recommendations for needed
maintenance activities. Community water systems shall have a professional
inspection performed and a written report produced on each of their
distribution storage tanks and clearwells at least once every five years.
Non-community water systems shall have a professional inspection performed and
written report produced on each of their atmospheric pressure and distribution
storage tanks and clearwells no less frequently than every five years. Records
of these inspections shall be available to the Department personnel for
inspection. Persons conducting underwater inspections of distribution system
finished water storage tanks and clearwells shall comply with AWWA standard
C-652-11 or later versions of the standard.
(34) Paints and coatings for the interior of
potable water storage facilities must be acceptable to the Department. Paints
and coatings accepted by the Environmental Protection Agency (EPA) and/or the
National Sanitation Foundation (NSF) for potable water contact are generally
acceptable to the Department. Paint systems for steel tanks shall be consistent
with AWWA Standard D102-78. Factory coated bolted steel tanks shall be in
accordance with AWWA D103-87. Wire-wound circular prestressed concrete tanks
shall be in accordance with AWWA D110-86.
(35) By January 1, 1996, public water systems
using surface water and ground water systems under the direct influence of
surface water that filter shall have rewash capability. Such systems shall
perform a rewash cycle, or filter to waste each time a filter is backwashed.
The rewash cycle shall be conducted in a way and manner necessary to prevent
the introduction of contaminants such as pathogens and turbidity trapped in the
filter into the clear well or distribution system.
Existing filter plants
may be approved to operate without rewash (filter-to-waste provisions) if
existing operational and backwash practices prevent water of unacceptable
quality from entering the clearwell or distribution system. To operate without
rewash the water system must demonstrate to the Department that filtered water
turbidity after backwashing is reliably and consistently below 0.5 NTU
immediately after backwashing each filter. Approval to operate without rewash
must be approved in writing and approval must be renewed if any modifications
are made to the operation or design of the plant. Each filter that operates
without rewash must have a continuous recording turbidimeter and retain the
records for a period of five years.
(36) By January 1, 1995, all chemicals,
additives, coatings or other materials used in the treatment, conditioning and
conveyance of drinking water must have been approved by the National Sanitation
Foundation (NSF) or American National Standards Institute (ANSI) certified
parties as meeting NSF product standard 60 and 61. Until 1995, products used
for treatment, conditioning and conveyance of drinking water shall have been
listed as approved by the US EPA or NSF.
(37) Any new Community Water System or
Non-Transient Non-Community Water System commencing operation after September
30, 1999 shall have a "Capacity Development Plan" and be a "viable water
system."
(38) Public Water Systems
identified as not complying or potentially not complying with the requirements
of the Safe Drinking Water Act and in accordance with the priorities
established in the Department's Capacity Development Strategy shall prepare a
"Capacity Development Plan" and demonstrate viability.
(39) Public water systems are not permitted
to construct uncovered finished water reservoirs after the effective date of
this subparagraph.
(40) Benchtop
and continuous turbidimeters used to determine compliance with limits set forth
in this rule chapter must be calibrated at least every three months with
primary standards and documented. Documentation shall be maintained for a
period not less than five years. Primary standards are Formazin, AMCO clear,
Stablcal, or alternatives approved in writing by the Department. Dilute
Formazin solutions are unstable and must be prepared on the day of calibration.
Manufacturers' recommendations on calibration procedure must be
followed.
(41) Verifications for
benchtop turbidimeters are comparisons to approved reference materials.
Verifications for continuous turbidimeters are comparisons to approved
reference materials or comparisons to a properly calibrated benchtop
turbidimeter. Secondary reference materials are assigned a value immediately
after acceptable primary calibration has been completed. Acceptable
verifications for turbidity measurements greater than 0.5 NTU must agree within
±10% from the reading assigned to the reference material after primary
calibration. Acceptable verifications for measurements 0.5 NTU or less must be
within ±0.05 NTU or less from the reading assigned to the reference
material after primary calibration. When comparisons are made from a continuous
turbidimeter to a benchtop turbidimeter, the continuous measurement must be
within ±10% of the benchtop reading for measurements above 0.5 NTU and
±0.05 NTU for reading 0.5 NTU or less. When acceptable verifications are
not achieved the instrument must be re-calibrated with primary standards
according to paragraph (40) of this rule. Approved reference materials for
benchtop and continuous turbidimeters are primary standards and materials
suggested by the manufacturer such as sealed sample cells filled with metal
oxide particles in a polymer gel and turbid glass tubes. All other reference
materials for turbidimeter verifications must be approved in writing by the
Department. Verifications for turbidimeters must be performed according to the
following:
(a) Verification of benchtop
turbidimeters must be performed daily and documented. Verifications must
include a sample in the expected working range of the instrument or as close to
the working range as possible. Documentation must include: assigned reference
material value after calibration, recorded daily reading for all reference
standards, instrument identification, and date.
(b) Combined filter effluent turbidimeters as
required by part (5)(c)1. of Rule
0400-45-01-.31
must be verified daily and documented. When reference material is utilized
documentation must include: instrument identification, date, assigned reference
material value after calibration, and daily value for reference material. When
comparisons to benchtop turbidimeters are utilized documentation must include:
instrument identification, date, continuous turbidimeter value, and benchtop
turbidimeter value.
(c) Individual
filter turbidimeters as required by part (5)(c)4. of Rule
0400-45-01-.31
must be verified weekly.