(1) General
Requirements
(a) Applicability
1. The requirements of this rule constitute
primary drinking water regulations for lead and copper. Unless otherwise
indicated each of the provisions of this rule apply to community and
non-transient, non-community water systems.
2. Reserved
(b) Scope. These regulations establish a
treatment technique that includes requirements for corrosion control treatment,
source water treatment, lead service line replacement, and public education.
These actions are triggered, in some cases, by lead and copper action levels
measured in samples collected at consumers' tap.
(c) Lead and Copper action levels.
1. The lead action level is exceeded if the
concentration of lead in more than 10 percent of tap water samples collected
during any monitoring period is greater than 0.015 mg/l (i.e., if the "90th
percentile" lead level is greater than 0.015 mg/l).
2. The copper action level is exceeded if the
concentration of copper in more than 10 percent of tap water samples collected
during any monitoring period is greater than 1.3 mg/l (i.e., if the "90th
percentile" copper level is greater than 1.3 mg/l).
3. The 90th percentile lead and copper levels
shall be computed as follows:
(i) The results
of all lead or copper samples taken during a monitoring period shall be placed
in ascending order from the sample with the lowest concentration to the sample
with the highest concentration. Each sampling result shall be assigned a
number, ascending by single integers beginning with the number 1 for the sample
with the lowest contaminant level. The number assigned to the sample with the
highest contaminant level shall be equal to the total number of samples
taken.
(ii) The number of samples
taken during the monitoring period shall be multiplied by 0.9.
(iii) The contaminant concentration in the
numbered sample yielded by the calculation in subpart (ii) of this part is the
90th percentile contaminant level.
(iv) For water systems serving fewer than 100
people that collect 5 samples per monitoring period, the 90th percentile is
computed by taking the average of the highest and second highest
concentrations.
(v) For a public
water system that has been allowed by the Department to collect fewer than five
samples in accordance with subparagraph (7)(c) of this rule, the sample result
with the highest concentration is considered the 90th percentile
value.
(d)
Corrosion control treatment requirements.
1.
All water systems shall install and operate optimal corrosion control treatment
as defined in Rule
0400-45-01-.04.
2. Any water system that complies with the
applicable corrosion control treatment requirements set forth in paragraphs (2)
and (3) of this rule shall be deemed in compliance with the treatment
requirement contained in part 1. of this subparagraph.
(e) Source water treatment requirements. Any
system exceeding the lead or copper action level shall implement all applicable
source water treatment requirements set forth in paragraph (4) of this
rule.
(f) Lead service line
replacement. Any system exceeding the lead action level after implementation of
applicable corrosion control and source water treatment requirements shall
complete the lead service line replacement requirements set forth in paragraph
(5) of this rule.
(g) Public
education requirements. Pursuant to paragraph (6) of this rule, all water
systems must provide a consumer notice of lead tap water monitoring results to
persons served at the sites (taps) that are tested. Any system exceeding the
lead action level shall implement the public education requirements set forth
in paragraph (6) of this rule.
(h)
Monitoring and analytical requirements. Tap water monitoring for lead and
copper, monitoring for water quality parameters, source water monitoring for
lead and copper, and analysis of the monitoring results shall be completed in
compliance with paragraphs (7), (8), (9) and (10) of this rule.
(i) Reporting Requirements. Systems shall
report to the Department any information required by the treatment provisions
of this rule.
(j) Recordkeeping
requirements. Systems shall maintain records in accordance with paragraph (12)
of this rule.
(k) Violation of
primary drinking water regulations. Failure to comply with the applicable
requirements of this rule, including requirements established by the Department
pursuant to these provisions, shall constitute a violation of the primary
drinking water regulations for lead and/or copper.
(2) Applicability of corrosion control
treatment steps to small, medium and large water systems.
(a) Systems shall complete the applicable
corrosion control treatment requirements described in paragraph (3) of this
rule by the deadlines established in this paragraph.
1. A large system (serving > 50,000
persons) shall complete the corrosion control treatment steps specified in
subparagraph (d) of this paragraph, unless it is deemed to have optimized
corrosion control under part (b)2. or 3. of this paragraph.
2. A small system (serving [LESS THAN EQAUL
TO] 3300 persons) and a medium-size system (serving > 3,300 and [LESS THAN
EQAUL TO] 50,000 persons) shall complete the corrosion control treatment steps
of specified in subparagraph (e) of this paragraph, unless it is deemed to have
optimized corrosion control under part (b)1., 2. or 3. of this
paragraph.
(b) A system
is deemed to have optimized corrosion control and is not required to complete
the applicable corrosion control treatment steps identified if the system
satisfies one of the criteria specified in parts 1. through 3. of this
subparagraph. Any such system deemed to have optimized corrosion control under
this paragraph, and which has treatment in place, shall continue to operate and
maintain optimal corrosion control treatment and meet any requirements that the
Department determines appropriate to ensure optimal corrosion control treatment
is maintained.
1. A small or medium-size water
system is deemed to have optimized corrosion control if the system meets the
lead and copper action levels during each of two consecutive six-month
monitoring periods conducted in accordance with paragraph (7) of this
rule.
2. Any water system may be
deemed by the Department to have optimized corrosion control treatment if the
system demonstrates to the satisfaction of the Department that it has conducted
activities equivalent to the corrosion control steps applicable to such system
under this paragraph. If the Department makes this determination, it shall
provide the system with written notice explaining the basis for its decision
and shall specify the water quality control parameters representing optimal
corrosion control in accordance with subparagraph (3)(f) of this rule. Water
systems deemed to have optimized corrosion control under this paragraph shall
operate in compliance with the Department-designated optimal water quality
control parameters in accordance with subparagraph (3)(g) of this rule and
continue to conduct lead and copper tap and water quality parameter sampling in
accordance with part (7)(d)3. and subparagraph (8)(d) of this rule,
respectively. A system shall provide the Department with the following
information in order to support a determination under this paragraph:
(i) The results of all test samples collected
for each of the water quality parameters in part (3)(c)3. of this
rule.
(ii) A report explaining the
test methods used by the water system to evaluate the corrosion control
treatments listed in part (3)(c)1. of this rule. The results of all tests
conducted, and the basis for the system's selection of optimal corrosion
control treatment;
(iii) A report
explaining how corrosion control has been installed and how it is being
maintained to insure minimal lead and copper concentrations at consumers'
taps;
(iv) The results of tap water
samples collected in accordance with paragraph (7) of this rule at least once
every six months for one year after corrosion control has been
installed.
3. Any water
system is deemed to have optimized corrosion control if it submits results of
tap water monitoring conducted in accordance with paragraph (7) of this rule
and source water monitoring conducted in accordance with paragraph (9) of this
rule that demonstrates for two consecutive 6-month monitoring periods that the
difference between the 90th percentile tap water lead level computed under part
(1)(c)3. of this rule, and the highest source water lead concentration is less
than the Practical Quantitation Level for lead specified in subpart
(10)(a)1.(ii) of this rule.
(i) Those systems
whose highest source water lead level is below the Method Detection Limit may
also be deemed to have optimized corrosion control under this paragraph if the
90th percentile tap water lead level is less than or equal to the Practical
Quantitation Level for lead for two consecutive 6-month monitoring
periods.
(ii) Any water system
deemed to have optimized corrosion control in accordance with this paragraph
shall continue monitoring for lead and copper at the tap no less frequently
than once every three calendar years using the reduced number of sites
specified in subparagraph (7)(c) of this rule and collecting the samples at
times and locations specified in subpart (7)(d)4.(iv) of this rule. Any such
system that has not conducted a round of monitoring pursuant to subparagraph
(7)(d) of this rule since September 30, 1997, shall complete a round of
monitoring pursuant to this paragraph no later than September 30,
2000.
(iii) Any water system deemed
to have optimized corrosion control pursuant to this paragraph shall notify the
Department in writing pursuant to subparagraph (11)(a) of this rule of any
upcoming long term change in treatment or addition of a new source as described
in this rule. The Department must review and approve the addition of a new
source or long term change in water treatment before it is implemented by the
water systems. The Department may require any such system to conduct additional
monitoring or to take other action the Department deems appropriate to ensure
that such systems maintain minimal levels of corrosion in the distribution
system.
(iv) As of July 12, 2001, a
system is not deemed to have optimized corrosion control under this paragraph,
and shall implement corrosion control treatment pursuant to subpart (v) of this
part unless it meets the copper action level.
(v) Any system triggered into corrosion
control because it is no longer deemed to have optimized corrosion control
under this paragraph shall implement corrosion control treatment in accordance
with the deadlines in subparagraph (e) of this paragraph. Any such large system
shall adhere to the schedule specified in that paragraph for medium-size
systems, with the time periods for completing each step being triggered by the
date the system is no longer deemed to have optimized corrosion control under
this paragraph.
(c) Any small or medium-size water system
that is required to complete the corrosion control steps due to its exceedance
of the lead or copper action level may cease completing the treatment steps
whenever the system meets both action levels during each of two consecutive
monitoring periods conducted pursuant to paragraph (7) of this rule and submits
the results to the Department. If any such water system thereafter exceeds the
lead or copper action level during any monitoring period, the system shall
recommence completion of the applicable treatment steps, beginning with the
first treatment step which was not previously completed in its entirety. The
Department may require a system to repeat treatment steps previously completed
by the system where the Department determines that this is necessary to
implement properly the treatment requirements of this paragraph. The Department
shall notify the system in writing of such a determination and explain the
basis for its decision that includes but is limited to the information required
under part (b)2. of this paragraph. The requirement for any small or
medium-size system to implement corrosion control treatment steps in accordance
with subparagraph (e) of this paragraph (including systems deemed to have
optimized corrosion control under part (b)1. of this paragraph) is triggered
whenever any small or medium-size system exceeds the lead or copper action
level.
(d) Treatment steps and
deadlines for large systems. Except as provided in parts (b)2. and 3. of this
paragraph, large systems shall complete the following corrosion control
treatment steps [described in the referenced portions of paragraphs (3), (7)
and (8) of this rule] by the indicated dates.
1. Step 1: The system shall conduct initial
monitoring [part (7)(d)1. and subparagraph (8)(b) of this rule], during two
consecutive six-month monitoring periods by January 1, 1993.
2. Step 2: The system shall complete
corrosion control studies [subparagraph (3)(c) of this rule] by July 1,
1994.
3. Step 3: The Department
shall designate optimal corrosion control treatment [subparagraph (3)(d) of
this rule] by January 1, 1995.
4.
Step 4: The system shall install optimal corrosion control treatment
[subparagraph (3)(e) of this rule] by January 1, 1997.
5. Step 5: The system shall complete
follow-up sampling by [part (7)(d)2. and subparagraph (8)(c) of this rule] by
January 1, 1998.
6. Step 6: The
Department shall review installation of treatment and designate optimal water
quality control parameters [subparagraph (3)(f) of this rule] by July 1,
1998.
7. Step 7: The system shall
continue thereafter to operate in compliance with the Department-specified
optimal water quality control parameters [subparagraph (3)(g) of this rule] and
continue to conduct tap sampling [part (7)(d)3. and subparagraph (8)(d) of this
rule].
(e) Treatment
steps and deadlines for small and medium-sized systems. Except as provided in
subparagraph (b) of this paragraph, small and medium-size systems shall
complete the following corrosion control treatment steps by the indicated time
periods.
1. Step 1: The system shall conduct
initial tap sampling until the system either exceeds the lead or copper action
level or becomes eligible for reduced monitoring under part (7)(d)4. of this
rule. A system exceeding the lead or copper action level shall recommend
optimal corrosion control treatment [subparagraph (3)(a) of this rule] within
six months after the end of the monitoring period during which it exceeds one
of the action levels; and
2. Step
2: Within 12 months after the end of the monitoring period during which a
system exceeds the lead or copper action level, the Department may require the
system to perform corrosion control studies [subparagraph (3)(b) of this rule].
If the Department does not require the system to perform such studies, the
Department shall specify optimal corrosion treatment pursuant to subparagraph
(3)(d) of this rule within the following timeframes:
(i) for medium-size systems, within 18 months
after the end of the monitoring period during which such system exceeds the
lead or copper action level; and
(ii) for small systems, within 24 months
after the end of the monitoring period during which such system exceeds the
lead or copper action level.
3. Step 3: If the Department requires a
system to perform corrosion control studies under step 2, the system shall
complete the studies within 18 months after the Department requires that such
studies be conducted.
4. Step 4: If
the system has performed corrosion control studies under step 2, the Department
shall designate optimal corrosion treatment within 6 months after completion of
step 3.
5. Step 5: The system shall
install optimal corrosion control treatment within 24 months after the
Department designates such treatment.
6. Step 6: The system shall complete
follow-up sampling within 36 months after the Department designates optimal
corrosion control treatment.
7.
Step 7: The Department shall review the system's installation of treatment and
designate optimal water quality control parameters within 6 months after
completion of step 6.
8. Step 8:
The system shall continue thereafter to operate in compliance with the
Department-designated optimal water quality control parameters and continue to
conduct tap sampling.
(3) Description of corrosion control
treatment requirements. Each system shall complete the corrosion control
treatment requirement described in this paragraph, which are applicable to such
a system as described in paragraph (2) of this rule.
(a) System recommendation regarding corrosion
control treatment. Based upon the results of lead and copper tap monitoring and
water quality parameter monitoring, small and medium-size water systems
exceeding the lead or copper action level shall recommend installation of one
or more of the corrosion control treatments listed in part (c)1. of this
paragraph, which the system believes constitutes optimal corrosion control for
that system. The Department may require the system to conduct additional water
quality parameter monitoring in accordance with subparagraph (8)(b) of this
rule to assist the Department in reviewing the system's
recommendation.
(b) The Department
may require any small or medium-size system that exceeds the lead or copper
action level to perform corrosion control studies under subparagraph (c) of
this paragraph to identify optimal corrosion control treatment for the
system.
(c) Performance of
corrosion control studies.
1. Any public water
system performing corrosion control studies shall evaluate the effectiveness of
each of the following treatments, and, if appropriate, combinations of the
following treatments to identify the optimal corrosion control treatment for
that system:
(i) Alkalinity and pH
adjustment;
(ii) Calcium hardness
adjustment; and
(iii) The addition
of a phosphate or silicate based corrosion inhibitor at a concentration
sufficient to maintain an effective residual concentration in all test tap
samples.
2. The water
system shall evaluate each of the corrosion control treatments using either
pipe rig/loop tests, metal coupon tests, partial-system tests, or analyses
based on documented analogous treatments approved by the Department with other
systems of similar size, water chemistry and distribution system
configuration.
3. The water system
shall measure the following water quality parameters in any tests conducted
under this paragraph before and after evaluating the corrosion control
treatments listed in part 1. of this subparagraph:
(i) Lead;
(ii) Copper;
(iii) pH;
(iv) Alkalinity;
(v) Calcium;
(vi) Conductivity
(vii) Orthophosphate (when an inhibitor
containing a phosphate compound is used);
(viii) Silicate (when an inhibitor containing
a silicate compound is used);
(ix)
Water temperature; and
(x) Other
parameters identified by the Department.
4. The water system shall identify all
chemical or physical constraints that limit or prohibit the use of a particular
corrosion control treatment and document such constraints with at least one of
the following:
(i) Data and documentation
showing that a particular corrosion control treatment has adversely affected
other water treatment processes when used by another water system with
comparable water quality characteristics; and/or
(ii) Data documentation demonstrating that
the water system has previously attempted to evaluate a particular corrosion
control treatment and has found that the treatment is ineffective or adversely
affects other water quality treatment processes.
5. The water system shall evaluate the effect
of the chemicals used for corrosion control treatment on other water quality
treatment processes.
6. On the
basis of an analysis of the data generated during each evaluation, the water
system shall recommend to the Department, in writing, the treatment option that
the corrosion control studies indicate constitutes optimal corrosion control
treatment for that system. The water system shall provide a rationale for its
recommendation along with all supporting documentation specified in parts 1.
through 5. of this subparagraph.
(d) Department designation of optimal
corrosion control treatment.
1. Based upon
consideration of available information including, where applicable, studies
performed under subparagraph (c) of this paragraph and a system's recommended
treatment alternative, the Department shall either approve the corrosion
control treatment option recommended by the system, or designate alternative
corrosion control treatment(s) from among those listed in part (c)1 of this
paragraph. When designating optimal treatment the Department may consider the
effects that additional corrosion control treatment will have on water quality
parameters and on other water quality treatment processes.
2. The Department shall notify the system of
its decision on optimal corrosion control treatment in writing and explain the
basis for this determination. If the Department requests additional information
to aid its review, the water system shall provide the information.
(e) Installation of optimal
corrosion control. Each system shall properly install and operate throughout
its distribution system the optimal corrosion control treatment designated by
the Department under subparagraph (d) of this paragraph.
(f) Department review of treatment and
specification of optimal water quality control parameters. The Department shall
evaluate the results of all lead and copper tap samples and water quality
parameter samples submitted by the water system and determine whether the
system has properly installed and operated the optimal corrosion control
treatment designated by the Department in subparagraph (d) of this paragraph.
Upon reviewing the results of tap water and water quality parameter monitoring
by the system, both before and after the system installs optimal corrosion
control treatment, the Department shall designate at least the following:
1. A minimum value or a range of values for
pH measured at each entry point to the distribution system;
2. A minimum pH value, measured in all tap
samples. Such value shall be equal to or greater than 7.0, unless the
Department determines that meeting a pH level of 7.0 is not technologically
feasible or is not necessary for the system to optimize corrosion
control;
3. If a corrosion
inhibitor is used, a minimum concentration or a range of concentrations for the
inhibitor, measured at each entry point to the distribution system and in all
tap samples, that the Department determines is necessary to form a passivating
film on the interior walls of the pipes of the distribution system;
4. If alkalinity is adjusted as part of
optimal corrosion control treatment, a minimum concentration or a range of
concentrations for alkalinity, measured at each entry point to the distribution
system and in all tap samples;
5.
If calcium carbonate stabilization is used as part of corrosion control, a
minimum concentration or a range of concentrations for calcium, measured in all
tap samples.
The values for the applicable water quality control
parameters listed in this subparagraph shall be those that the Department
determines to reflect optimal corrosion control treatment for the system. The
Department may designate values for additional water quality control parameters
determined by the Department to reflect optimal corrosion control for the
system. The Department shall notify the system in writing of these
determinations and explain the basis for its decisions.
(g) Continued operation and
monitoring. All systems optimizing corrosion control shall continue to operate
and maintain optimal corrosion control treatment, including maintaining water
quality parameters at or above minimum values or within ranges designated by
the Department under subparagraph (f) of this paragraph for all samples
collected under subparagraphs (8)(d) through (f) of this rule. Compliance with
the requirements of this paragraph shall be determined every six months, as
specified by subparagraph (8)(d) of this rule. A water system is out of
compliance with the requirements of this paragraph for a six-month period if it
has excursions for any Department-specified parameter on more than nine days
during the period. An excursion occurs whenever the daily value for one or more
of the water quality parameters measured at a sampling location is below the
minimum value or outside the range designated by the Department. Daily values
are calculated as follows (the Department has the discretion to delete results
of obvious sampling errors from this calculation):
1. On days when more than one measurement for
the water quality parameter is collected at the sampling location, the daily
value shall be the average of all results collected during the day regardless
of whether they are collected through continuous monitoring, grab sampling, or
a combination of both. If EPA has approved an alternative formula under
40 CFR
142.16 in the Department's application for a
program revision submitted pursuant to
40 CFR
142.12, the Department's formula shall be
used to aggregate multiple measurements taken at a sampling point for the water
quality parameter in lieu of the formula in this subparagraph.
2. On days when only one measurement for the
water quality parameter is collected at the sampling location, the daily value
shall be the result of that measurement.
3. On days when no measurement is collected
for the water quality parameter at the sampling location, the daily value shall
be the daily value calculated on the most recent day on which the water quality
parameter was measured at the sample site.
(h) Modification of Department treatment
decisions. Upon its own initiative or in response to a request by a water
system, the Department may modify its determination of the optimal corrosion
control treatment under subparagraph (d) of this paragraph or optimal water
quality control parameters under subparagraph (f) of this paragraph. A request
for modification by a system or other interested party shall be in writing,
explain why the modification is appropriate, and provide supporting
documentation. The Department may modify its determination where it concludes
that such change is necessary to ensure that the system continues to optimize
corrosion control treatment. A revised determination shall be made in writing,
set forth the new treatment requirements, explain the basis for the
Department's decision, and provide an implementation schedule for completing
the treatment modifications.
(4) Source water treatment requirements.
Systems shall complete the applicable source water monitoring and treatment
requirements by the following deadlines.
(a)
Deadlines for Completing Source Water Treatment Steps:
1. Step 1: A system exceeding the lead or
copper action level shall complete lead and copper source water monitoring and
make a treatment recommendation to the Department not later than 180 days after
the end of the monitoring period during which the lead or copper action level
was exceeded.
2. Step 2: The
Department shall make a determination regarding source water treatment within 6
months after submission of monitoring results under step 1.
3. Step 3: If the Department requires
installation of source water treatment the system shall install the treatment
within 24 months after completion of step 2.
4. Step 4: The system shall complete
follow-up tap water monitoring and source water monitoring within 36 months
after completion of step 2.
5. Step
5: The Department shall review the system's installation and operation of
source water treatment and specify maximum permissible source water levels
within 6 months after completion of step 4.
6. Step 6: The system shall continue
thereafter to operate in compliance with the Department-specified maximum
permissible lead and copper source water levels and continue source water
monitoring in accordance with part (9)(d)4. of this rule.
(b) Description of Source Water Treatment
Requirements:
1. System treatment
recommendation. Any system which exceeds the lead or copper action level shall
recommend in writing to the Department the installation and operation of one of
the source water treatments listed in part 2. of this subparagraph. A system
may recommend that no treatment be installed based upon a demonstration that
source water treatment is not necessary to minimize lead and copper levels at
users' taps.
2. Department
determination regarding source water treatment. The Department shall complete
an evaluation of the results of all source water samples submitted by the water
system to determine whether source water treatment is necessary to minimize
lead or copper levels in water delivered to users' taps. If the Department
determines, based on source water levels of lead and copper, that treatment is
needed, the Department shall either require installation and operation of the
source water treatment recommended by the system (if any) or require the
installation and operation of another source water treatment from among the
following: ion exchange, reverse osmosis, lime softening or
coagulation/filtration. If the Department requests additional information to
aid in its review, the water system shall provide the information by the date
specified by the Department in its request. The Department shall notify the
system in writing of its determination and set forth the basis for its
decision.
3. Installation of source
water treatment. Each system shall properly install and operate the source
water treatment designated by the Department under part 2. of this
subparagraph.
4. Department review
of source water treatment and specification of maximum permissible source water
levels. The Department shall review the source water samples taken by the water
system both before and after the system installs source water treatment, and
determine whether the system has properly installed and operated the source
water treatment designated by the Department. Based upon its review, the
Department shall designate the maximum permissible lead and copper
concentrations for finished water entering the distribution system. Such levels
shall reflect the contaminant removal capability of the treatment properly
operated and maintained. The Department shall notify the system in writing and
explain the basis for its decision.
5. Continued operation and maintenance. Each
water system shall maintain lead and copper levels below the maximum
permissible concentrations designated by the Department at each sampling point
monitored. The system is out of compliance if the level of lead or copper at
any sampling is greater than the maximum permissible concentration designated
by the Department.
6. Modification
of Department treatment decisions. Upon its own initiative or in response to a
request by a water system, the Department may modify its determination of the
source water treatment under part 2. of this subparagraph, or maximum
permissible lead and copper concentrations for finished water entering the
distribution system under part 4. of this subparagraph. A request for
modification by a system shall be in writing, explain why the modification is
appropriate, and provide supporting documentation. The Department may modify
its determination where it concludes that such change is necessary to ensure
that the system continues to minimize lead and copper concentrations in source
water. A revised determination shall be made in writing, set forth the new
treatment requirements, explain the basis for the Department's decision, and
provide an implementation schedule for completing the treatment
modifications.
7. Treatment
decisions by EPA in lieu of the Department. The EPA Regional Administrator may
review treatment determinations made by a Department under parts 2., 4., or 6.
of this subparagraph and issue Federal treatment determinations consistent with
the requirements of those parts where the Administrator finds that:
(i) The Department has failed to issue a
treatment determination by the applicable deadlines contained in subparagraph
(a) of this paragraph,
(ii) The
Department has abused its discretion in a substantial number of cases or in
cases affecting a substantial population, or
(iii) The technical aspects of a Department's
determination would be indefensible in an expected Federal enforcement action
taken against a system.
(5) Lead service line replacement
requirements.
(a) Systems that fail to meet
the lead action level in tap samples, after installing corrosion control and/or
source water treatment, shall replace lead service lines in accordance with the
requirements of this paragraph. If a system is in violation of the rules or Act
for failure to install source water or corrosion control treatment, the
Department may require the system to commence lead service line replacement
under this paragraph after the date by which the system was required to conduct
monitoring under part (7)(d)2. of this rule has passed.
(b) A water system shall replace annually at
least 7 percent of the initial number of lead service lines in its distribution
system. The initial number of lead service lines is the number of lead lines in
place at the time the replacement program begins. The system shall identify the
initial number of lead service lines in its distribution system, including an
identification of the portion(s) owned by the system, based on a materials
evaluation, including the evaluation required under subparagraph (7)(a) of this
rule and relevant legal authorities (e.g., contracts, local ordinances)
regarding the portion owned by the system. The first year of lead service line
replacement shall begin on the first day following the end of the monitoring
period in which the action level was exceeded in subparagraph (a) of this
paragraph.
1. If monitoring is required
annually or less frequently, the end of the monitoring period is September 30
of the calendar year in which the sampling occurs. If the Department has
established an alternate monitoring period, then the end of the monitoring
period will be the last day of that period.
2. Any water system resuming a lead service
line replacement program after the cessation of its lead service line
replacement program as allowed by subparagraph (f) of this paragraph shall
update its inventory of lead service lines to include those sites that were
previously determined not to require replacement through the sampling provision
under subparagraph (c) of this paragraph. The system will then divide the
updated number of remaining lead service lines by the number of remaining years
in the program to determine the number of lines that must be replaced per year
(7 percent lead service line replacement is based on a 15-year replacement
program, so, for example, systems resuming lead service line replacement after
previously conducting two years of replacement would divide the updated
inventory by 13). For those systems that have completed a 15-year lead service
line replacement program, the Department will determine a schedule for
replacing or retesting lines that were previously tested out under the
replacement program when the system re-exceeds the action level.
(c) A system is not required to
replace an individual lead service line if the lead concentration in all
service line samples from that line, taken pursuant to part (7)(b)3 of this
rule, is less than or equal to 0.015 mg/l.
(d) A water system shall replace that portion
of the lead service line that it owns. In cases where the system does not own
the entire lead service line, the system shall notify the owner of the line, or
the owner's authorized agent, that the system will replace the portion of the
service line that it owns and shall offer to replace the owner's portion of the
line. A system is not required to bear the cost of replacing the
privately-owned portion of the line, nor is it required to replace the
privately-owned portion where the owner chooses not to pay the cost of
replacing the privately-owned portion of the line, or where replacing the
privately-owned portion would be precluded by State, local or common law. A
water system that does not replace the entire length of the service line also
shall complete the following tasks.
1. At
least 45 days prior to commencing with the partial replacement of a lead
service line, the water system shall provide notice to the resident(s) of all
buildings served by the line explaining that they may experience a temporary
increase of lead levels in their drinking water, along with guidance on
measures consumers can take to minimize their exposure to lead. The Department
may allow the water system to provide notice under the previous sentence less
than 45 days prior to commencing partial lead service line replacement where
such replacement is in conjunction with emergency repairs. In addition, the
water system shall inform the resident(s) served by the line that the system
will, at the system's expense, collect a sample from each partially-replaced
lead service line that is representative of the water in the service line for
analysis of lead content, as prescribed under part (7)(b)3. of this rule,
within 72 hours after the completion of the partial replacement of the service
line. The system shall collect the sample and report the results of the
analysis to the owner and the resident(s) served by the line within three
business days of receiving the results. Mailed notices post- marked within
three business days of receiving the results shall be considered "on
time."
2. The water system shall
provide the information required by part 1. of this subparagraph to the
residents of individual dwellings by mail or by other methods approved by the
Department. In instances where multi-family dwellings are served by the line,
the water system shall have the option to post the information at a conspicuous
location.
(e) The
Department shall require a system to replace lead service lines on a shorter
schedule than that required by this paragraph, taking into account the number
of lead service lines in the system, where such shorter replacement schedule is
feasible. The Department shall make this determination in writing and notify
the system of its finding within 6 months after the system is triggered into
lead service line replacement based on monitoring referenced in subparagraph
(a) of this paragraph.
(f) Any
system may cease replacing lead service lines whenever first draw samples
collected pursuant to part (7)(b)2. of this rule meets the lead action level
during each of two consecutive monitoring periods and the system submits the
results to the Department. If the first draw samples in any such water system
thereafter exceeds the lead action level, the system shall recommence replacing
lead service lines, pursuant to subparagraph (b) in this paragraph;
and
(g) To demonstrate compliance
with subparagraphs (a) through (d) of this paragraph, a system shall report to
the Department the information specified in subparagraph (11)(e) of this
rule.
(6) Public
education and supplemental monitoring requirements.
All water systems
must deliver a consumer notice of lead tap water monitoring results to persons
served by the water system at sites that are tested, as specified in
subparagraph (e) of this paragraph. A water system that exceeds the lead action
level based on tap water samples collected in accordance with paragraph (7) of
this rule shall deliver to its customers the public education materials
contained in subparagraph (a) of this paragraph in accordance with the
requirements of subparagraph (c) of this paragraph. Water systems that exceed
the lead action level must sample the tap water of any customer who requests it
in accordance with subparagraph (d) of this paragraph.
(a) Content of written public education
materials.
1. Community water systems and
Non-transient non-community water systems. Water systems must include the
following elements in printed materials (e.g., brochures and pamphlets) in the
same order as listed below. In addition, language in subparts (i), (ii) and
(vi) of this part must be included in the materials, exactly as written, except
for the text in brackets in these subparts for which the water system must
include system-specific information. Any additional information presented by a
water system must be consistent with the information in this part and be in
plain language that can be understood by the general public. Water systems must
submit all written public education materials to the Department prior to
delivery. The Department may require the system to obtain approval of the
content of written public materials prior to delivery.
(i) Important Information About Lead in Your
Drinking Water. [Insert Name of Water System] found elevated levels of lead in
drinking water in some homes/buildings. Lead can cause serious health problems,
especially for pregnant women and young children. Please read this information
closely to see what you can do to reduce lead in your drinking water.
(ii) Health effects of lead. Lead can cause
serious health problems if too much enters your body from drinking water or
other sources. It can cause damage to the brain and kidneys, and can interfere
with the production of red blood cells that carry oxygen to all parts of your
body. The greatest risk of lead exposure is to infants, young children, and
pregnant women. Scientists have linked the effects of lead on the brain with
lowered IQ in children. Adults with kidney problems and high blood pressure can
be affected by low levels of lead more than healthy adults. Lead is stored in
the bones, and it can be released later in life. During pregnancy, the child
receives lead from the mother's bones, which may affect brain
development.
(iii) Sources of Lead
(I) Explain what lead is.
(II) Explain possible sources of lead in
drinking water and how lead enters drinking water. Include information on
home/building plumbing materials and service lines that may contain
lead.
(III) Discuss other important
sources of lead exposure in addition to drinking water (e.g., paint).
(iv) Discuss the steps the
consumer can take to reduce their exposure to lead in drinking water.
(I) Encourage running the water to flush out
the lead.
(II) Explain concerns
with using hot water from the tap and specifically caution against the use of
hot water for preparing baby formula.
(III) Explain that boiling water does not
reduce lead levels.
(IV) Discuss
other options consumers can take to reduce their exposure to lead in drinking
water, such as alternative sources or treatment of drinking water.
(V) Suggest that parents have their child's
blood tested for lead. The following is a list of some Department approved
laboratories in your area that you can call to have your water tested for lead
(Insert names and phones numbers of at least two laboratories).
(v) The steps described above will
reduce the lead concentrations in your drinking water. However, if a water test
indicates that the drinking water coming from your tap contains lead
concentrations in excess of 15 ppb after flushing, or after we have completed
our actions to minimize lead levels, then you may want to take the following
additional measures:
(I) Purchase or lease a
home treatment device. Home treatment devices are limited in that each unit
treats only the water that flows from the faucet to which it is connected, and
all of the devices require periodic maintenance and replacement. Devices such
as reverse osmosis systems or distillers can effectively remove lead from your
drinking water. Some activated carbon filters may reduce lead levels at the
tap, however all lead reduction claims should be investigated. Be sure to check
the actual performance of a specific home treatment device before and after
installing the unit.
(II) Purchase
bottled water for drinking and cooking.
(vi) You can consult a variety of sources for
additional information. Your family doctor or pediatrician can perform a blood
test for lead and provide you with information about the health effects of
lead. State and local government agencies that can be contacted include:
(I) (insert the name of city or county
department of public utilities) at (insert phone number) can provide you with
information about your community's water supply, and a list of local
laboratories that have been certified by EPA for testing water
quality;
(II) (insert the name of
the city or county department that issues building permits (at insert telephone
number) can provide you with information about building permit records that
should contain the name of plumbing contractors that plumbed your home;
and
(III) (insert the name of the
State Department of Public Health) at (insert phone number) or the (insert the
name of the city or county health department) at (insert phone number) can
provide you with information about the health effects of lead and how you can
have your child's blood tested.
(vii) The following is a list of some
Department approved laboratories in your area that you can call to have your
water tested for lead (Insert names and phones numbers of at least two
laboratories).
(viii) Explain why
there are elevated levels of lead in the system's drinking water (if known) and
what the water system is doing to reduce the lead levels in homes/buildings in
this area.
(ix) For more
information call us at [Insert Your Number] [(If Applicable), or visit our Web
site at [Insert Your Web Site Here]]. For more information on reducing lead
exposure around your home/building and the health effects of lead, visit EPA's
Web site at
http://www.epa.gov/lead or contact your
health care provider.
2.
Community water systems. In addition to including the elements specified in
part (a)1 of this paragraph, community water systems must:
(i) Tell consumers how to get their water
tested.
(ii) Discuss lead in
plumbing components and the difference between low lead and lead
free.
(b)
Reserved
(c) Delivery of a public
education materials.
1. For public water
systems serving a large proportion of non-English speaking consumers, as
determined by the Department, the public education materials must contain
information in the appropriate language(s) regarding the importance of the
notice or contain a telephone number or address where persons served may
contact the water system to obtain a translated copy of the public education
materials or to request assistance in the appropriate language.
2. A community water system that exceeds the
lead action level on the basis of tap water samples collected in accordance
with paragraph (7) of this rule, and that is not already conducting public
education tasks under this subparagraph, must conduct the public education
tasks under this subparagraph within 60 days after the end of the monitoring
period in which the exceedance occurred:
(i)
Deliver printed materials meeting the content requirements of subparagraph (a)
of this paragraph to all bill paying customers.
(ii) Contact of customers most at risk.
(I) Contact customers who are most at risk by
delivering education materials that meet the content requirements of
subparagraph (a) of this paragraph to local public health agencies even if they
are not located within the water system's service area, along with an
informational notice that encourages distribution to all the organization's
potentially affected customers or community water system's users. The water
system must contact the local public health agencies directly by phone or in
person. The local public health agencies may provide a specific list of
additional community based organizations serving target populations, which may
include organizations outside the service area of the water system. If such
lists are provided, systems must deliver education materials that meet the
content requirements of subparagraph (a) of this paragraph to all organizations
on the provided lists.
(II) Contact
customers who are most at risk by delivering materials that meet the content
requirements of subparagraph (a) of this paragraph to the following
organizations listed in subitems I. through VI. of this item that are located
within the water system's service area, along with an informational notice that
encourages distribution to all the organization's potentially affected
customers or community water system's users:
I. Public and private schools or school
boards.
II. Women, Infants and
Children (WIC) and Head Start programs.
III. Public and private hospitals and medical
clinics.
IV.
Pediatricians.
V. Family planning
clinics.
VI. Local welfare
agencies.
(III) Make a
good faith effort to locate the following organizations within the service area
and deliver materials that meet the content requirements of subparagraph (a) of
this paragraph to them, along with an informational notice that encourages
distribution to all potentially affected customers or users. The good faith
effort to contact at-risk customers may include requesting a specific contact
list of these organizations from the local public health agencies, even if the
agencies are not located within the water system's service area:
I. Licensed childcare centers
II. Public and private preschools.
III. Obstetricians-Gynecologists and
Midwives.
(iii) No less often than quarterly, provide
information on or in each water bill as long as the system exceeds the action
level for lead. The message on the water bill must include the following
statement exactly as written except for the text in brackets for which the
water system must include system-specific information: [Insert Name of Water
System] found high levels of lead in drinking water in some homes. Lead can
cause serious health problems. For more information please call [Insert Name of
Water System] [or visit (Insert Your Web Site Here)]. The message or delivery
mechanism can be modified in consultation with the Department; specifically,
the Department may allow a separate mailing of public education materials to
customers if the water system cannot place the information on water
bills.
(iv) Post material meeting
the content requirements of subparagraph (a) of this paragraph on the water
system's Web site if the system serves a population greater than
100,000.
(v) Submit a press release
to newspaper, television and radio stations.
(vi) In addition to subparts (i) through (v)
of this part, systems must implement at least three activities from one or more
categories listed below. The educational content and selection of these
activities must be determined in consultation with the Department.
(I) Public Service Announcements.
(II) Paid advertisements.
(III) Public Area Informational
Displays.
(IV) E-mails to
customers.
(V) Public
Meetings.
(VI) Household
Deliveries.
(VII) Targeted
Individual Customer Contact.
(VIII)
Direct material distribution to all multi-family homes and
institutions.
(IX) Other methods
approved by the Department.
(vii) For systems that are required to
conduct monitoring annually or less frequently, the end of the monitoring
period is September 30 of the calendar year in which the sampling occurs, or,
if the Department has established an alternate monitoring period, the last day
of that period.
3. As
long as a community water system exceeds the action level, it must repeat the
activities pursuant to part 2. of this subparagraph as described in subparts
(i) through (iv) of this part.
(i) A community
water system shall repeat the tasks contained in subparts 2.(i), (ii) and (vi)
of this subparagraph every 12 months.
(ii) A community water system shall repeat
tasks contained in subpart 2(iii) of this subparagraph with each billing
cycle.
(iii) A community water
system serving a population greater than 100,000 shall post and retain material
on a publicly accessible Web site pursuant to subpart 2.(iv) of this
subparagraph.
(iv) The community
water system shall repeat the task in subpart 2.(v) of this subparagraph twice
every 12 months on a schedule agreed upon with the Department. The Department
can allow activities in part 2. of this subparagraph to extend beyond the
60-day requirement if needed for implementation purposes on a case-by-case
basis; however, this extension must be approved in writing by the Department in
advance of the 60-day deadline.
4. Within 60 days after the end of the
monitoring period in which the exceedance occurred (unless it already is
repeating public education tasks pursuant to part 5. of this subparagraph), a
non-transient noncommunity water system shall deliver the public education
materials specified by subparagraph (a) of this paragraph as follows:
(i) Post informational posters on lead in
drinking water in a public place or common area in each of the buildings served
by the system; and
(ii) Distribute
informational pamphlets and/or brochures on lead in drinking water to each
person served by the non-transient non-community water system. The Department
may allow the system to utilize electronic transmission in lieu of or combined
with printed materials as long as it achieves at least the same
coverage.
(iii) For systems that
are required to conduct monitoring annually or less frequently, the end of the
monitoring period is September 30 of the calendar year in which the sampling
occurs, or, if the Department has established an alternate monitoring period,
the last day of that period.
5. A non-transient non-community water system
shall repeat the tasks contained in part 4 of this subparagraph at least once
during each calendar year in which the system exceeds the lead action level.
The Department can allow activities in part 4 of this subparagraph to extend
beyond the 60-day requirement if needed for implementation purposes on a
case-by-case basis; however, this extension must be approved in writing by the
Department in advance of the 60-day deadline.
6. A water system may discontinue delivery of
public education materials if the system has met the lead action level during
the most recent six-month monitoring period conducted pursuant to paragraph (7)
of this rule. The system shall recommence public education in accordance with
this paragraph if it subsequently exceeds the lead action level during any
monitoring period.
7. A community
water system may apply to the Department, in writing, (unless the Department
has waived the requirement for prior Department approval) to use only the text
specified in part (a)1. of this paragraph in lieu of the text in parts (a)1.
and (a)2. of this paragraph and to perform the tasks listed in parts 4. and 5.
of this subparagraph in lieu of the tasks in parts 2. and 3. of this
subparagraph if:
(i) The system is a facility,
such as a prison or a hospital, where the population served is not capable of
or is prevented from making improvements to plumbing or installing point of use
treatment devices; and
(ii) The
system provides water as part of the cost of services provided and does not
separately charge for water consumption.
8. A community water system serving 3,300 or
fewer people may limit certain aspects of their public education programs as
follows:
(i) With respect to the requirements
of subpart 2.(vi) of this subparagraph, a system serving 3,300 or fewer must
implement at least one of the activities listed in that subpart.
(ii) With respect to the requirements of
subpart 2.(ii) of this subparagraph, a system serving 3,300 or fewer people may
limit the distribution of the public education materials required under that
subparagraph to facilities and organizations served by the system that are most
likely to be visited regularly by pregnant women and children.
(iii) With respect to the requirements of
subpart 2.(v) of this subparagraph, the Department may waive this requirement
for systems serving 3,300 or fewer persons as long as system distributes
notices to every household served by the system.
(d) Supplemental monitoring and
notification of results.
A water system that fails to meet the lead
action level on the basis of tap samples collected in accordance with paragraph
(7) of this rule shall offer to sample the tap water of any customer who
requests it. The system is not required to pay for collecting or analyzing the
sample, nor is the system required to collect and analyze the sample
itself.
(e) Notification of
results.
1. Reporting requirement. All water
systems must provide a notice of the individual tap results from lead tap water
monitoring carried out under the requirements of paragraph (7) of this rule to
the persons served by the water system at the specific sampling site from which
the sample was taken (e.g., the occupants of the residence where the tap was
tested).
2. Timing of notification.
A water system must provide the consumer notice as soon as practical, but no
later than 30 days after the system learns of the tap monitoring
results.
3. Content. The consumer
notice must include the results of lead tap water monitoring for the tap that
was tested, an explanation of the health effects of lead, list steps consumers
can take to reduce exposure to lead in drinking water and contact information
for the water utility. The notice must also provide the maximum contaminant
level goal and the action level for lead and the definitions for these two
terms from Rule
0400-45-01-.35.
4. Delivery. The consumer notice must be
provided to persons served at the tap that was tested, either by mail or by
another method approved by the Department. For example, upon approval by the
Department, a non-transient non-community water system could post the results
on a bulletin board in the facility to allow users to review the information.
The system must provide the notice to customers at sample taps tested,
including consumers who do not receive water bills.
(7) Monitoring requirements for
lead and copper in tap water.
(a) Sample site
location.
1. By the applicable date for
commencement of monitoring under part (d)1. of this paragraph, each water
system shall identify a pool of sampling sites that meets the requirements of
this paragraph, and which is sufficiently large to ensure that the water system
can collect the number of lead and copper tap samples required in subparagraph
(c) of this paragraph. All sites from which first draw samples are collected
shall be selected from this pool of sampling sites. Sampling sites may not
include faucets that have point-of-use or point-of-entry treatment devices
designed to remove inorganic contaminants.
2. A public water system shall review at
least the information on lead, copper, and galvanized steel under paragraph (1)
of Rule
0400-45-01-.21
when conducting a materials evaluation. When an evaluation of the information
collected pursuant to paragraph (1) of Rule
0400-45-01-.21
is insufficient to locate the requisite number of lead and copper sampling
sites that meet the targeting criteria in subparagraph (a) of this paragraph,
the water system shall review at least the sources of information listed below
in order to identify a sufficient number of sampling sites. In addition, the
system shall seek to collect such information in the course of its normal
operations (e.g., checking service line materials when reading water meters or
performing maintenance activities):
(i) All
plumbing codes, permits, and records in the files of the building department(s)
which indicate the plumbing materials that are installed within publicly and
privately owned structures connected to the distribution system;
(ii) All inspections and records of the
distribution system that indicate the material composition of the service
connections that connect a structure to the distribution system; and
(iii) All existing water quality information,
which includes the results of all prior analyses of the system or individual
structures connected to the system, indicating locations that may be
particularly susceptible to high lead or copper concentrations.
3. Community water systems shall
use tier 1 sampling sites for monitoring for lead and copper action level
determination. Tier 1 sampling sites for a community water system shall consist
of single family structures that:
(i) Contain
copper pipes with lead solder installed after 1982 or contain lead pipes;
and/or
(ii) Are served by a lead
service line. When multiple-family residences comprise at least 20 percent of
the structures served by a water system, the system may include these types of
structure in its sampling pool.
4. Any community water system with
insufficient tier 1 sampling sites shall use "tier 2 sampling sites", which
consists of buildings, including multiple-family residences that:
(i) Contain copper pipes with lead solder
installed after 1982 or contain lead pipes; and/or
(ii) Are served by a lead service
line.
5. Any community
water system with insufficient tier 1 and tier 2 sampling sites shall complete
its sampling pool with "tier 3 sampling sites", consisting of single family
structures that contain copper pipes with lead solder installed before 1983. A
community water system with insufficient tier 1, tier 2, and tier 3 sampling
sites shall complete its sampling pool with representative sites throughout the
distribution system. For the purpose of this paragraph, a representative site
is a site in which the plumbing materials used at that site would be commonly
found at other sites served by the water system.
6. Non-transient non-community water systems
shall use tier 1 sampling sites for lead and copper. The sampling sites
selected for a non-transient non-community water system ("tier 1 sampling
sites") shall consist of buildings that:
(i)
Contain copper pipes with lead solder installed after 1982 or contain lead
pipes; and/or
(ii) Are served by a
lead service line.
7. A
non-transient non-community water system with insufficient tier 1 sites that
meet the targeting criteria in part 6. of this subparagraph shall complete its
sampling pool with sampling sites that contain copper pipes with lead solder
installed before 1983. If additional sites are needed to complete the sampling
pool, the non-transient non-community water system shall use representative
sites throughout the distribution system. For the purpose of this paragraph, a
representative site is a site in which the plumbing materials used at that site
would be commonly found at other sites served by the water system.
8. Any water system whose distribution system
contains lead service lines shall draw 50 percent of the samples it collects
during each monitoring period from sites that contain lead pipes, or copper
pipes with lead solder, and 50 percent of the samples from sites served by a
lead service line. A water system that cannot identify a sufficient number of
sampling sites served by a lead service line shall collect first-draw samples
from all of the sites identified as being served by such lines.
(b) Sample collection methods.
1. All tap samples for lead and copper
collected in accordance with this rule, with the exception of lead service line
samples collected under subparagraph (5)(c) of this rule and samples collected
under part 5. of this subparagraph, shall be first-draw samples.
2. Each first-draw tap sample for lead and
copper shall be one liter in volume and have stood motionless in the plumbing
system of each sampling site for at least six hours. First-draw samples from
residential housing shall be collected from the cold water kitchen tap or
bathroom sink tap. First-draw samples from a nonresidential building shall be
one liter in volume and shall be collected at an interior tap from which water
is typically drawn for consumption. Non-first-draw samples collected in lieu of
first-draw samples pursuant to part 5. of this subparagraph shall be one liter
in volume and shall be collected at an interior tap from which water is
typically drawn for consumption. First-draw samples may be collected by the
system or the system may allow residents to collect first-draw samples after
instructing the residents of the sampling procedures specified in this
subparagraph. To avoid problems of residents handling nitric acid,
acidification of first-draw samples may be done up to 14 days after the sample
is collected. After acidification to resolubilize the metals, the sample must
stand in the original container for the time specified in the approved EPA
method before the sample can be analyzed. If a system allows residents to
perform sampling, the system may not challenge, based on alleged errors in
sample collection, the accuracy of sampling results.
3. Each lead service line sample shall be one
liter in volume and have stood motionless in the lead service line for at least
six hours. Lead service line samples shall be collected in one of the following
three ways:
(i) At the tap after flushing the
volume of water between the tap and the lead service line. The volume of water
shall be calculated based on the interior diameter and length of the pipe
between the tap and lead service line;
(ii) Tapping directly into the lead service
line.
(iii) If the sampling site is
a building constructed as a single-family residence, allowing the water to run
until there is a significant change in temperature which would be indicative of
water that has been standing in the lead service line.
4. A water system shall collect each first
draw tap sample from the same sampling site from which it collected the
previous sample. If, for any reason, the water system cannot gain entry to a
sampling site in order to collect a follow-up tap sample, the system may
collect the follow-up tap sample from another sampling site in its sampling
pool as long as the new site meets the same targeting criteria, and is within
reasonable proximity of the original site.
5. A non-transient non-community water
system, or a community water system that meets the criteria of subparts
(6)(c)7.(i) and (ii) of this rule, that does not have enough taps that can
supply first-draw samples, as defined in Rule
0400-45-01-.04, may
apply to the Department in writing to substitute non-first-draw samples. Such
systems must collect as many first-draw samples from appropriate taps as
possible and identify sampling times and locations that would likely result in
the longest standing time for the remaining sites. The Department has the
discretion to waive the requirement for prior Department approval of
non-first-draw sample sites selected by the system, either through Department
regulation or written notification to the system.
(c) Number of samples. Water systems shall
collect at least one sample during each monitoring period specified in
subparagraph (d) of this paragraph from the number of sites listed in the first
column ("standard monitoring") of the table in this subparagraph. A system
conducting reduced monitoring under part (d)4. of this paragraph shall collect
at least one sample from the number of sites specified in the second column
("reduced monitoring") of the table in this paragraph during each monitoring
period specified in part (d)4. of this paragraph. Such reduced monitoring sites
shall be representative of the sites required for standard monitoring. A public
water system that has fewer than five drinking water taps, that can be used for
human consumption meeting the sample site criteria of subparagraph (a) of this
paragraph to reach the required number of sample sites listed in this
subparagraph, must collect at least one sample from each tap and then must
collect additional samples from those taps on different days during the
monitoring period to meet the required number of sites. Alternatively, the
Department may allow these public water systems to collect a number of samples
less than the number of sites specified in this subparagraph, provided that 100
percent of all taps that can be used for human consumption are sampled. The
Department must approve this reduction of the minimum number of samples in
writing based on a request from the system or onsite verification by the
Department. The Department may specify sampling locations when a system is
conducting reduced monitoring. The table is as follows:
TABLE
0400-45-01-.33(7)(c)
System size (number of People served)
1
|
Number
of sites (standard monitoring)
|
Number of
sites (reduced monitoring)
|
>100,000
|
100
|
50
|
10,001 to 100,000
|
60
|
30
|
3,301 to 10,000
|
40
|
20
|
501
to 3,300
|
20
|
10
|
101 to 500
|
10
|
5
|
less than or equal to 100
|
5
|
5
|
1 Populations
shall be determined by count of the population served or by the household
factor multiplied by the number of connections the system has as determined by
the latest federal census. Water systems serving multi-family residences such
as apartment complexes and mobile home parks shall include each individual
residence unit as a connection in determining the population for the
system.
(d) Timing of
Monitoring
1. Initial tap sampling. The first
six-month monitoring period for small, medium-size and large systems shall
begin on the following dates:
TABLE 0400-45-01-.33(7)(d) 1.
System size (No. People
served)1
|
First
six- month monitoring period begins on
|
>50,000
|
January 1,
1992
|
3,301 to 50,000
|
July 1, 1992
|
less than or equal to 3,300
|
July 1, 1993
|
1 Populations shall be
determined by count of the population served or by the household factor
multiplied by the number of connections the system has as determined by the
latest federal census. Water systems serving multi-family residences such as
apartment complexes and mobile home parks shall include each individual
residence unit as a connection in determining the population for the
system.
(i) All large systems shall
monitor for at least two consecutive six-month periods; and
(ii) All small and medium-size systems shall
monitor during each six-month monitoring period until:
(I) The system exceeds the lead or copper
action level and is therefore required to implement the corrosion control
treatment requirements under paragraph (2) of this rule, in which case the
system shall continue monitoring in accordance with part 2. of this
subparagraph, or
(II) The system
meets the lead or copper action levels during two consecutive six-month
monitoring periods, in which case the system may reduce monitoring in
accordance with part 4. of this subparagraph.
2. Monitoring after installation of corrosion
control and source water treatment.
(i) Any
large system which installs optimal corrosion control treatment pursuant to
part (2)(d)4. of this rule shall monitor for at least two consecutive six-month
monitoring periods by the date specified in part (2)(d)5. of this rule by
January 1, 1998.
(ii) Any small or
medium-size system which installs optimal corrosion control treatment pursuant
to part (2)(e)5. of this rule shall monitor for at least two consecutive
six-month monitoring periods by the date specified in part (2)(e)6. of this
rule.
(iii) Any system which
installs source water treatment pursuant to part (4)(a)3. of this rule shall
monitor for at least two consecutive six-month monitoring periods by the date
specified in part (4)(a)4. of this rule.
3. Monitoring after the Department specifies
water quality parameter values for optimal corrosion control. After the
Department specifies the values for water quality control parameters pursuant
to subparagraph (3)(f) of this rule, the system shall monitor during each
subsequent six-month monitoring period, with the first monitoring period to
begin on the date the Department specifies the optimal values pursuant to
subparagraph (3)(f) of this rule.
4. Reduced Monitoring
(i) A small or medium-size water system that
meets the lead and copper action levels during each of two consecutive
six-month monitoring periods may reduce the number of samples in accordance
with subparagraph (c) of this paragraph and reduce the frequency of sampling to
once per year. A small or medium water system collecting fewer than five
samples as specified in subparagraph (c) of this paragraph, that meets the lead
and copper action levels during each of two consecutive six-month monitoring
periods may reduce the frequency of sampling to once per year. In no case can
the system reduce the number of samples required below the minimum of one
sample per available tap. This sampling shall begin during the calendar year
immediately following the end of the second consecutive six-month monitoring
period.
(ii) Any water system that
meets the lead action level and maintains the range of values for the water
quality control parameters reflecting optimal corrosion control treatment
specified by the Department under subparagraph (3)(f) of this rule during each
of two consecutive six-month monitoring periods may reduce the frequency of
monitoring to once per year and reduce the number of lead and copper samples in
accordance with subparagraph (c) of this paragraph if it receives written
approval from the Department. This sampling shall begin during the calendar
year immediately following the end of the second consecutive six-month
monitoring period. The Department shall review monitoring, treatment, and other
relevant information submitted by the water system in accordance with paragraph
(11) of this rule, and shall notify the system in writing when it determines
the system is eligible to commence reduced monitoring pursuant to this
paragraph. The Department shall review, and where appropriate, revise its
determination when the system submits new monitoring or treatment data, or when
other data relevant to the number and frequency of tap sampling becomes
available.
(iii) A small or
medium-size water system that meets the lead and copper action levels during
three consecutive years of monitoring may reduce the frequency of monitoring
for lead and copper from annually to once every three years. Any water system
that meets the lead action level and maintains the range of values for the
water quality control parameters reflecting optimal corrosion control treatment
specified by the Department under subparagraph (3)(f) of this rule during three
consecutive years of monitoring may reduce the frequency of monitoring from
annually to once every three years if it receives written approval from the
Department. Samples collected once every three years shall be collected no
later than every third calendar year. The Department shall review monitoring,
treatment, and other relevant information submitted by the water system in
accordance with paragraph (11) of this rule, and shall notify the system in
writing when it determines the system is eligible to reduce the frequency of
monitoring to once every three years. The Department shall review, and where
appropriate, revise its determination when the system submits new monitoring or
treatment data, or when other data relevant to the number and frequency of tap
sampling becomes available.
(iv) A
water system that reduces the number and frequency of sampling shall collect
these samples from representative sites included in the pool of targeted
sampling sites identified in subparagraph (a) of this paragraph. Systems
sampling annually or less frequently shall conduct the lead and copper tap
sampling during the months of June, July, August, or September unless the
Department has approved a different sampling period in accordance with item (I)
of this subpart.
(I) The Department may
approve a different period for conducting the lead and copper tap sampling for
systems collecting a reduced number of samples. Such a period shall be no
longer than four consecutive months and must represent a time of normal
operation where the highest levels of lead are most likely to occur. For a
non-transient non-community water system that does not operate during the
months of June through September, and for which the period of normal operation
where the highest levels of lead are most likely to occur is not known, the
Department shall designate a period that represents a time of normal operation
for the system. This sampling shall begin during the period approved or
designated by the Department in the calendar year immediately following the end
of the second consecutive six-month monitoring period for systems initiating
annual monitoring and during the three-year period following the end of the
third consecutive calendar year of annual monitoring for systems initiating
triennial monitoring.
(II) Systems
monitoring annually, that have been collecting samples during the months of
June through September and that receive Department approval to alter their
sample collection period under item (I) of this subpart, must collect their
next round of samples during a time period that ends no later than 21 months
after the previous round of sampling. Systems monitoring triennially that have
been collecting samples during the months of June through September, and
receive Department approval to alter the sampling collection period as per item
(I) of this subpart, must collect their next round of samples during a time
period that ends no later than 45 months after the previous round of sampling.
Subsequent rounds of sampling must be collected annually or triennially, as
required by this section. Small systems with waivers, granted pursuant to
subparagraph (g) of this paragraph, that have been collecting samples during
the months of June through September and receive Department approval to alter
their sample collection period under item (I) of this subpart must collect
their next round of samples before the end of the 9-year period.
(v) Any water system that
demonstrates for two consecutive 6-month monitoring periods that the tap water
lead level computed under part (1)(c)3. of this rule is less than or equal to
0.005 mg/L and the tap water copper level computed under part (1)(c)3. of this
rule is less than or equal to 0.65 mg/L may reduce the number of samples in
accordance with subparagraph (c) of this paragraph and reduce the frequency of
sampling to once every three calendar years.
(vi)
(I) A
small or medium-size water system subject to reduced monitoring that exceeds
the lead or copper action level shall resume sampling in accordance with part
3. of this subparagraph and collect the number of samples specified for
standard monitoring under subparagraph (c) of this paragraph. Such a system
shall also conduct water quality parameter monitoring in accordance with
subparagraph (8)(b), (c) or (d) of this rule (as appropriate) during the
monitoring period in which it exceeded the action level. Any such system may
resume annual monitoring for lead and copper at the tap at the reduced number
of sites specified in subparagraph (c) of this paragraph after it has completed
two subsequent consecutive six-month rounds of monitoring that meet the
criteria of subpart (i) of this part and/or may resume triennial monitoring for
lead and copper at the reduced number of sites after it demonstrates through
subsequent rounds of monitoring that it meets the criteria of either subpart
(iii) or (v) of this part.
(II) Any
water system subject to the reduced monitoring frequency that fails to meet the
lead action level during any four-month monitoring period or that fails to
operate at or above the minimum value or within the range of values for the
water quality parameters specified by the Department under subparagraph (3)(f)
of this rule for more than nine days in any six-month period specified in
subparagraph (8)(d) of this rule shall conduct tap water sampling for lead and
copper at the frequency specified in part 3. of this subparagraph, collect the
number of samples specified for standard monitoring under subparagraph (c) of
this paragraph, and shall resume monitoring for water quality parameters within
the distribution system in accordance with subparagraph (8)(d) of this rule.
This standard tap water sampling shall begin no later than the six-month period
beginning January 1 of the calendar year following the lead action level
exceedance or water quality parameter excursion. Such a system may resume
reduced monitoring for lead and copper at the tap and for water quality
parameters within the distribution system under the following conditions:
I. The system may resume annual monitoring
for lead and copper at the tap at the reduced number of sites specified in
subparagraph (c) of this paragraph after it has completed two subsequent
six-month rounds of monitoring that meet the criteria of subpart (ii) of this
part and the system has received written approval from the Department that it
is appropriate to resume reduced monitoring on an annual frequency. This
sampling shall begin during the calendar year immediately following the end of
the second consecutive six month monitoring period.
II. The system may resume triennial
monitoring for lead and copper at the tap at the reduced number of sites after
it demonstrates through subsequent rounds of monitoring that it meets the
criteria of either subpart (iii) or (v) of this part and the system has
received written approval from the Department that it is appropriate to resume
triennial monitoring.
III. The
system may reduce the number of water quality parameter tap water samples
required in accordance with part (8)(e)1. of this rule and the frequency with
which it collects such samples in accordance with part (8)(e)2. of this rule.
Such a system may not resume triennial monitoring for water quality parameters
at the tap until it demonstrates, in accordance with the requirements of part
(8)(e)2. of this rule, that it has re-qualified for triennial
monitoring.
(vii) Any water system subject to a reduced
monitoring frequency under this part shall notify the Department in writing in
accordance with part (11)(a)3. of this rule of any upcoming long term change in
treatment or addition of a new source as described in part (11)(a)3. of this
rule. The Department must review and approve the addition of a new source or
long-term change in water treatment before it is implemented by the water
system. The Department may require the system to resume sampling in accordance
with part 3. of this subparagraph and collect the number of samples specified
for standard monitoring under subparagraph (c) of this paragraph or take other
appropriate steps such as increased water quality parameter monitoring or
reevaluation of its corrosion control treatment given the potentially different
water quality considerations.
(e) Additional monitoring by systems. The
results of any monitoring conducted in addition to the minimum requirements of
this paragraph shall be considered by the system and may be considered by the
Department in making any determinations (i.e., calculating the 90th percentile
lead or copper level) under this rule.
(f) Invalidation of lead or copper tap water
samples. A sample invalidated under this subparagraph does not count toward
determining lead or copper 90th percentile levels under subparagraph (1)(c) of
this rule or toward meeting the minimum monitoring requirements of subparagraph
(c) of this paragraph.
1. The Department may
invalidate a lead or copper tap water sample at least if one of the following
conditions is met.
(i) The laboratory
establishes that improper sample analysis caused erroneous results.
(ii) The Department determines that the
sample was taken from a site that did not meet the site selection criteria of
this paragraph.
(iii) The sample
container was damaged in transit.
(iv) There is substantial reason to believe
that the sample was subject to tampering.
2. The system must report the results of all
samples to the Department and all supporting documentation for samples the
system believes should be invalidated.
3. To invalidate a sample under part 1. of
this subparagraph, the decision and the rationale for the decision must be
documented in writing. The Department may not invalidate a sample solely on the
grounds that a follow-up sample result is higher or lower than that of the
original sample.
4. The water
system must collect replacement samples for any samples invalidated under this
subparagraph if, after the invalidation of one or more samples, the system has
too few samples to meet the minimum requirements of subparagraph (c) of this
paragraph. Any such replacement samples must be taken as soon as possible, but
no later than 20 days after the date the Department invalidates the sample or
by the end of the applicable monitoring period, whichever occurs later.
Replacement samples taken after the end of the applicable monitoring period
shall not also be used to meet the monitoring requirements of a subsequent
monitoring period. The replacement samples shall be taken at the same locations
as the invalidated samples or, if that is not possible, at locations other than
those already used for sampling during the monitoring period.
(g) Monitoring waivers for small
systems. Any small system serving fewer than 3300 persons that meets the
criteria of this paragraph may apply to the Department to reduce the frequency
of monitoring for lead and copper under this paragraph to once every nine years
(i.e., a "full waiver") if it meets all of the materials criteria specified in
part 1. of this subparagraph and all of the monitoring criteria specified in
part 2. of this subparagraph. Any small system that meets the criteria in parts
1. and 2. of this subparagraph only for lead, or only for copper, may apply to
the Department for a waiver to reduce the frequency of tap water monitoring to
once every nine years for that contaminant only (i.e., a "partial waiver").
1. Materials criteria. The system must
demonstrate that its distribution system and service lines and all drinking
water supply plumbing, including plumbing conveying drinking water within all
residences and buildings connected to the system, are free of lead- containing
materials and/or copper-containing materials, as those terms are defined in
this rule, as follows:
(i) Lead. To qualify
for a full waiver, or a waiver of the tap water monitoring requirements for
lead (i.e., a "lead waiver"), the water system must provide certification and
supporting documentation to the Department that the system is free of all
lead-containing materials, as follows:
(I) It
contains no plastic pipes which contain lead plasticizers, or plastic service
lines which contain lead plasticizers; and
(II) It is free of lead service lines, lead
pipes, lead soldered pipe joints, and leaded brass or bronze alloy fittings and
fixtures, unless such fittings and fixtures meet the specifications of any
standard established pursuant to
42 U.S.C.
300g-6(e) [SDWA section
1417(e)].
(ii) Copper.
To qualify for a full waiver, or a waiver of the tap water monitoring
requirements for copper (i.e., a "copper waiver"), the water system must
provide certification and supporting documentation to the Department that the
system contains no copper pipes or copper service lines.
2. Monitoring criteria for waiver issuance.
The system must have completed at least one 6-month round of standard tap water
monitoring for lead and copper at sites approved by the Department and from the
number of sites required by subparagraph (c) of this paragraph and demonstrate
that the 90th percentile levels for any and all rounds of monitoring conducted
since the system became free of all lead-containing and/or copper-containing
materials, as appropriate, meet the following criteria.
(i) Lead levels. To qualify for a full
waiver, or a lead waiver, the system must demonstrate that the 90th percentile
lead level does not exceed 0.005 mg/L.
(ii) Copper levels. To qualify for a full
waiver, or a copper waiver, the system must demonstrate that the 90th
percentile copper level does not exceed 0.65 mg/L.
3. Department approval of waiver application.
The Department shall notify the system of its waiver determination, in writing,
setting forth the basis of its decision and any condition of the waiver. As a
condition of the waiver, the Department may require the system to perform
specific activities (e.g., limited monitoring, periodic outreach to customers
to remind them to avoid installation of materials that might void the waiver)
to avoid the risk of lead or copper concentration of concern in tap water. The
small system must continue monitoring for lead and copper at the tap as
required by parts (d)1. through (d)4. of this paragraph, as appropriate, until
it receives written notification from the Department that the waiver has been
approved.
4. Monitoring frequency
for systems with waivers.
(i) A system with a
full waiver must conduct tap water monitoring for lead and copper in accordance
with subpart (d)4.(iv) of this paragraph at the reduced number of sampling
sites identified in subparagraph (c) of this paragraph at least once every nine
years and provide the materials certification specified in part 1. of this
subparagraph for both lead and copper to the Department along with the
monitoring results. Samples collected every nine years shall be collected no
later than every ninth calendar year.
(ii) A system with a partial waiver must
conduct tap water monitoring for the waived contaminant in accordance with
subpart (d)4.(iv) of this paragraph at the reduced number of sampling sites
specified in subparagraph (c) of this paragraph at least once every nine years
and provide the materials certification specified in part 1. of this
subparagraph pertaining to the waived contaminant along with the monitoring
results. Such a system also must continue to monitor for the non-waived
contaminant in accordance with requirements of parts (d)1. through 4. of this
paragraph, as appropriate.
(iii)
Any water system with a full or partial waiver shall notify the Department in
writing in accordance with part (11)(a)3. of this rule of any upcoming
long-term change in treatment or addition of a new source, as described in that
paragraph. The Department must review and approve the addition of a new source
or long-term change in water treatment before it is implemented by the water
system. The Department has the authority to require the system to add or modify
waiver conditions (e.g., require recertification that the system is free of
lead-containing and/or copper-containing materials, require additional round(s)
of monitoring), if it deems such modifications are necessary to address
treatment or source water changes at the system.
(iv) If a system with a full or partial
waiver becomes aware that it is no longer free of lead-containing or
copper-containing materials, as appropriate, (e.g., as a result of new
construction or repairs), the system shall notify the Department in writing no
later than 60 days after becoming aware of such a change.
5. Continued eligibility. If the system
continues to satisfy the requirements of part 4. of this subparagraph, the
waiver will be renewed automatically, unless any of the conditions listed in
subparts (i) through (iii) of this part occurs. A system whose waiver has been
revoked may re-apply for a waiver at such time as it again meets the
appropriate materials and monitoring criteria of parts 1. and 2. of this
subparagraph.
(i) A system with a full waiver
or a lead waiver no longer satisfies the materials criteria of subpart 1.(i) of
this subparagraph or has a 90th percentile lead level greater than 0.005
mg/L.
(ii) A system with a full
waiver or a copper waiver no longer satisfies the materials criteria of subpart
1.(ii) of this subparagraph or has a 90th percentile copper level greater than
0.65 mg/L.
(iii) The Department
notifies the system, in writing, that the waiver has been revoked, setting
forth the basis of its decision.
6. Requirements following waiver revocation.
A system whose full or partial waiver has been revoked by the Department is
subject to the corrosion control treatment and lead and copper tap water
monitoring requirements, as follows:
(i) If
the system exceeds the lead and/or copper action level, the system must
implement corrosion control treatment in accordance with the deadlines
specified in subparagraph (2)(e) of this rule, and any other applicable
requirements of of this rule.
(ii)
If the system meets both the lead and the copper action level, the system must
monitor for lead and copper at the tap no less frequently than once every three
years using the reduced number of sample sites specified in subparagraph (c) of
this paragraph.
7.
Pre-existing waivers. Small system waivers approved by the Department in
writing prior to April 11, 2000 shall remain in effect under the following
conditions:
(i) If the system has demonstrated
that it is both free of lead-containing and copper-containing materials, as
required by part 1. of this subparagraph and that its 90th percentile lead
levels and 90th percentile copper levels meet the criteria of part 2. of this
subparagraph, the waiver remains in effect so long as the system continues to
meet the waiver eligibility criteria of part 5. of this subparagraph. The first
round of tap water monitoring conducted pursuant to part 4. of this
subparagraph shall be completed no later than nine years after the last time
the system has monitored for lead and copper at the tap.
(ii) If the system has met the materials
criteria of part 1. of this subparagraph but has not met the monitoring
criteria of part 2. of this subparagraph, the system shall conduct a round of
monitoring for lead and copper at the tap demonstrating that it meets the
criteria of part 2. of this subparagraph no later than September 30, 2000, or
the effective date of this rule whichever is later. Thereafter, the waiver
shall remain in effect as long as the system meets the continued eligibility
criteria of part 5. of this subparagraph. The first round of tap water
monitoring conducted pursuant to part 4. of this subparagraph shall be
completed no later than nine years after the round of monitoring conducted
pursuant to part 2. of this subparagraph.
(8) Monitoring requirements for
water quality parameters.
All large water systems and all small and
medium-size systems that exceed the lead or copper action level shall monitor
water quality parameters in addition to lead and copper in accordance with this
paragraph. The requirements of this paragraph are summarized in the table at
the end of this paragraph.
(a) General
Requirements.
1. Sample Collection Methods.
(i) Tap samples shall be representative of
water quality throughout the distribution system taking into account the number
of persons served, the different sources of water, the different treatment
methods employed by the system, and seasonal variability. Tap sampling under
this subpart is not required to be conducted at taps targeted for lead and
copper sampling pursuant to subparagraph (7)(a) of this rule. (Note: Systems
may find it convenient to conduct tap sampling for water quality parameters at
sites used for coliform sampling).
(ii) Samples collected at the entry point(s)
to the distribution system shall be from locations representative of each
source after treatment. If a system draws water from more than one source and
the sources are combined before distribution, the system must sample at an
entry point to the distribution system during periods of normal operating
conditions (i.e., when water is representative of all sources being
used).
2. Number of
samples.
(i) Systems shall collect two tap
samples for applicable water quality parameters during each monitoring period
specified under subparagraphs (b) through (e) of this paragraph from the
following number of sites.
TABLE 0400-45-01-.33(8)(a) 2.(i)
System size (No. People
served)
|
No. of sites for water quality
parameters
|
>100,000..........
|
25
|
10,001-100,000.........
|
10
|
3,301 to 10,000........
|
3
|
501 to 3,300..........
|
2
|
101
to 500..........
|
1
|
[LESS THAN EQAUL TO]100............
|
1
|
(ii) Except as provided in part
(c)3. of this paragraph, systems shall collect two samples for each applicable
water quality parameter at each entry point to the distribution system during
each monitoring period specified in subparagraph (b) of this
paragraph.
(b) Initial Sampling. All large water systems
shall measure the applicable water quality parameters as specified in part 1.
of this subparagraph at taps and at each entry point to the distribution system
during each six-month monitoring period specified in part (7)(d)1. of this
rule. All small and medium size systems shall measure the applicable water
quality parameters at the locations specified in parts 1. and 2. of this
subparagraph during each six-month monitoring period specified in part (7)(d)1.
of this rule during which the system exceeds the lead or copper action level.
1. Water Quality Parameters for Monitoring at
Taps:
(i) pH;
(ii) Alkalinity;
(iii) Orthophosphate, when an inhibitor
containing a phosphate compound is used;
(iv) Silica, when an inhibitor containing a
silicate compound is used;
(v)
Calcium;
(vi)
Conductivity;
(vii) Water
temperature; and
(viii) Other
parameters as specified by the Department.
2. At each entry point to the distribution
system: all of the applicable parameters listed in part 1. of this
subparagraph.
(c)
Monitoring after Installation of corrosion control. Any large system which
installs optimal corrosion control treatment pursuant to part (2)(d)4. of this
rule shall measure the water quality parameters at the locations and
frequencies specified in parts 1., 2. and 3. of this subparagraph during each
six-month monitoring period specified in subpart (7)(d)2.(i) of this rule. Any
small or medium-size system which installs optimal corrosion control treatment
shall conduct such monitoring during each six-month monitoring period specified
in subpart (7)(d)2.(ii) of this rule in which the system exceeds the lead or
copper action level.
1. Water Quality
Parameters for Monitoring at Taps, two samples for:
(i) pH;
(ii) Alkalinity;
(iii) Orthophosphate, when an inhibitor
containing a phosphate compound is used;
(iv) Silica, when an inhibitor containing a
silicate compound is used;
(v)
Calcium, when calcium carbonate stabilization is used as part of corrosion
control; and
(vi) Other parameters
as specified by the Department.
2. Except as provided in part 3. of this
subparagraph, at each entry point to the distribution system, at least one
sample no less frequently than every two weeks (biweekly) for:
(i) pH;
(ii) When alkalinity is adjusted as part of
optimal corrosion control, a reading of the dosage rate of the chemical used to
adjust alkalinity, and the alkalinity concentration; and
(iii) When a corrosion inhibitor is used as
part of optimal corrosion control, a reading of the dosage rate of the
inhibitor used, and the concentration of orthophosphate or silica (whichever is
applicable).
(iv) Other parameters
as specified by the Department.
3. Any ground water system can limit entry
point sampling described in part 2. of this subparagraph to those entry points
that are representative of water quality and treatment conditions throughout
the system. If water from untreated ground water sources mixes with water from
treated ground water sources, the system must monitor for water quality
parameters both at representative entry points receiving treatment and
representative entry points receiving no treatment. Prior to the start of any
monitoring under this subparagraph, the system shall provide to the Department
written information identifying the selected entry points and documentation,
including information on seasonal variability, sufficient to demonstrate that
the sites are representative of water quality and treatment conditions
throughout the system.
(d) Monitoring after the Department specifies
water quality parameter values for optimal corrosion control. After the
Department specifies the values for applicable water quality control parameters
reflecting optimal corrosion control treatment under subparagraph (3)(f) of
this rule, all large systems shall measure the applicable water quality
parameters in accordance with subparagraph (c) of this paragraph and determine
compliance with the requirements of subparagraph (3)(g) of this rule every six
months with the first six-month period to begin either January 1 or July 1,
whichever comes first, after the Department specifies the optimal values under
subparagraph (3)(f) of this rule. Any small or medium-size system shall conduct
such monitoring during each six-month period specified in this subparagraph in
which the system exceeds the lead or copper action level. For any such small
and medium-size system that is subject to a reduced monitoring frequency
pursuant to part (7)(d)4. of this rule at the time of the action level
exceedance, the start of the applicable six-month period under this
subparagraph shall coincide with the start of the applicable monitoring period
under part (7)(d)4. of this rule. Compliance with Department-designated optimal
water quality parameter values shall be determined as specified under
subparagraph (3)(g) of this rule.
(e) Reduced monitoring.
1. Any water system that maintains the range
of values for the water quality parameters reflecting optimal corrosion control
treatment during each of two consecutive six-month monitoring periods under
subparagraph (d) of this paragraph shall continue monitoring at the entry
point(s) to the distribution system as specified in part (c)2. of this
paragraph. The system may collect two tap samples for applicable water quality
parameters from the following reduced number of sites during each six-month
monitoring period, if it qualifies for and requests reduced tap monitoring for
water quality parameters.
TABLE 0400-45-01-.33(8)(e) 1.
System size (No. People
served)
|
No. of sites for water quality
parameters
|
>100,000.............
|
10
|
10,001-100,000.........
|
7
|
3,301
to 10,000..........
|
3
|
501 to 3,300............
|
2
|
101
to 500............
|
1
|
[LESS THAN EQAUL TO]100..............
|
1
|
2.
(i) Any water system that maintains the range
of values for the water quality parameters reflecting optimal corrosion control
treatment specified by the Department under subparagraph (3)(f) of this rule
during three consecutive years of monitoring may reduce the frequency with
which it collects the number of tap samples for applicable water quality
parameters specified in part 1 of this subparagraph from every six months to
annually. This sampling begins during the calendar year immediately following
the end of the monitoring period in which the third consecutive year of
six-month monitoring occurs. Any water system that maintains the range of
values for water quality parameters reflecting optimal corrosion control
treatment specified by the Department under subparagraph (3)(f) of this rule
during three consecutive years of annual monitoring under this paragraph may
reduce the frequency with which it collects the number of tap samples for
applicable water quality parameters specified in part 1. of this subparagraph
from annually to every three years. This sampling begins no later than the
third calendar year following the end of the monitoring period in which the
third consecutive year of monitoring occurs.
(ii) A water system may reduce the frequency
with which it collects tap samples for applicable water quality parameters
specified in part 1. of this subparagraph to every three years if it
demonstrates during two consecutive monitoring periods that its tap water lead
level at the 90th percentile is less than or equal to the PQL for lead
specified in subparagraph (10)(e) of Rule
0400-45-01-.14,
that its tap water copper level at the 90th percentile is less than or equal to
0.65 mg/L for copper in part (1)(c)2. of this rule, and that it also has
maintained the range of values for the water quality parameters reflecting
optimal corrosion control treatment specified by the Department under
subparagraph (3)(f) of this rule. Monitoring conducted every three years shall
be done no later than every third calendar year.
3. A water system that conducts sampling
annually shall collect these samples throughout the year so as to reflect
seasonal variability as per this subparagraph.
4. Any water system subject to the reduced
monitoring frequency that fails to operate at or above the minimum value or
within the range of values for the water quality parameters specified by the
Department in subparagraph (3)(f) for more than nine days in any six-month
period specified in subparagraph (3)(g) shall resume distribution system tap
water sampling in accordance with the number and frequency requirements in
subparagraph (d) of this paragraph. Such a system may resume annual monitoring
for water quality parameters at the tap at the reduced number of sites
specified in part 1. of this subparagraph after it has completed two subsequent
consecutive six-month rounds of monitoring that meet the criteria of of part 1.
of this subparagraph and/or may resume triennial monitoring for water quality
parameters at the tap at the reduced number of sites after it demonstrates
through subsequent rounds of monitoring that it meets the criteria of either
subpart 2.(i) or (ii) of this subparagraph.
(f) Additional monitoring by systems. The
results of any monitoring conducted in addition to the minimum requirements of
this paragraph shall be considered by the system and may be considered by the
Department in making any determinations (i.e., determining concentrations of
water quality parameters) under this paragraph or paragraph (3) of this rule.
TABLE 0400-45-01-.33(8)(f)
SUMMARY OF MONITORING
REQUIREMENTS FOR WATER QUALITY PARAMETERS1
Monitoring
Period
|
Parameters2
|
Location
|
Frequency
|
Initial Monitoring
|
pH, alkalinity, orthophosphate,
or
silica3
calcium, or conductivity,
temperature
|
Taps and at entry point(s) to
distribution system
|
Every 6 months
|
After Installation of Corrosion
Control
|
pH, alkalinity,
orthophosphate, or silica3
calcium4
|
Taps
|
Every 6 months
|
|
pH, alkalinity
dosage rate and concentration (if alkalinity adjusted as part of corrosion
control) inhibitor dosage rate and inhibitor
residual5
|
Entry
point(s) to distribution system
|
No less
frequently than every two weeks
|
After Department Specifies Parameter Values for Optimal Corrosion
Control
|
pH, alkalinity , 3
orthophosphate or silica , calcium 4
|
Entry point(s) to distribution system
|
Every 6 months
|
|
pH, alkalinity dosage rate and concentration ( if
alkalinity adjusted as part of corrosion control) inhibitor dosage rate
andinhibitor residual5
|
Entry point(s) to distribution system
|
No less frequently than every two
weeks.
|
Reduced
Monitoring
|
pH, alkalinity , 3 ,
orthophosphate or silica calcium 4
|
Taps
|
Every 6 months , annually 7 ,or
every 3 years 8 reduced number of sites
|
|
pH, alkalinity dosage rate and
concentration ( if alkalinity adjusted as part of corrosion control) inhibitor
dosage rate andinhibitor residual5
|
Entry point(s) to distribution system
|
No less frequently than every two
weeks.
|
1 table is for
illustrative purposes; consult the text of this section for precise regulatory
requirements.
2 Small and medium-size systems have to monitor for
water quality parameters only during monitoring periods in which the system
exceeds the lead or copper action level.
3 Orthophosphate must be
measured only when an inhibitor containing a phosphate compound is used. Silica
must be measured only when an inhibitor containing silicate compound is
used.
4 Calcium must be measured only when calcium carbonate
stabilization is used as part of corrosion control.
5 Inhibitor
dosage rates and inhibitor residual concentrations (orthophosphate or silica)
must be measured only when an inhibitor is used.
6 Ground water
systems may limit monitoring to representative locations throughout the
system.
7 Water systems may reduce frequency of monitoring for
water quality parameters at the tap from every six months to annually if they
have maintained the range of values for water quality parameters reflecting
optimal corrosion control during 3 consecutive years of monitoring.
8 Water systems may further reduce the frequency of monitoring for water
quality parameters at the tap from annually to once every 3 years if they have
maintained the range of values for water quality parameters reflecting optimal
corrosion control during 3 consecutive years of annual monitoring. Water
systems may accelerate to triennial monitoring for water quality parameters at
the tap if they have maintained 90th percentile lead levels less than or equal
to 0.005 mg/L, 90th percentile copper levels less than or equal to 0.65 mg/L,
and the range of water quality parameters designated by the Department under
paragraph (3)(f) as representing optimal corrosion control during two
consecutive six-month monitoring periods.
(9) Monitoring requirements for lead and
copper in source water.
(a) Sample location,
collection methods, and number of samples.
1.
A water system that fails to meet the lead or copper action level on the basis
of tap samples collected in accordance with paragraph (7) of this rule shall
collect lead and copper source water samples in accordance with the following
requirements regarding sample location, number of samples, and collection
methods:
(i) Groundwater systems shall take a
minimum of one sample at every entry point to the distribution system which is
representative of each well after treatment (hereafter called a sampling
point). The system shall take one sample at the same sampling point unless
conditions make another sampling point more representative of each source or
treatment plant.
(ii) Surface water
systems shall take a minimum of one sample at every entry point to the
distribution system after any application of treatment or in the distribution
system at a point which is representative of each source after treatment
(hereafter called a sampling point). The system shall take each sample at the
same sampling point unless conditions make another sampling point more
representative of each source or treatment plant.
Note: For the purposes
of this subpart, surface water systems include systems with a combination of
surface and ground sources.
(iii) If a system draws water from more than
one source and the sources are combined before distribution, the system must
sample at an entry point to the distribution system during periods of normal
operating conditions (i.e., when water is representative of all sources being
used).
(iv) The Department may
reduce the total number of samples which must be analyzed by allowing the use
of compositing. Compositing of samples must be done by certified laboratory
personnel. Composite samples from a maximum of five samples are allowed,
provided that if the lead concentration in the composite sample is greater than
or equal to 0.001 mg/L or the copper concentration is greater than or equal to
0.160 mg/L, then either:
(I) A follow-up
sample shall be taken and analyzed within 14 days at each sampling point
included in the composite; or
(II)
If duplicates of or sufficient quantities from the original samples from each
sampling point used in the composite are available, the system may use these
instead of resampling.
2. Where the results of sampling indicate an
exceedance of maximum permissible source water levels established under part
(4)(b)4. of this rule, one confirmation sample shall be collected as soon as
possible after the initial sample was taken (but not to exceed two weeks) at
the same sampling point. If a required confirmation sample is taken for lead or
copper, then the results of the initial and confirmation sample shall be
averaged in determining compliance with the Department-specified maximum
permissible level. Any sample value below the detection limit shall be
considered to be zero. Any value above the detection limit, but below the
practical quantitation limit (PQL), as set forth in subparagraph (10)(d) of
Rule
0400-45-01-.14,
shall either be considered as the measured value or be considered one-half the
PQL.
(b) Monitoring
frequency after system exceeds tap water action level. Any system which exceeds
the lead or copper action level at the tap shall collect one source water
sample from each entry point to the distribution system no later than six
months after the end of the monitoring period during which the lead or copper
action level was exceeded. For monitoring periods that are annual or less
frequent, the end of the monitoring period is September 30 of the calendar year
in which the sampling occurs, or if the Department has established an alternate
monitoring period, the last day of that period.
(c) Monitoring frequency after installation
of source water treatment. Any system which installs source water treatment
pursuant to part (4)(a)3. of this rule shall collect an additional source water
sample from each entry point to the distribution system during two consecutive
six-month monitoring periods by the deadline specified in part (4)(a)4. of this
rule.
(d) Monitoring frequency
after the Department specifies maximum permissible source water levels or
determines that source water treatment is not needed.
1. A system shall monitor at the frequency
specified in subpart (i) or (ii) of this part in cases where the Department
specifies maximum permissible source water levels pursuant to part (4)(b)4. of
this rule or determines that the system is not required to install source water
treatment pursuant to part (4)(b)2. of this rule.
(i) A water system using only groundwater
shall collect samples once during the three-year compliance period in effect
when the applicable Department determination under part 1. of this subparagraph
is made. Such systems shall collect samples once during each subsequent
compliance period. Triennial samples shall be collected every third calendar
year.
(ii) A water system using
surface water (or a combination of surface water and ground water) shall
collect samples once during each calendar year, the first annual monitoring
period to begin during the year in which the applicable Department
determination is made under part 1. of this subparagraph.
2. A system is not required to conduct source
water sampling for lead and/or copper if the system meets the action level for
the specific contaminant in tap water samples during the entire source water
sampling period applicable to the system under subpart 1.(i) or (ii) of this
subparagraph.
(e)
Reduced monitoring frequency.
1. A water
system using only ground water may reduce the monitoring frequency for lead and
copper in source water to once during each nine-year compliance cycle provided
that the samples are collected no later than every ninth calendar year and if
the system meets one of the following criteria:
(i) The system demonstrates that finished
drinking water entering the distribution system has been maintained below the
maximum permissible lead and copper concentrations specified by the Department
in part (4)(b)4. of this rule during at least three consecutive compliance
periods under part (d)1. of this paragraph, or
(ii) The Department has determined that
source water treatment is not needed and the system demonstrates that, during
at least three consecutive compliance periods in which sampling was conducted
under part (d)1. of this paragraph, the concentration of lead in source water
was less than or equal to 0.005 mg/L and the concentration of copper in source
water was less than or equal to 0.65 mg/L.
2. A water system using surface water (or a
combination of surface water and ground water) may reduce the monitoring
frequency in part (d)1. of this paragraph to once during each nine-year
compliance cycle provided that the samples are collected no later than every
ninth calendar year and if the system meets one of the following criteria:
(i) The system demonstrates that finished
drinking water entering the distribution system has been maintained below the
maximum permissible lead and copper concentrations specified by the Department
in part (4)(b)4. of this rule for at least three consecutive years;
or
(ii) The Department has
determined that source water treatment is not needed and the system
demonstrates that, during at least three consecutive years, the concentration
of lead in source water was less than or equal to 0.005 mg/L and the
concentration of copper in source water was less than or equal to 0.65
mg/L.
3. A water system
that uses a new source of water is not eligible for reduced monitoring for lead
and/or copper until concentrations in samples collected from the new source
during three consecutive monitoring periods are below the maximum permissible
lead and copper concentrations specified by the Department in part (4)(a)5. of
this rule.
(10) Reserved
(11) Reporting requirements. All water
systems shall report all of the following information to the Department in
accordance with this paragraph.
(a) Reporting
requirements for tap water monitoring for lead and copper and for water quality
parameter monitoring.
1. Except as provided in
subpart (viii) of this part, a water system shall report the information
specified subparts (i) through (viii) of this part for all tap water samples
specified in paragraph (7) of this rule and for all water quality parameter
samples specified in paragraph (8) of this rule within the first 10 days
following the end of each applicable monitoring period specified in paragraphs
(7) and (8) of this rule (i.e., every six months, annually, every 3 years, or
every 9 years). For monitoring periods with a duration less than six months,
the end of the monitoring period is the last date samples can be collected
during that period as specified in paragraphs (7) and (8) of this rule.
(i) The results of all tap samples for lead
and copper including the location of each site and criteria under parts
(7)(a)3., 4., 5., 6. and/or 7. of this rule, under which the site was selected
for the system's sampling pool;
(ii) Documentation for each tap water lead or
copper sample for which the water system requests invalidation pursuant to part
(7)(f)2. of this rule;
(iii)
[Reserved];
(iv) The 90th
percentile lead and copper concentrations measured from among all lead and
copper tap water samples collected during each monitoring period calculated in
accordance with part (1)(c)3. of this rule, unless the Department calculates
the system's 90th percentile lead and copper levels under subparagraph (h) of
this paragraph;
(v) With the
exception of initial tap sampling conducted pursuant to part (7)(d)1. of this
rule, the system shall designate any site which was not sampled during previous
monitoring periods, and include an explanation of why sampling sites have
changed;
(vi) The results of all
tap samples for pH, and where applicable, alkalinity, calcium, conductivity,
temperature, and orthophosphate or silica collected pursuant to subparagraphs
(8)(b) through (e) of this rule; and
(vii) The results of all samples collected at
the entry point(s) to the distribution system for applicable water quality
parameters under subparagraphs (8)(b) through (e) of this rule;
(viii) A water system shall report the
results of all water quality parameter samples collected under subparagraphs
(8)(c) through (f) of this rule during each six-month monitoring period
specified in subparagraph (8)(d) of this rule within the first 10 days
following the end of the monitoring period unless the Department has specified
a more frequent reporting requirement.
2. For a non-transient non-community water
system, or a community water system meeting the criteria of subparts
(6)(c)7.(i) and (ii) of this rule, that does not have enough taps that can
provide first-draw samples, the system must either:
(i) Provide written documentation to the
Department identifying standing times and locations for enough non-first-draw
samples to make up its sampling pool under part (7)(b)5. of this rule by the
start of the first applicable monitoring period under paragraph (7)(d) of this
rule that commences after April 11, 2000, unless the Department has waived
prior Department approval of non-first-draw sample sites selected by the system
pursuant to part (7)(b)5. of this rule; or
(ii) If the Department has waived prior
approval of non-first-draw sample sites selected by the system, identify, in
writing, each site that did not meet the six-hour minimum standing time and the
length of standing time for that particular substitute sample collected
pursuant to part (7)(b)5. of this rule and include this information with the
lead and copper tap sample results required to be submitted pursuant to subpart
1.(i) of this subparagraph.
3. At a time specified by the Department, or
if no specific time is designated by the Department then as early as possible
prior to the addition of a new source or any change in water treatment, a water
system deemed to have optimized corrosion control under part (2)(b)3. of this
rule, a water system subject to reduced monitoring pursuant to part (7)(d)4. of
this rule, or a water system subject to a monitoring waiver pursuant to
subparagraph (7)(g) of this rule, shall submit written documentation to the
Department describing the change or addition. The Department must review and
approve the addition of a new source or long-term change in treatment before it
is implemented by the water system. Examples of long-term treatment changes
include the addition of a new treatment process or modification of an existing
treatment process. Examples of modifications include switching secondary
disinfectants, switching coagulants (e.g., alum to ferric chloride), and
switching corrosion inhibitor products (e.g., orthophosphate to blended
phosphate). Long-term changes can include dose changes to existing chemicals if
the system is planning long-term changes to its finished water pH or residual
inhibitor concentration. Long-term treatment changes would not include chemical
dose fluctuations associated with daily raw water quality changes.
4. Any small system applying for a monitoring
waiver under subparagraph (7)(g) of this rule, or subject to a waiver granted
pursuant to part (7)(g)3. of this rule, shall provide the following information
to the Department in writing by the specified deadline:
(i) By the start of the first applicable
monitoring period in subparagraph (7)(d) of this rule, any small water system
applying for a monitoring waiver shall provide the documentation required to
demonstrate that it meets the waiver criteria of parts (7)(g)1. and 2. of this
rule.
(ii) No later than nine years
after the monitoring previously conducted pursuant to part (7)(g)2. or subpart
(7)(g)4.(i) of this rule, each small system desiring to maintain its monitoring
waiver shall provide the information required by subparts (7)(g)4.(i) and (ii)
of this rule.
(iii) No later than
60 days after it becomes aware that it is no longer free of lead-containing
and/or copper-containing material, as appropriate, each small system with a
monitoring waiver shall provide written notification to the Department, setting
forth the circumstances resulting in the lead-containing and/or
copper-containing materials being introduced into the system and what
corrective action, if any, the system plans to remove these
materials.
(iv) By October 10,
2000, any small system with a waiver granted prior to April 11, 2000 and that
has not previously met the requirements of part (7)(g)2. of this rule shall
provide the information required by that part.
5. Each ground water system that limits water
quality parameter monitoring to a subset of entry points under part (8)(c)3. of
this rule shall provide, by the commencement of such monitoring, written
correspondence to the Department that identifies the selected entry points and
includes information sufficient to demonstrate that the sites are
representative of water quality and treatment conditions throughout the
system.
(b) Source water
monitoring reporting requirements.
1. A water
system shall report the sampling results for all source water samples collected
in accordance with paragraph (9) of this rule within the first 10 days
following the end of each source water monitoring period (i.e., annually, per
compliance period, per compliance cycle) specified in paragraph (9) of this
rule.
2. With the exception of the
first round of source water sampling conducted pursuant to subparagraph (9)(b)
of this rule, the system shall specify any entry point which was not sampled
during previous monitoring periods and include an explanation of why the
sampling point has changed.
(c) Corrosion control treatment reporting
requirements. By the applicable dates under paragraph (2) of this rule, systems
shall report the following information:
1. For
systems demonstrating that they have already optimized corrosion control,
information required pursuant to part (2)(b)2. or 3. of this rule;
2. For systems required to optimize corrosion
control, their recommendation regarding optimal corrosion control treatments
pursuant to subparagraph (3)(a) of this rule;
3. For systems required to evaluate the
effectiveness of corrosion control treatments pursuant to subparagraph (3)(c)
of this rule, the information required by that subparagraph; and
4. For systems required to install optimal
corrosion control designated by the Department pursuant to subparagraph (3)(d)
of this rule, a letter certifying that the system has completed installing that
treatment.
(d) Source
water treatment reporting requirements. By the applicable dates pursuant to
paragraph (4) of this rule, systems shall provide the following information to
the Department:
1. If required under part
(4)(b)1. of this rule, their recommendation regarding source water
treatment;
2. For systems required
to install source water treatment pursuant to part (4)(b)2. of this rule, a
letter certifying that the system has completed installing the treatment
designated by the Department within 24 months after the Department designated
the treatment.
(e) Lead
service line replacement reporting requirements. A system shall report the
following information to the Department to demonstrate compliance with the
requirements of paragraph (5) of this rule:
1.
No later than 12 months after the end of the monitoring period in which a
system exceeds the lead action level in sampling referred to in subparagraph
(5)(a) of this rule, the system must submit written documentation to the
Department of the material evaluation conducted as required in subparagraph
(7)(a) of this rule, identify the initial number of lead service lines in its
distribution system at the time the system exceeds the lead action level and
provide the system's schedule for annually replacing at least 7 percent of the
initial number of lead service lines in its distribution system.
2. No later than 12 months after the end of
the monitoring period in which a system exceeds the lead action level in
sampling pursuant to subparagraph (5)(a) of this rule, and every 12 months
thereafter, the system shall demonstrate to the Department in writing that the
system has either:
(i) Replaced in the
previous 12 months at least 7 percent of the initial lead service lines (or a
greater number of lines specified by the Department pursuant to subparagraph
(5)(e) of this rule in its distribution system); or
(ii) Conducted sampling which demonstrates
that the lead concentration in all service line samples from an individual
line(s), taken pursuant to part (7)(b)3. of this rule is less than or equal to
0.015 mg/L. In such cases, the total number of lines replaced and/or which meet
the criteria in subparagraph (5)(c) of this rule shall equal at least 7 percent
of the initial number of lead lines identified under part 1. of this
subparagraph (or the percentage specified by the Department under subparagraph
(5)(e) of this rule).
3.
The annual writing submitted to the Department under part 2. of this
subparagraph shall contain the following information:
(i) The number of lead service lines
scheduled to be replaced during the previous year of the system's replacement
schedule;
(ii) The number and
location of each lead service line replaced during the previous year of the
system's replacement schedule; and
(iii) If water samples are collected, the
water lead concentration and location of each lead service line sampled, the
sampling method, and the date of sampling.
4. Any system which collects lead service
line samples following partial lead service line replacement required by
paragraph (5) of this rule shall report the results to the Department within
the first ten days of the month following the month in which the system
receives the laboratory results, or as specified by the Department. The
Department, at its discretion, may eliminate this requirement to report these
monitoring results. Systems shall also report any additional information as
specified by the Department, and in a time and manner prescribed by the
Department, to verify that all partial lead service line replacement activities
have taken place.
(f)
Public education program reporting requirements.
1. Any water system that is subject to the
public education requirements in paragraph (6) of this rule shall, within ten
days after the end of each period in which the system is required to perform
public education tasks in accordance with subparagraph (6)(c) of this rule,
send written documentation to the Department that contains:
(i) A demonstration that the system has
delivered the public education materials that meet the content requirements in
subparagraphs (6)(a) and (b) of this rule and the delivery requirements in
subparagraph (6)(c) of this rule; and
(ii) A list of all the newspapers, radio
stations, television stations, and facilities and organizations to which the
system delivered public education materials during the period in which the
system was required to perform public education tasks.
2. Unless required by the Department, a
system that previously has submitted the information required by subpart 1.(ii)
of this subparagraph need not resubmit the information required by subpart
1.(ii) of this subparagraph, as long as there have been no changes in the
distribution list and the system certifies that the public education materials
were distributed to the same list submitted previously.
3. No later than 3 months following the end
of the monitoring period, each system must mail a sample copy of the consumer
notification of tap results to the Department along with a certification that
the notification has been distributed in a manner consistent with the
requirements of subparagraph (6)(e) of this rule.
(g) Reporting of additional monitoring data.
Any system which collects sampling data in addition to that required by the
lead and copper control regulations shall report the results to the Department
by the end of the applicable monitoring period under paragraphs (7), (8) and
(9) of this rule during which the samples are collected.
(h) Reporting of 90th percentile lead and
copper concentrations where the Department calculates a system's 90th
percentile concentrations. A water system is not required to report the 90th
percentile lead and copper concentrations measured from among all lead and
copper tap water samples collected during each monitoring period, as required
by subpart (a)1.(iv) of this paragraph if:
1.
The Department has previously notified the water system that it will calculate
the water system's 90th percentile lead and copper concentrations, based on the
lead and copper tap results submitted pursuant to subpart 2.(i) of this
subparagraph, and has specified a date before the end of the applicable
monitoring period by which the system must provide the results of lead and
copper tap water samples;
2. The
system has provided the following information to the Department by the date
specified in part 1. of this subparagraph:
(i)
The results of all tap samples for lead and copper including the location of
each site and the criteria under parts (7)(a)3., 4., 5., 6. and/or 7. of this
rule under which the site was selected for the system's sampling pool, pursuant
to subpart (a)1.(i) of this paragraph; and
(ii) An identification of sampling sites
utilized during the current monitoring period that were not sampled during
previous monitoring periods, and an explanation why sampling sites have
changed; and
3. The
Department has provided the results of the 90th percentile lead and copper
calculations, in writing, to the water system before the end of the monitoring
period.
(12)
Recordkeeping requirements. Any system subject to the requirements of this rule
shall retain on its premises original records of all sampling data and
analyses, reports, surveys, letters, evaluations, schedules, Department
determinations, and any other information required by paragraphs (2) through
(9) of this rule. Each water system shall retain the records required by this
paragraph for no fewer than 12 years.