Utah Admin. Code R307-315-4 - Requirements

(1) An owner or operator of a boiler subject to this rule shall:
(a) install a burner that meets a NOx emission rate of nine parts per million by volume (ppmv) or less at 3% volume stack gas oxygen on a dry basis; and
(b) meet a CO emission rate of 400 ppmv or less at 3% volume stack gas oxygen on a dry basis.
(2) An owner or operator of a boiler subject to Subsection R307-315-4(1) shall:
(a) operate and maintain the boiler and boiler subsystems, including burners, according to the manufacturer's instructions;
(b) determine continued compliance based on Section R307-315-6; and
(c) meet the applicable recordkeeping requirements for any control device.

Notes

Utah Admin. Code R307-315-4
Adopted by Utah State Bulletin Number 2023-14, effective 7/10/2023 Amended by Utah State Bulletin Number 2024-22, effective 11/1/2024

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.