Utah Admin. Code R307-315-4 - Requirements
(1) An owner or operator of a boiler subject
to this rule shall:
(a) install a burner that
meets a NOx emission rate of nine parts per million by volume (ppmv) or less at
3% volume stack gas oxygen on a dry basis; and
(b) meet a CO emission rate of 400 ppmv or
less at 3% volume stack gas oxygen on a dry basis.
(2) An owner or operator of a boiler subject
to Subsection R307-315-4(1) shall:
(a) operate
and maintain the boiler and boiler subsystems, including burners, according to
the manufacturer's instructions;
(b) determine continued compliance based on
Section R307-315-6; and
(c) meet
the applicable recordkeeping requirements for any control device.