Utah Admin. Code R309-211-5 - Routine Monitoring Requirements for Water Systems Serving 1,000 or Fewer People
(1) General.
(a) The provisions of this section apply to
water systems serving 1,000 or fewer people.
(b) Following any total coliform-positive
sample taken under the provisions of this section, systems must comply with the
repeat monitoring requirements and E. coli analytical requirements in
R309-211-7.
(c) Once all monitoring required by this
section and
R309-211-7 for a calendar month has been completed, systems must determine whether any
coliform treatment technique triggers specified in
R309-211-8 have been exceeded. If any trigger has been exceeded, systems must complete
assessments as required by
R309-211-8.
(2) Monitoring frequency for total
coliforms. The monitoring frequency for total coliforms is one
sample/month.
(3) Seasonal systems.
(a) All seasonal systems must demonstrate
completion of a Director-approved start-up procedure, which may include a
requirement for startup sampling prior to serving water to the
public.
(b) A seasonal system must
monitor every month that it is in operation.
(c) The Director may exempt any seasonal
system from some or all of the requirements for seasonal systems if the entire
distribution system remains pressurized during the entire period that the
system is not operating.