Utah Admin. Code R309-550-7 - Separation of Water Mains and Transmission Lines from Sewers
(1) Basic Separation Standards.
(a) The horizontal distance between water
lines and sanitary sewer lines shall be at least 10 feet. Where a water main
and a sewer line must cross, the water main shall be at least 18 inches above
the sewer line. Separation distances shall be measured edge-to-edge (i.e. from
the nearest edges of the facilities).
(b) Water mains and sewer lines shall not be
installed in the same trench.
(c)
Where local conditions make it impossible to install water or sewer lines at
separation distances required by subsection (a), the sewer pipes are in good
condition, and there is not high groundwater in the area, it may be acceptable
if the design includes a minimum horizontal separation of 6 feet and a minimum
vertical clearance of 18 inches with the waterline being above. In order to
determine whether the design is acceptable, the following information shall be
submitted as part of the plans for review.
(i)
reason for not meeting the minimum separation standard;
(ii) location where the water and sewer line
separation is not being met;
(iii)
horizontal and vertical clearance that will be achieved;
(iv) sewer line information including pipe
material, condition, size, age, type of joints, thickness or pressure class,
whether the pipe is pressurized or not, etc.;
(v) water line information including pipe
material, condition, size, age, type of joints, thickness or pressure class,
etc.;
(vi) ground water and soil
conditions; and ,
(vii) any
mitigation efforts .
(d) If the basic separation standards as
outlined in subsections (a) though (c) above cannot be met, an exception to the
rule can be applied for with additional mitigation measures to protect public
health, in accordance with
R309-105-6(2)(b).
(3) Special Provisions.
The following special provisions apply to all situations:
(a) The basic separation standards
are applicable under normal conditions for sewage collection lines and water
distribution mains. More stringent requirements may be necessary if conditions
such as high groundwater exist.
(b) All water transmission lines that may
become unpressurized shall not be installed within 20 feet of sewer lines.
(c) In the installation of water
mains or sewer lines, measures shall be taken to prevent or minimize
disturbances of the existing line.
(d) Special consideration shall be given to
the selection of pipe materials if corrosive conditions are likely to exist or
where the minimum separation distances cannot be met. These conditions may be
due to soil type, groundwater, and/or the nature of the fluid conveyed in the
conduit, such as a septic sewage which produces corrosive hydrogen sulfide.
(e) Sewer Force Mains
(i) When a new sewer force main crosses under
an existing water main, all portions of the sewer force main within 10 feet
(horizontally) of the water main shall be enclosed in a continuous sleeve.
(ii) When a new water main crosses
over an existing sewer force main, the water main shall be constructed of pipe
materials with a minimum rated working pressure of 200 psi or equivalent
pressure rating.
(4) Water Service Laterals Crossing Sewer
Mains and Laterals.
Water service laterals shall conform to all requirements given herein for the separation of water and sewer lines.