Utah Admin. Code R315-264-1053 - Standards: Compressors
(a) Each compressor
shall be equipped with a seal system that includes a barrier fluid system and
that prevents leakage of total organic emissions to the atmosphere, except as
provided in Subsections R315-264-1053(h) and (i).
(b) Each compressor seal system as required
in Subsection R315-264-1053(a) shall be:
(1)
Operated with the barrier fluid at a pressure that is at all times greater than
the compressor stuffing box pressure, or
(2) Equipped with a barrier fluid system that
is connected by a closed-vent system to a control device that complies with the
requirements of Section
R315-264-1060,
or
(3) Equipped with a system that
purges the barrier fluid into a hazardous waste stream with no detectable
emissions to atmosphere.
(c) The barrier fluid shall not be a
hazardous waste with organic concentrations 10 percent or greater by weight.
(d) Each barrier fluid system as
described in Subsections R315-264-1053(a) through (c) shall be equipped with a
sensor that will detect failure of the seal system, barrier fluid system, or
both.
(e)
(1) Each sensor as required in Subsection
R315-264-1053(d) shall be checked daily or shall be equipped with an audible
alarm that shall be checked monthly to ensure that it is functioning properly
unless the compressor is located within the boundary of an unmanned plant site,
in which case the sensor shall be checked daily.
(2) The owner or operator shall determine,
based on design considerations and operating experience, a criterion that
indicates failure of the seal system, the barrier fluid system, or both.
(f) If the sensor
indicates failure of the seal system, the barrier fluid system, or both based
on the criterion determined under Subsection R315-264-1053(e)(2), a leak is
detected.
(g)
(1) When a leak is detected, it shall be
repaired as soon as practicable, but not later than 15 calendar days after it
is detected, except as provided in Section
R315-264-1059.
(2) A first attempt at repair,
e.g., tightening the packing gland, shall be made no later than 5 calendar days
after each leak is detected.
(h) A compressor is exempt from the
requirements of Subsections R315-264-1053(a) and (b) if it is equipped with a
closed-vent system capable of capturing and transporting any leakage from the
seal to a control device that complies with the requirements of Section
R315-264-1060,
except as provided in Subsection R315-264-1053(i).
(i) Any compressor that is designated, as
described in Subsection
R315-264-1064(g)(2),
for no detectable emissions as indicated by an instrument reading of less than
500 ppm above background is exempt from the requirements of Subsections
R315-264-1053(a) through (h) if the compressor:
(1) Is determined to be operating with no
detectable emissions, as indicated by an instrument reading of less than 500
ppm above background, as measured by the method specified in Subsection
R315-264-1063(c).
(2) Is tested for compliance with
Subsection R315-264-1053(i)(1) initially upon designation, annually, and at
other times as requested by the Director.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.