Utah Admin. Code R315-265-1088 - Air Emission Standards for Tanks, Surface Impoundments, and Containers - Standards: Closed-Vent Systems and Control Devices
(a) Section R315-265-1088 applies to each
closed-vent system and control device installed and operated by the owner or
operator to control air emissions in accordance with standards of Sections
R315-265-1080 through R315-265-1090.
(b) The closed-vent system shall meet the
following requirements:
(1) The closed-vent
system shall route the gases, vapors, and fumes emitted from the hazardous
waste in the waste management unit to a control device that meets the
requirements specified in Subsection R315-265-1088(c).
(2) The closed-vent system shall be designed
and operated in accordance with the requirements specified in Subsection
R315-265-1033(j).
(3) If the
closed-vent system includes bypass devices that could be used to divert the gas
or vapor stream to the atmosphere before entering the control device, each
bypass device shall be equipped with either a flow indicator as specified in
Subsection R315-265-1088(b)(3)(i) or a seal or locking device as specified in
Subsection R315-265-1088(b)(3)(ii). For the purpose of complying with
Subsection R315-265-1088(b), low leg drains, high point bleeds, analyzer vents,
open-ended valves or lines, spring-loaded pressure relief valves, and other
fittings used for safety purposes are not considered to be bypass devices.
(i) If a flow indicator is used to comply
with Subsection R315-265-1088(b)(3), the indicator shall be installed at the
inlet to the bypass line used to divert gases and vapors from the closed-vent
system to the atmosphere at a point upstream of the control device inlet. For
Subsection R315-265-1088(b), a flow indicator means a device which indicates
the presence of either gas or vapor flow in the bypass line.
(ii) If a seal or locking device is used to
comply with Subsection R315-265-1088(b)(3), the device shall be placed on the
mechanism by which the bypass device position is controlled, for example, valve
handle, damper lever, if the bypass device is in the closed position such that
the bypass device cannot be opened without breaking the seal or removing the
lock. Examples of such devices include, but are not limited to, a car-seal or a
lock-and-key configuration valve. The owner or operator shall visually inspect
the seal or closure mechanism at least once every month to verify that the
bypass mechanism is maintained in the closed position.
(4) The closed-vent system shall be inspected
and monitored by the owner or operator in accordance with the procedure
specified in Subsection R315-265-1033(k).
(c) The control device shall meet the
following requirements:
(1) The control
device shall be one of the following devices:
(i) A control device designed and operated to
reduce the total organic content of the inlet vapor stream vented to the
control device by at least 95 percent by weight;
(ii) An enclosed combustion device designed
and operated in accordance with the requirements of Subsection
R315-265-1033(c); or
(iii) A flare
designed and operated in accordance with the requirements of Subsection
R315-265-1033(d).
(2)
The owner or operator who elects to use a closed-vent system and control device
to comply with the requirements of Section R315-265-1088 shall comply with the
requirements specified in Subsections R315-265-1088(c)(2)(i) through
R315-265-1088(c)(2)(vi).
(i) Periods of
planned routine maintenance of the control device, during which the control
device does not meet the specifications of Subsections R315-265-1088(c)(1)(i),
R315-265-1088(c)(1)(ii), or R315-265-1088(c)(1)(iii), as applicable, shall not
exceed 240 hours per year .
(ii) The
specifications and requirements in Subsections R315-265-1088(c)(1)(i),
R315-265-1088(c)(1)(ii), or R315-265-1088(c)(1)(iii) for control devices do not
apply during periods of planned routine maintenance.
(iii) The specifications and requirements in
Subsections R315-265-1088(c)(1)(i), R315-265-1088(c)(1)(ii), or
R315-265-1088(c)(1)(iii) for control devices do not apply during a control
device system malfunction.
(iv) The
owner or operator shall demonstrate compliance with the requirements of
Subsection R315-265-1088(c)(2)(i), for example, planned routine maintenance of
a control device, during which the control device does not meet the
specifications of Subsections R315-265-1088(c)(1)(i), R315-265-1088(c)(1)(ii),
or R315-265-1088(c)(1)(iii), as applicable, shall not exceed 240 hours per
year , by recording the information specified in Subsection
R315-265-1090(e)(1)(v).
(v) The
owner or operator shall correct control device system malfunctions as soon as
practicable after their occurrence in order to minimize excess emissions of air
pollutants.
(vi) The owner or
operator shall operate the closed-vent system such that gases, vapors, and
fumes are not actively vented to the control device during periods of planned
maintenance or control device system malfunction, for example, periods if the
control device is not operating or not operating normally, except in cases if
it is necessary to vent the gases, vapors, or fumes to avoid an unsafe
condition or to implement malfunction corrective actions or planned maintenance
actions.
(3) The owner
or operator using a carbon adsorption system to comply with Subsection
R315-265-1088(c)(1) shall operate and maintain the control device in accordance
with the following requirements:
(i)
Following the initial startup of the control device, all activated carbon in
the control device shall be replaced with fresh carbon on a regular basis in
accordance with the requirements of Subsections R315-265-1033(g) or
R315-265-1033(h).
(ii) All carbon
that is a hazardous waste and that is removed from the control device shall be
managed in accordance with the requirements of Subsection R315-265-1033(m),
regardless of the average volatile organic concentration of the
carbon.
(4) An owner or
operator using a control device other than a thermal vapor incinerator, flare,
boiler, process heater, condenser, or carbon adsorption system to comply with
Subsection R315-265-1088(c)(1) shall operate and maintain the control device in
accordance with the requirements of R315-265-1033(i).
(5) The owner or operator shall demonstrate
that a control device achieves the performance requirements of Subsection
R315-265-1088(c)(1) as follows:
(i) An owner
or operator shall demonstrate using either a performance test as specified in
Subsection R315-265-1088(c)(5)(iii) or a design analysis as specified in
Subsection R315-265-1088(c)(5)(iv) the performance of each control device
except for the following:
(A) A
flare;
(B) A boiler or process
heater with a design heat input capacity of 44 megawatts or greater;
(C) A boiler or process heater into which the
vent stream is introduced with the primary fuel;
(D) A boiler or industrial furnace burning
hazardous waste for which the owner or operator has been issued a final permit
under Rule R315-270 and has designed and operates the unit in accordance with
the requirements of Sections
R315-266-100
through
R315-266-112;
or
(E) A boiler or industrial
furnace burning hazardous waste for which the owner or operator has designed
and operates in accordance with the interim status requirements of Sections
R315-266-100
through
R315-266-112.
(ii) An owner or operator shall
demonstrate the performance of each flare in accordance with the requirements
specified in Subsection R315-265-1033(e).
(iii) For a performance test conducted to
meet the requirements of Subsection R315-265-1088(c)(5)(i), the owner or
operator shall use the test methods and procedures specified in Subsections
R315-265-1034(c)(1) through R315-265-1034(c)(4).
(iv) For a design analysis conducted to meet
the requirements of Subsection R315-265-1088(c)(5)(i), the design analysis
shall meet the requirements specified in Subsection
R315-265-1035(b)(4)(iii).
(v) The
owner or operator shall demonstrate that a carbon adsorption system achieves
the performance requirements of Subsection R315-265-1088(c)(1) based on the
total quantity of organics vented to the atmosphere from all carbon adsorption
system equipment that is used for organic adsorption, organic desorption or
carbon regeneration, organic recovery, and carbon disposal.
(6) If the owner or operator and
the Director do not agree on a demonstration of control device performance
using a design analysis then the disagreement shall be resolved using the
results of a performance test performed by the owner or operator in accordance
with the requirements of Subsection R315-265-1088(c)(5)(iii). The Director may
choose to have an authorized representative observe the performance
test .
(7) The closed-vent system
and control device shall be inspected and monitored by the owner or operator in
accordance with the procedures specified in Subsections R315-265-1033(f)(2) and
R315-265-1033(k). The readings from each monitoring device required by
Subsection R315-265-1033(f)(2) shall be inspected at least once each operating
day to check control device operation. Any necessary corrective measures shall
be immediately implemented to ensure the control device is operated in
compliance with the requirements of Section R315-265-1088.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.