Utah Admin. Code R317-3-7 - Biological Treatment
7.1. Trickling
Filters
A. General. Trickling filters shall
be preceded by effective settling tanks equipped with scum and grease
collecting devices, or other suitable pretreatment facilities.
B. Hydraulics
1. Distribution. The sewage may be
distributed over the filter by rotary distributors or other suitable devices
which will ensure uniform wastewater distribution to the surface area. Uniform
hydraulic distribution of sewage on the filters is required.
2. For reaction type distributors, a minimum
head of 24 inches (61 centimeters) between low water level in the siphon
chamber and center of the arms is required. Similar allowance in design shall
be provided for added pumping head requirements where pumping to the reaction
type distributor is used. The applicant should evaluate other types of drivers
and drives.
3. A minimum clearance
of 6 inches (15 centimeters) between media and distributor arms shall be
provided. Larger clearance than 6 inches (15 centimeters) must be provided
where ice buildup may occur.
C. Wastewater Application. Application of the
sewage shall be continuous. The piping system shall be designed for
recirculation. The design must provide for routine flushing of filters by heavy
dosing at intermittent intervals.
D. Piping System. The piping system,
including dosing equipment and distributor, shall be designed to provide
capacity for the peak design rate of flow, including recirculation.
E. Media
1.
Quality
a. The media may be crushed rock,
slag, or specially manufactured material. The media shall be durable, resistant
to spalling or flaking and insoluble in sewage. The top 18 inches (46
centimeters) shall have a loss by the 20-cycle, sodium sulfate soundness test
of not more than 10 percent. The balance is to pass a ten-cycle test using the
same criteria. Slag media shall be free from iron.
b. Manufactured media shall be resistant to
ultraviolet degradation, disintegration, erosion, aging, all common acids and
alkalies, organic compounds, and fungus and biological attack. Such media shall
be structurally capable of supporting a man's weight or a suitable access
walkway shall be provided to allow for distributor maintenance.
2. Depth. The filter design shall
provide for a depth of:
a. not less than 5
feet (1.5 meters) above the underdrains, but not more than 10 feet (3 meters)
when rock or slag media is used in the filters.
b. not less than 10 feet (3 meters) above the
underdrains to provide adequate contact time with the wastewater, but not more
than 30 feet (9 meters) unless additional structural construction and aeration
are provided, when manufactured media is used in the filters.
3. Size and Grading of Media
a. Rock, Slag and Similar Media
(1) Rock, slag, and similar media shall not
contain more than 5 percent by weight of pieces whose longest dimension is
three times the least dimension.
(2) Media shall be free from thin, elongated
and flat pieces, dust, clay, sand or fine material and shall conform to the
size and grading when mechanically graded over vibrating screens with square
openings, as shown in Table
R317-3-7.1(E)
(3(a)(2).
b.
Manufactured Media. The applicant must evaluate suitability of manufactured
media on the basis of experience with installations handling similar wastes and
loadings.
c. Handling and Placing
of Media. Material delivered to the filter site shall be stored on wood-
planked or other approved clean, hard-surfaced areas. All material shall be
rehandled at the filter site and no material shall be dumped directly into the
filter. Crushed rock, slag and similar media shall be washed and rescreened or
forked at the filter site to remove all fines. Such material shall be placed by
hand to a depth of 12 inches (30 centimeters) above the tile underdrains. The
remainder of material may be placed by means of belt conveyors or equally
effective methods approved by the design engineer. All material shall be
carefully placed so as not to damage the underdrains. Manufactured media shall
be handled and placed as approved by the engineer. Trucks, tractors, and other
heavy equipment shall not be driven over the filter during or after
construction.
F. Underdrain System
1. Arrangement. Underdrains with semicircular
inverts or equivalent should be provided and the underdrainage system shall
cover the entire floor of the filter. Inlet openings into the underdrains shall
have an unsubmerged gross combined area equal to at least 15 percent of the
surface area of the filter.
2.
Hydraulic Capacity and Ventilation.
a. The
underdrains shall have a minimum slope of 1 percent. Effluent channels shall be
designed to produce a minimum velocity of two (2) feet per second (0.61 meters
per second) at average daily rates of application to the filter.
b. The underdrainage system, effluent
channels, and effluent pipe shall be designed to permit a free passage of air
preventing septicity within the filter. The size of drains, channels, and pipe
should be such that not more than 50 percent of their cross-sectional area will
be submerged under the design peak hydraulic loading, including proposed or
possible future recirculated flows. Forced air ventilation must be provided for
deep or covered filters using manufactured media. The design of filters should
be compatible for the installation of odor control equipment such as covers,
forced air ventilation, scrubber, etc., as a retrofit.
3. Flushing. The design should include means
for flushing of the underdrains. In small filters, use of a peripheral head
channel with vertical vents is acceptable for flushing purposes. Means or
facilities of inspection of underdrainage should be provided.
G. Special Features
1. Flooding. Appropriate valves, sluice
gates, or other structures shall be provided to enable flooding of filters
comprised of rock or slag media.
2.
Freeboard. A freeboard of not less than 4 feet (1.2 meters) should be provided
for tall filters using manufactured media, to maximize the containment of
windblown spray.
3. Maintenance.
All distribution devices, underdrains, channels, and pipes shall be installed
so that they may be properly maintained, flushed or drained.
4. Freeze Protection. When climatic
conditions are expected to result in operational problems due to cold
temperatures, the filters may be covered for protection against freezing;
maintaining operation and treatment efficiencies.
5. Recirculation. The piping and pumping
systems shall be designed for recirculation rates as required to achieve
sufficient wetting of biofilm and the design efficiency.
6. Recirculation Measurement. Recirculation
rate to the filters shall be measured using flow measurement and recording
devices. Time lapse meters and pump head recording devices are acceptable for
facilities treating less than 1 million gallons per day (3,785 cubic meters per
day).
H. Rotary
Distributor Seals. Mercury seals are not permitted. The design of the
distributor support septum shall provide for convenient and easy seal
replacement to assure continuity of operation.
I. Multi-Stage Filters. The foregoing
standards in this rule also apply to all multi-stage filters.
J. Unit Sizing
1. Required volumes of rock or slag media
filters shall be based upon the following equations: For Single or First stage
of Trickling Filter: E = 100 - ((100 / ( 3 + 2 ( R/I))) + ( 0.4 x ( W / V) -
10)). For Second stage of Trickling Filter: E = 100 x (( 1 + (
R2 / I)) / ( 2 + ( R2 / I)))
where, E = Efficiency, percent R = recirculated flow through trickling filter,
mgd I = raw sewage flow, mgd W = pounds of BOD5 per day
in raw sewage V = volume of filter media in 1000 cubic feet
R2 = recirculated flow through second-stage trickling
filter, mgd.
2. The required volume
of media may be determined by pilot testing or use of any of the various
empirical design equations that have been verified through actual full scale
experience. Such calculations must be submitted if pilot testing is not
utilized. Pilot testing is recommended to verify performance predictions based
upon the various design equations, particularly when significant amounts of
industrial wastes are present.
3.
Expected performance of filters packed with manufactured media shall be
determined from documented full scale experience on similar installations or
through actual use of a pilot plant on site.
K. Nitrification
1. Trickling filters may be used for
nitrification. The design should be based as shown in Table
R317-3-7.1(K)(1).
2. Nitrification
is affected by variations in flow, loadings and temperature, and other factors.
Therefore, the applicant must conduct pilot studies before developing the
design criteria.
L.
Design Safety Factors. Trickling filters are affected by diurnal load
conditions. The volume of media determined from either pilot plant studies or
use of acceptable design equations shall be based upon organic loading at the
maximum design rate of flow rather than the average design rate of flow.
7.2. Activated Sludge
A. General. The activated sludge process and
its several modifications may be used to accomplish varied degrees of removal
of suspended solids, and reduction of carbonaceous and nitrogenous oxygen
demand. The degree and consistency of treatment required, type of waste to be
treated, proposed plant size, anticipated degree of operation and maintenance,
and operating and capital costs determine the choice of the process to be used.
The design shall provide for flexibility in operation. Plants over 1 million
gallons per day (3,785 cubic meters per day) shall be designed to facilitate
easy conversion to various operational modes. In severe climates, protection
against freezing shall be provided to ensure continuity of operation and
performance.
B. Aeration
1. Capacities and Permissible Loadings
a. The design of the aeration tank for any
particular adaptation of the process shall be based on full scale experience at
the plants receiving wastewater of similar characteristics under similar
climatic conditions, pilot plant studies, or calculations based on process
kinetics parameters reported in technical literature. The size of treatment
plant, diurnal load variations, degree of treatment required, temperature, pH,
and reactor dissolved oxygen when designing for nitrification, influence the
design. Calculations using values differing substantially from those in the
table shown below must reference actual operational data.
b. The applicant must substantiate capability
of the aeration and clarification systems in the processes using mixed liquor
suspended solids levels greater than 5,000 milligrams per liter.
c. The applicant shall use the values shown
in Table R317-3-7.2(B)(1)(c) to determine the aeration tank capacities and
permissible loadings for the several adaptations of the processes, when process
design calculations are not submitted. These values are based on the average
design rate of flow, and apply to plants receiving peak to average diurnal load
ratios ranging from about 2:1 to 4:1.
2. Arrangement of Aeration Tanks
a. Dimensions. Effective mixing and
utilization of air must be the basis of dimensions of each independent mixed
liquor aeration tank or return sludge reaeration tank. Liquid depths should not
be less than 10 feet (3 meters) or more than 30 feet (9 meters) unless the
applicant justifies the need for shallower or deeper tanks.
b. Short-circuiting. The shape of the tank
and the installation of aeration equipment should provide for positive control
of short-circuiting through the aeration tank.
c. Number of Units. Total aeration tank
volume shall be divided among two or more units, capable of independent
operation, to meet applicable effluent limitations and reliability
guidelines.
d. Inlets and Outlets.
Inlets and outlets for each aeration tank unit shall be suitably equipped with
valves, gates, stop plates, weirs, or other devices to permit controlling the
flow to any unit and to maintain reasonable constant liquid level. The
hydraulic properties of the system shall permit the maximum instantaneous
hydraulic load to be carried with any single aeration tank unit out of
service.
e. Conduits. Channels and
pipes carrying liquids with solids in suspension shall be designed to maintain
self-cleaning velocities or shall be agitated to keep such solids in suspension
at all rates of flow within the design limits. Drains shall be installed in the
aeration tank to drain segments or channels which are not being used due to
alternate flow patterns.
f.
Freeboard. All aeration tanks should have a freeboard of not less than 18
inches (46 centimeters). Additional freeboard or windbreak may be necessary to
protect against freezing or windblown spray.
3. Aeration Requirements
a. Oxygen requirements must be calculated
based on factors such as, maximum organic loading, degree of treatment, level
of suspended solids concentration (mixed liquor) to be maintained, and
uniformly maintaining a minimum dissolved oxygen concentration in the aeration
tank, at all times, of two milligrams per liter.
b. When pilot plant or experimental data on
oxygenation requirements are not available, the design oxygen requirements
shall be calculated on the basis of:
(1) 1.2
pounds 02 per pound of maximum
BOD5 applied to the aeration tanks (1.2 kilograms
02 per kilogram of maximum BOD5),
for carbonaceous BOD5 removal in all activated sludge
processes with the exception of the extended aeration process,
(2) 2 pounds 02 per
pound of maximum BOD5 applied to the aeration tanks (two
kilograms 02 per kilogram of maximum
BOD5) for carbonaceous BOD5
removal in the extended aeration process,
(3) 4.6 pounds 02 per
pound of maximum total kjeldahl nitrogen (TKN) applied to the aeration tanks
(1.2 kilograms 02 per kilogram of maximum TKN), for
oxidizing ammonia in the case of nitrification, and
(4) oxygen demand due to the high
concentrations of BOD5 and TKN associated with recycle
flows such as, digester supernatant, heat treatment supernatant, belt filter
pressate, vacuum filtrate, elutriates, etc.
c. Oxygen utilization should be maximized per
unit power input. The aeration system should be designed to match the diurnal
organic load variation while economizing on power input.
4. Diffused Air Systems
a. The design of the diffused air system to
provide the oxygen requirements shall be done using data derived from pilot
testing or an empirical approach.
b. Air requirements for a diffused air system
may be determined by use of any of the recognized equations incorporating such
factors as:
(1) tank depth;
(2) alpha factor of waste;
(3) beta factor of waste;
(4) certified aeration device transfer
efficiency;
(5) minimum aeration
tank dissolved oxygen concentrations;
(6) critical wastewater temperature;
and
(7) altitude of
plant.
c. In the absence
of experimentally determined alpha and beta factors by an independent
laboratory for the manufacturer or at the site, wastewater transfer efficiency
shall be assumed to be 50 percent of clean water efficiency for plants treating
primarily (90 percent or greater) domestic sewage. Treatment plants where the
waste contains higher percentages of industrial wastes shall use a
correspondingly lower percentage of clean water efficiency and shall submit
calculations to justify such a percentage.
d. The design air requirements shall be
calculated on the basis of:
(1) 1,500 cubic
feet per pound of maximum BOD5 applied to the aeration
tanks (94 cubic meters per kilogram of maximum BOD5),
for carbonaceous BOD5 removal in all activated sludge
processes with the exception of the extended aeration process,
(2) 2,000 cubic feet per pound of maximum
BOD5 applied to the aeration tanks (125 cubic meters per
kilogram of maximum BOD5) for carbonaceous
BOD5 removal in the extended aeration process,
(3) 5800 cubic feet per pound of maximum
total kjeldahl nitrogen (TKN) applied to the aeration tanks (360 cubic meters
per kilogram of maximum TKN), for oxidizing ammonia in the case of
nitrification,
(4) corresponding
air quantities for satisfaction of oxygen demand due to the high concentrations
of BOD5 and TKN associated with recycle flows such as,
digester supernatant, heat treatment supernatant, belt filter pressate, vacuum
filtrate, elutriates, etc., and
(5)
air required for channels, pumps, aerobic digesters, or other uses.
e. The capacity of blowers or air
compressors, particularly centrifugal blowers, must be calculated on the basis
of air intake temperature of 40 degrees Centigrade (104 degrees Fahrenheit) or
higher and the less than normal operating pressure. The capacity of drive motor
must be calculated on the basis of air intake temperature of -30 degrees
Centigrade (-22 degrees Fahrenheit) or less. The design must include means of
controlling the rate of air delivery to prevent overheating or damage to the
motor.
f. The blowers shall be
provided in multiple units, so arranged and in such capacities as to meet the
maximum air demand with the single largest unit out of service. The design
shall also provide for varying the volume of air delivered in proportion to the
load demand of the plant. Aeration equipment shall be easily adjustable in
increments and shall maintain solids suspension within these limits.
g. Diffuser systems shall be capable of
providing for the maximum design oxygen demand or 200 percent of the average
design oxygen demand, whichever is larger. The air diffusion piping and
diffuser system shall be capable of delivering normal air requirements with
minimal friction losses.
h. Air
piping systems should be designed such that total head loss from blower outlet
(or silencer outlet where used) to the diffuser inlet does not exceed 0.5
pounds per square inch (0.04 kilogram per square centimeter) at average
operating conditions.
i. The
spacing of diffusers should be in accordance with the oxygen requirements
through the length of the channel or tank, and should be designed to facilitate
adjustment of their spacing without major revision to air header piping.
Removable diffuser assemblies are recommended to minimize downtime of aeration
tanks.
j. Individual assembly units
of diffusers shall be equipped with control valves, preferably with indicator
markings for throttling, or for complete shutoff. Diffusers in any single
assembly shall have substantially uniform pressure loss.
k. Air filters shall be provided in numbers,
arrangements, and capacities to furnish, at all times, an air supply
sufficiently free from dust to prevent damage to blowers and clogging of the
diffuser system used.
5.
Mechanical Aeration Systems
a. Oxygen
Transfer Performance. The mechanism and drive unit shall be designed for the
expected conditions in the aeration tank in terms of the power performance. The
mechanical aerator performance shall be verified by certified
testing.
b. Design Requirements.
The design requirements of a mechanical aeration system shall accomplish the
following:
(1) Maintain a minimum of 2.0
milligrams per liter of dissolved oxygen in the mixed liquor at all times
throughout the tank or basin;
(2)
Maintain all biological solids in suspension;
(3) Meet maximum oxygen demand and maintain
process performance with the largest unit out of service; and
(4) Provide for varying the amount of oxygen
transferred in proportion to the load demand on the plant.
c. Winter Protection. Due to high heat loss
and the nature of spray-induced agitation, the mechanism, as well as subsequent
treatment units, shall be protected from freezing where extended cold weather
conditions occur.
6.
Return Sludge Equipment
a. Return Sludge Rate
(1) The minimum permissible return sludge
rate of withdrawal from the final settling tank is a function of the
concentration of suspended solids in the mixed liquor entering it, the sludge
volume index of these solids, and the length of time these solids are retained
in the settling tank. Since undue retention of solids in the final settling
tanks may be deleterious to both the aeration and sedimentation phases of the
activated sludge process, the rate of sludge return expressed as a percentage
of the average design flow of sewage should be between the limits set forth in
Table R317-3-7.2(B)(6)(a)(1).
(2)
The rate of sludge return shall be varied by means of variable speed motors,
drives, or timers (in plants designed for less than one million gallons per day
- 3,785 cubic meters per day) to pump sludge at the above rates.
b. Return Sludge Pumps
(1) If motor driven return sludge pumps are
used, the maximum return sludge capacity shall be with the largest pump out of
service. A positive head should be provided on pump suctions. Pumps should have
at least 3 inch (7.6 centimeters) suction and discharge openings.
(2) If air lifts are used for returning
sludge from each settling tank hopper, no standby unit is required provided the
design of the air lifts are such to facilitate their rapid and easy cleaning
and provided standby air lifts are provided. Air lifts should be at least 3
inches (7.6 centimeters) in diameter.
c. Return Sludge Piping. Discharge piping
shall not be less than 4 inches (10 centimeters) in diameter, and should be
designed to maintain a velocity of not less than two (2) feet per second (0.61
meters per second) when return sludge facilities are operating at normal return
sludge rates. Sight glasses, sampling ports and rate of flow controllers for
return activated sludge flow from each settling tank hopper shall be
provided.
7. Waste
Sludge Facilities
a. The design of waste
sludge control facilities should be based on a logically developed solids mass
balance at the maximum design flow. Otherwise, a maximum capacity of not less
than 25 percent of the average design flow shall be provided, and function
satisfactorily at rates of 0.5 percent of average sewage flow or a minimum of
10 gallons per minute (0.63 liters per second), whichever is larger.
b. Sight glasses, sampling ports and rate of
flow controllers for waste activated sludge flow shall be provided.
c. Waste sludge may be discharged to the
concentration or thickening tank, primary settling tank, sludge digestion tank,
vacuum filters, other thickening equipment, or any practical combination of
these units.
7.3. Flow Measurement. Instrumentation should
be provided in all plants for indicating flow rates of raw sewage or primary
effluent, return sludge, and air to each tank unit. For plants designed for the
average design rate of flow of 1 million gallons per day (3,785 cubic meters
per day) or more, these devices should total, record, and indicate the rate of
flow. Where the design provides for all return sludge to be mixed with the raw
sewage (or primary effluent) at one location, then the mixed liquor flow rate
to each aeration unit should be measured.
7.4. Other Biological Systems. The Director
may consider and approve new biological treatment processes with promising
applicability in wastewater treatment. The approval will be based on the
required engineering data for new process evaluation as provided in this
rule.
7.5. Packaged Plants. The
Director may consider and approve packaged biological treatment plants only
when there are no other and appropriate alternatives for waste treatment. These
type of plants shall be designed for handling large flow variations and to meet
all requirements contained in this rule. The applicant must consider the need
for close attention and competent operating supervision, including routine
laboratory control, when proposing a packaged plant.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.