Utah Admin. Code R317-4-14 - Appendices
(1) Appendix A. Septic Tank Construction.
(a) Plans for each septic tank or underground
holding tank shall be submitted to the division for approval. Such plans shall
show all dimensions, capacities, reinforcing, maximum depth of soil cover, and
such other pertinent data as may be required. Each tank shall conform to the
design drawing and shall be constructed under strict, controlled supervision by
the manufacturer.
(i) Each precast reinforced
concrete tank shall conform to the following:
(A) The walls and base of each precast tank
shall be securely bonded together and the walls shall be of monolithic or keyed
construction.
(B) The sidewalls and
bottom of such a tank shall be at least 3 inches in thickness.
(C) The top shall have a minimum thickness of
4 inches.
(D) Each tank shall have
reinforcing of at least 6 inch x 6 inch No. 6, welded wire fabric, or
equivalent. Exceptions to this reinforcing requirement may be considered by the
division based on an evaluation of acceptable structural engineering data
submitted by the manufacturer.
(E)
All concrete used in each precast tank shall be Class A, at least 4,000 pounds
per square inch, and shall be vibrated or well-rodded to minimize honeycombing
and to assure water tightness.
(F)
Precast sections shall be set evenly in a full bed of sealant. If grout is used
it shall consist of two parts plaster sand to one part cement with sufficient
water added to make the grout flow under its own weight.
(G) Any excessively mortared joint should be
trimmed flush.
(H) The inside and
outside of each mortar joint shall be sealed with a waterproof bituminous
sealing compound.
(I) For early
reuse of forms, the concrete may be steam cured. Other curing by water spraying
or a membrane curing compound may be used and shall comply to best acceptable
methods as outlined in Guide to Curing Concrete, ACI308R-01, by American
Concrete Institute, Farmington Hills, Michigan.
(ii) Each poured-in-place concrete septic
tank shall conform to the following:
(A) The
top of each poured-in-place septic tank with a liquid capacity of 1,000 to
1,250 gallons shall be a minimum of 4 inches thick, and reinforced with 3/8
inch reinforcing rods 12 inches on center both ways, or equivalent.
(B) The top of each tank with a liquid
capacity of greater than 1,250 gallons shall be a minimum of 6 inches thick,
and reinforced with 3/8 inch reinforcing rods 8 inches on center both ways, or
equivalent.
(C) The walls and floor
shall be a minimum of 6 inches thick. The walls shall be reinforced with 3/8
inch reinforcing rods 8 inches on center both ways, or equivalent. Inspections
by the regulatory authority may be required of the tank reinforcing steel
before any concrete is poured.
(D)
A 6 inch water stop shall be used at the wall-floor juncture to ensure water
tightness.
(E) All concrete used in
poured-in-place tanks shall be Class A, at least 4,000 pounds per square inch,
and shall be vibrated or well-rodded to minimize honeycombing and to ensure
water tightness.
(F) Curing of
concrete shall comply with the requirements in Subsection
R317-4-14(1)(a)(i)(II).
(iii) Each fiberglass tank shall conform to
the following:
(A) Each fiberglass tank shall
comply with one of the following criteria for acceptance:
(I) The Interim Guide Criteria for
Glass-Fiber-Reinforced Polyester Septic Tanks, International Association of
Plumbing and Mechanical Officials Z1000-2007. The identifying seal of the
International Association of Plumbing and Mechanical Officials shall be
permanently embossed in the fiberglass as evidence of compliance.
(II) Manufactured to meet the structural
requirements of Underwriters Laboratories (UL) Standard 1316.
(III) Professionally engineered plans
demonstrating compliance to tank configuration requirements of this rule
including acceptable structural calculations or other pertinent data as may be
required.
(B) Each inlet
or outlet tee shall be attached to the tank by a rubber or synthetic rubber
ring seal and compression plate, or in some other manner approved by the
division.
(C) Each tank shall be
installed in accordance with the manufacturer's
recommendations.
(iv)
Each polyethylene tank shall conform to the following:
(A) Each polyethylene tank shall comply with
the criteria for acceptance established in Prefabricated Septic Tanks and
Wastewater Holding Tanks, Can 3-B66-10 by the Canadian Standards Association,
Ontario, Canada.
(B) Each inlet or
outlet tee shall be attached to the tank by a rubber or synthetic rubber ring
seal and compression plate, or in some other manner approved by the
division.
(C) Each tank shall be
installed in accordance with the manufacturer's
recommendations.
(b) Each prefabricated or precast tank that
is commercially manufactured shall be plainly, legibly, and permanently marked
or stamped with:
(i) the manufacturer's name
and address, or nationally registered trademark;
(ii) the liquid capacity of the tank in
gallons on the exterior at the outlet end within 6 inches of the top of the
wall; and
(iii) the inlet and
outlet of all such tanks shall be plainly marked as "IN" or "OUT"
respectively.
(c) Each
inlet, outlet, or tank compartment shall meet the minimum diameter requirements
for building sewers.
(i) Only one inlet or
outlet is allowed, unless preauthorized by the regulatory authority.
(ii) An inlet and outlet shall be located on
opposite ends of each tank.
(A) The invert of
flow line of the inlet shall be located at least 2 inches, above the invert of
the outlet to allow for momentary rise in liquid level during discharge to the
tank.
(B) An approved tank with
offset inlets may be used when approved by the regulatory
authority.
(iii) Each
inlet and outlet shall have a baffle or sanitary tee.
(A) An inlet baffle or sanitary tee of wide
sweep design shall be provided to divert the incoming wastewater downward. This
baffle or tee is to penetrate at least 6 inches below the liquid level, but the
penetration is not to be greater than that allowed for the outlet
device.
(B) For each tank with
vertical sides, the outlet baffle or sanitary tee shall extend below the liquid
surface a distance equal to about 40% of the liquid depth. For each horizontal
cylindrical tank or tank of any other shape, that distance shall be reduced to
about 35% of the liquid depth.
(C)
Each baffle shall be constructed from sidewall to sidewall or shall be designed
as a conduit.
(D) Each sanitary tee
shall be permanently fastened in a vertical, rigid
position.
(iv) Each inlet
and outlet pipe connection to the septic tank shall be sealed and adhere to the
tank and pipe to form a watertight connection with a bonding compound or
sealing ring.
(v) Any inlet or
outlet device may not include any design feature preventing free venting of
gases generated in the tank or absorption system back through the roof vent in
the building plumbing system. The top of each baffle or sanitary tee shall
extend at least 6 inches above the liquid level to provide scum storage, but no
closer than 1 inch to the inside top of the tank.
(d) Liquid depth of each tank shall be at
least 30 inches. Depth greater than 72 inches may only be considered in
calculating liquid volume required in Subsection
R317-4-6(7) if
the tank length is at least two times the liquid depth.
(e) The maximum burial depth shall be stated
on the plans submitted.
(f) Any
septic tank may be divided into compartments provided the tank meets the
following:
(i) The volume of the first
compartment shall equal or exceed two-thirds of the total required septic tank
volume.
(ii) No compartment may
have an inside horizontal dimension less than 24 inches.
(iii) Each inlet or outlet shall be designed
as specified for tanks, except that when a partition wall is used to form a
multi-compartment tank, an opening in the partition may serve for flow between
compartments provided the minimum dimension of the opening is 4 inches, the
cross-sectional area is not less than that of a 6 inch diameter pipe (28.3
square inches), and the mid-point is below the liquid surface a distance about
equal to 40% of the liquid depth of the tank.
(g) Scum storage volume shall consist of 15%
or more of the required liquid capacity of the tank and shall be provided in
the space between the liquid surface and the top of inlet and outlet
devices.
(h) Adequate access to
each tank shall be provided to facilitate inspection, servicing and
maintenance, and shall have no structure or other obstruction placed over it
and shall conform to the following requirements:
(i) Access to each compartment of any tank
shall be provided through properly placed manhole openings not less than 18
inches in diameter, in minimum horizontal dimension or by an easily removable
lid section.
(ii) Each access cover
shall be designed and constructed in such a manner that it may not pass through
the access openings, and when closed shall be child-proof and prevent entrance
of surface water, dirt, or other foreign material, and seal the odorous gases
in the tank. Each concrete access cover for a manhole opening shall have
adequate handles.
(iii) Access to
each inlet or outlet device shall be provided through a properly spaced opening
not less than 12 inches in minimum horizontal dimension or by an easily
removable lid section.
(2) Appendix B. Pressure Distribution, Pumps,
Controls, and Alarms.
(a) Each absorption
system designed to use pressure distribution shall conform to the following:
(i) Pressure distribution design shall
generally be based on the Utah Guidance for Performance, Application, Design,
Operation and Maintenance: Pressure Distribution Systems document with the
following exceptions:
(A) Design and equipment
shall emphasize ease of maintenance, longevity, and reliability of components
and shall be proven suitable by operational experience, test, or analysis,
acceptable to the regulatory authority.
(B) Electrical disconnects shall be provided
that are appropriate for the installation and shall have gas-tight junction
boxes or splices. Each electrical component used in an onsite wastewater system
shall comply with applicable requirements of the State of Utah Electrical
Code.
(C) Each component shall be
constructed and installed to facilitate ease of service without having to alter
any other part.
(ii)
Before final approval for operation, each pump, control and related apparatus
shall be field tested and found to operate as designed.
(A) When a duplex pump system is designed,
controls shall be provided that an alarm shall signal when one of the pumps
malfunctions.
(B) Where multiple
pumps are operated in series, controls shall be installed to prevent the
operation of a pump or pumps preceding a station that experiences a high level
alarm event.
(C) Controls shall be
capable of controlling all functions incorporated or required in the design of
the system.
(I) The control panel for each
pressure distribution system shall include a pump run-time hour meter and a
pump event counter or other acceptable flow measurement method.
(II) The control panel shall be installed
within sight of the access risers. An other location may be approved by the
regulatory authority.
(III)
Supporting hydraulic calculations and pump curve analysis shall be submitted to
the regulatory authority with the design.
(3) Appendix C. Soil
Exploration Pits, Soil Logs, Soil Evaluations.
(a) Soil conditions shall be obtained from a
soil exploration pit dug to a depth of 10 feet in the absorption area, or to
the ground water table if it is shallower than 10 feet below ground surface. If
an absorption system excavation will be deeper than 6 feet, the soil
exploration pit shall extend to a depth of at least 4 feet below the bottom of
the proposed absorption system excavation. Each soil exploration pit shall be
constructed in a manner to reduce potential for physical injury. One end of
each pit should be sloped gently or "stair-stepped" to permit easy entry if
necessary.
(b) The soil log shall
contain the following information.
(i) A
signed statement certifying that the log was evaluated and recorded in
accordance with this rule.
(ii) The
names of all qualified individuals per Rule R317-11 conducting the
tests.
(iii) The location of the
property.
(iv) The location of the
soil exploration pit on the property.
(v) The date of the log.
(vi) A description and depths of the soil
horizons throughout the soil exploration pit to include:
(A) soil texture and structure using the USDA
system of classification;
(B)
estimated volume percentage of coarse fragments defined as:
(I) "Gravel" means a rock fragment from 0.1
inches to 3 inches in diameter;
(II) "Cobble" means rock fragment from 3
inches to 10 inches in diameter;
(III) "Stone" means a rock fragment greater
than 10 inches in diameter;
(C) the presence and abundance of mottling
defined as:
(I) "Few" when less than 2% of the
exposed surface is occupied by mottles;
(II) "Common" when from 2% to 20% of the
exposed surface is occupied by mottles; and
(III) "Many" when more than 20% of the
exposed surface is occupied by mottles;
(D) depth to groundwater or bedrock, if
encountered, and maximum anticipated groundwater table; and
(E) any other pertinent
information.
(c) Soils shall be evaluated using the USDA
Soil Texture Classification method. The soil horizon with the lowest loading
rate shall be used in calculating the required absorption
area.
(4) Appendix D.
Percolation Method.
(a) Each percolation test
shall be completed by an individual certified per Rule R317-11 and shall be
conducted in accordance with the instructions in this appendix.
(b) When a percolation test is conducted, the
test shall be conducted at a point and elevation selected as typical of the
area in which the absorption system shall be located.
(c) Percolation test results shall be
submitted on a signed "Percolation Test Certificate". The test certificate
shall contain the following:
(i) A signed
statement certifying that the test was conducted in accordance with this
rule.
(ii) The names of all
individuals per Rule R317-11 conducting the test.
(iii) The location of the property.
(iv) The location of the percolation test on
the property.
(v) The depth to the
bottom of the percolation test hole from the existing grade.
(vi) The final stabilized percolation rate of
each test in minutes per inch.
(vii) The date of the test.
(viii) Any other pertinent
information.
(d) Each
percolation test shall be conducted at the owner's expense and in accordance
with the following:
(i) A percolation test may
not be conducted in any test hole that extends into ground water, bedrock, or
frozen ground. Where shrink-swell clays, fissured soil formations, or saprolite
is encountered, each test shall be made under the direction of the regulatory
authority.
(ii) Since the
appropriate percolation test depth depends on the soil conditions at a specific
site, the percolation test shall be conducted only after the soil exploration
pit has been dug and examined for suitable and porous strata and ground water
table information. Percolation test results should be related to the soil
conditions found.
(iii) Each
percolation test hole should begin in a specially prepared larger excavation,
preferably made with a backhoe, of sufficient size that extend to a depth about
6 inches above the strata to be tested.
(iv) Each test hole shall be dug or bored,
preferably with hand tools such as shovels or augers, and shall have horizontal
dimensions ranging from 4 to 18 inches, preferably 8 to 12 inches. The vertical
sides shall be at least 12 inches deep, terminating in the soil at an elevation
6 inches below the bottom of the proposed onsite wastewater system. In testing
individual soil strata for deep wall trenches and seepage pits, the percolation
test hole shall be located entirely within the strata to be tested, if
possible.
(v) Each percolation test
hole shall be properly prepared. Carefully remove any smeared soil surfaces to
provide an open, natural soil interface into that water may percolate. Remove
all loose soil from the bottom of the hole. Add 2 to 3 inches of clean pea
gravel to protect the bottom from scouring or sealing with sediment when water
is added. Caving or sloughing in some test holes can be prevented by placing in
the test hole a wire cylinder or perforated pipe surrounded by clean pea
gravel.
(vi) Adequate saturation
and swelling of the soil shall be completed. It is important to distinguish
between saturation and swelling. Saturation means that the void spaces between
soil particles are full of water. This can be accomplished in a relatively
short period. Swelling is a soil volume increase caused by intrusion of water
into the individual soil particles. This is a slow process, especially in
clay-type soil, and is the reason for requiring a prolonged swelling
period.
(vii) Water should be
placed carefully into the test hole using a small diameter siphon hose or other
suitable method to prevent washing down the side of the hole.
(viii) Necessary equipment for measuring the
percolation rate should consist of a tape measure with at least 1/16 inch
calibration or float gauge, and a time piece or other suitable equipment. All
measurements shall be made from a fixed reference point near the top of the
test hole to the surface of the water.
(ix) Each percolation test shall follow a
consistent procedure. The hole shall be carefully filled with clear water and a
minimum depth of 12 inches shall be maintained above the gravel for at least a
four hour period by refilling when necessary. Water remaining in the hole after
four hours may not be removed. Immediately following the saturation period, the
soil shall be allowed to swell not less than 16 hours or more than 30 hours.
Immediately following the soil swelling period, the percolation rate
measurements shall be made as follows:
(A) Any
soil that has sloughed into the hole shall be removed and water shall be
adjusted to 6 inches over the gravel.
(B) Thereupon, from the fixed reference
point, the water level shall be measured and recorded at about 30 minute
intervals for a period of four hours.
(I) If
6 inches of water seeps away in less than 30 minutes, a shorter time interval
of 15 minutes between measurements may be used.
(II) If 6 inches of water seeps away in less
than 15 minutes, a shorter time interval of 5 minutes between measurements may
be used.
(III) Eight consecutive
time intervals shall be recorded unless two successive water level drops do not
vary more than 1/16 of an inch and show that an approximate stabilized rate has
been obtained.
(C) The
hole shall be filled with 6 inches of clear water above the gravel after each
time interval.
(D) In no case may
the water depth exceed 6 inches above the gravel.
(E) The final water level drop shall be used
to calculate the percolation rate. If no stabilized rate is achieved, the
smallest drop shall be used to make this calculation.
(F) Precautions shall be taken to prohibit
water or soil from freezing during the test procedure.
(x) The percolation test procedure for Type 1
or Type 2 soils shall follow a separate procedure. The hole shall be carefully
filled with clear water to a minimum depth of 12 inches over the gravel and the
time for this amount of water to seep away shall be determined. The procedure
shall be repeated and if the water from the second filling of the hole at least
12 inches above the gravel seeps away in 10 minutes or less, the test may
proceed immediately as follows:
(A) Water
shall be added to a point not more than 6 inches above the gravel.
(B) Thereupon, from the fixed reference
point, water levels shall be measured at 10 minute intervals for a period of
one hour.
(I) If 6 inches of water seeps away
in less than 10 minutes, a shorter time interval of 5 minutes between
measurements may be used.
(II) Six
consecutive time intervals shall be recorded unless two successive water level
drops do not vary more than 1/16 of an inch and show that an approximate
stabilized rate has been obtained.
(C) The hole shall be filled with 6 inches of
clear water above the gravel after each time interval.
(D) In no case shall the water depth exceed 6
inches above the gravel.
(E) The
final water level drop shall be used to calculate the percolation rate. If no
stabilized rate is achieved, the smallest drop shall be used to make this
calculation.
(xi) The
percolation rate is equal to the time elapsed in minutes for the water column
to drop, divided by the distance the water dropped in inches and fractions
thereof.
(xii) The minimum or
slowest percolation rate shall be used in calculating the required absorption
area.
(5)
Appendix E. Septic Tank Operation and Maintenance.
(a) Each septic tank shall be emptied before
too much sludge or scum is allowed to accumulate and seriously reduce the tank
volume settling depth. If either the settled solids or floating scum layer
accumulate too close to the bottom of the outlet baffle or bottom of the
sanitary tee pipe in the tank, solid particles may overflow into the absorption
system and eventually clog the soil and ruin its absorption capacity.
(b) A septic tank that receives normal
loading should be inspected as stated in Section
R317-4-11 to determine if it
needs emptying. Although there are wide differences in the rate that sludge and
scum accumulate in tanks, a septic tank for a private residence requires
emptying every three to five years. Actual measurement of scum and sludge
accumulation is the only sure way to determine when a tank needs to be emptied.
Experience for a particular system may show the desirability of longer or
shorter intervals between inspections.
(c) The tank should be completely emptied if
either the bottom of the floating scum mat is within 3 inches of the bottom of
the outlet baffle or tee or the sludge level has built up to about 12 inches
from the bottom of the outlet baffle or tee, or the scum and sludge layers
together equal 40% or more of the tank volume. All scum and solids should be
washed out and removed from the tank.
(d) If multiple tanks or tanks with multiple
compartments are provided, care should be taken to ensure that each tank or
compartment is inspected and emptied.
(e) Septic tank wastes contain disease
causing organisms and shall be disposed of only in areas and in a manner that
is acceptable to local health authorities and consistent with state
rules.
(f) Immediate replacement of
any damaged inlet or outlet fitting in the septic tank is essential for
effective operation of the system.
(g) Remove any effluent screen or filter in a
manner that prevents solids from passing to the absorption system. Wash the
filter over the inlet side of septic tank. Replace the cleaned filter back into
the outlet tee.
(h) When the tank
is empty, the interior surfaces of the tank should be inspected for leaks or
cracks using a strong light.
(i) A
written record of any maintenance of the septic tank and absorption system
should be kept by the owner of that system.
(j) The functional operation of a septic tank
is not improved by the addition of yeasts, disinfectants, additives or other
chemicals; therefore, use of these materials is not recommended.
(k) The advice of the regulatory authority
should be sought before chemicals arising from a hobby or home industry or
other unusual activities are discharged into a septic tank system.
(l) Economy in the use of water helps prevent
overloading of a septic tank system that could shorten its life and require
expensive repairs. The plumbing fixtures in the building should be checked
regularly to repair any leaks that can add substantial amounts of water to the
system. Industrial wastes and other liquids that may adversely affect the
operation of the onsite wastewater system should not be discharged into such a
system. Paper towels, facial tissue, disinfectant wipes, newspaper, wrapping
paper, disposable diapers, sanitary napkins, coffee grounds, rags, sticks, and
similar materials should also be excluded from the septic tank since they do
not readily decompose and can lead to clogging of both the plumbing and the
absorption system.
(m) Any
measurable amount of sludge or scum present in any other tank should be
removed. If an effluent screen or filter is present, it should be cleaned over
the inlet side of the septic tank.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.