Utah Admin. Code R432-11-2 - General Construction
(1) The licensee
shall additionally comply with Section
R432-4-19 and ensure compliance
with the following modifications:
(a)
corridors in patient use areas are a minimum of eight feet wide;
(b) handrails are provided on both sides of
corridors and hallways used by patients that are 34 inches above the floor,
except for areas serving children and other special care areas; and
(c) fixtures in a resident toilet and
bathroom are wheelchair accessible with wheelchair turning space within the
room.
(2) The licensee
shall provide the following:
(a) plumbing,
including medical gas and suction systems;
(b) an emergency electrical
service;
(c) an onsite emergency
generator connected to the recommended services in the plans review required in
Section R432-4-12;
(d) telephone;
(e) nurse call;
(f) heating equipment necessary to provide
adequate heated space to house all patients under emergency
conditions;
(g) one duplex
receptacle in each patient room;
(h) one duplex receptacle at each nurse
station;
(i) duplex receptacles in
the emergency heated area at a ratio of one for each ten patients;
and
(j) fuel storage capacity that
permits continuous operation for at least 48 hours.