Utah Admin. Code R432-12-22 - Electrical Systems
(1) The licensee
shall ensure:
(a) electrical materials are
tested and approved by Underwriters Laboratory;
(b) electrical installations, including alarm
and nurse call systems, if required, are tested to demonstrate that equipment
installation and operation is as intended and appropriate; and
(c) a written record of performance tests of
special electrical systems and equipment shows compliance with applicable
codes.
(2) The licensee
shall ensure that switchboards and power panels comply with the following:
(a) the main switchboard is located in an
area separate from plumbing and mechanical equipment and is accessible only to
authorized persons;
(b)
switchboards are convenient for use, readily accessible for maintenance, clear
of traffic lanes, and located in a dry, ventilated space;
(c) overload protection devices operate
properly in the ambient room temperatures, except for existing Level IV
facilities; and
(d) switchboards
serving normal lighting and appliance circuits are located on the same floor as
the circuits they serve.
(3) The licensee shall ensure lighting
complies with the following:
(a) any spaces
within buildings that house people, machinery, equipment, or approaches to
buildings have fixtures for lighting that are compliant with Table 4;
and
(b) resident rooms have:
(i) general and night lighting;
(ii) a reading light for each
resident;
(iii) flexible light
arms, if used, that are mechanically controlled to prevent the bulb from coming
in contact with bed linen;
(iv) at
least one night light fixture is controlled at the entrance to each resident
room; and
(v) any controls for
lighting in resident areas operate quietly.
(4) The licensee shall ensure:
(a) parking lots have fixtures for lighting
to provide light at levels recommended in the plans review Section
R432-4-12; and
(b) corridor lighting is adjustable so that
light levels may be reduced at night and still provide a maximum brightness
ratio of 1:10.
(5)
Lighting levels shown in Table 4 are used as minimum standards and do not
preclude the use of higher levels that may be needed to ensure the health and
safety of the specific facility population served.
(6) values in Table 4 are the minimum
maintained average illuminance measured at the task plane.
|
TABLE 4 SMALL HEALTH CARE FACILITIES LIGHTING STANDARDS |
||
|
MINIMUM FOOT-CANDLES (one lumen per square foot) |
||
|
Physical Plan Area |
Level I, II, III Facilities |
Level IV Facilities |
|
Corridors |
||
|
Day |
20 |
15 |
|
Night |
10 |
10 |
|
Exits |
20 |
20 |
|
Stairways |
20 |
20 |
|
Nursing Station |
||
|
General |
30 |
30 |
|
Charting |
75 |
75 |
|
Med. Prep. |
75 |
75 |
|
Pt./Res. Room |
||
|
General |
10 |
10 |
|
Reading/Mattress Level |
30 |
30 |
|
Toilet area |
30 |
30 |
|
Lounge |
||
|
General |
10 |
10 |
|
Reading |
30 |
30 |
|
Dining |
30 |
30 |
|
Laundry |
30 |
30 |
(6)
The licensee shall ensure that each resident room has duplex grounding type
receptacles as follows:
(a) one located on
each side of the head of each bed;
(b) one for television, if used;
and
(c) one on each other
wall.
(7) The licensee
may omit receptacles from exterior walls where construction would make
installation impractical.
(8) The
licensee shall ensure that duplex grounded receptacles for general use are
installed in any corridors.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.